62-61753-21
7-19
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
24
COMPRESSION RATIO EXCEEDED
TRIGGER ON: If the compressor compression ratio is greater than 21 for 20 seconds.
UNIT CONTROL:
Engine operation: Engine and unit shutdown and alarm.
Standby operation: Refrigeration system shutdown and alarm with PSCON
still energized.
RESET CONDITION: Auto reset when compression ratio is less than 21 for 3 minutes or,
alarm may be manually reset via keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Look for high discharge or low suc-
tion pressure causes.
Discharge and suction pressures must be in normal
range for the current ambient and refrigerated com-
partment temperature conditions. Refer to Abnormal
Pressure Trouble Shooting Section 9.4.7.
Summary of Contents for NDK33BN0KB
Page 2: ......
Page 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Page 4: ......
Page 14: ......
Page 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Page 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Page 30: ...62 61753 21 2 6...
Page 48: ......
Page 212: ......
Page 226: ......
Page 248: ......
Page 252: ......
Page 262: ......
Page 270: ......