2

!

WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death or property damage.
Before installing, modifying, or servicing system, main electrical

disconnect switch must be in the OFF position and install a

lockout tag. There may be more than one disconnect switch.

Lock out and tag switch with a suitable warning label. Verify

proper operation after servicing.

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage or

improper operation.
Do NOT use this kit with furnaces with an input of 26,000

BTUH; the unit will be severely over

fired. This could result in

flame roll

out, sooting or premature heat exchanger failure.

This instruction covers the installation of gas conversion to

convert the following furnaces from Propane gas usage to natural

gas usage. See appropriate section for your furnace type.

Section 1

 

 Models 59SC2, 59SP2, 59SC5, 59SE5, 59SP5,

912S, 915S, 922S, 925S, and PG92S are 4

Way Multipoise, Hot

Surface Ignition, Condensing Furnaces with 40,000 to 120,000

btuh gas input rates. Models 59SC5, 915S, and PG95S are

4

Way Multipoise, Hot Surface Ignition, Condensing Furnaces

with  40,000 to 140,000 btuh gas input rates.

Section 2

 

 Models 58DL, 58PH, 58ST, 310A, 310J, 311A, 311J,

313A, 313J, PG8MA, PG8JA, PG8ME, and PG8JE 33.3

Inch

High, Induced

 Combustion, Hot

Surface Ignition, Single

Stage,

Non

 Condensing 4

Way Multipoise Furnaces with 42,000 to

154,000 btuh gas input rates.

DESCRIPTION AND USAGE

See 

Table 1

 for kit contents. This kit is designed for use in the

furnaces listed in 

Table 2

 and 

Table 4

To accommodate many

different furnace models, more parts are shipped in kit than will

be needed to complete conversion. When installation is

complete, discard extra parts.

Table 1

NAHD00901NG Contents

COMPONENT

NUMBER

QTY

DESCRIPTION

 EF39ZW037

1

VALVE CVRSN KIT W/R SPRING 92­0935

 323267-701

1

PARTS ASSY #42

 323267-702

1

PARTS ASSY #43

 323267-703

1

PARTS ASSY #44

 323267-704

1

PARTS ASSY #45

 339851-701

1

LABEL KIT

 339851-702

1

LABEL KIT

 319965-448

1

LABEL,SHIPPING

 AG-KGBPN1SP-XX

1

INSTR GAS CVRSN LP TO NAT

 CA64AS001

1

PLUG, PIPE

SECTION 1

CONDENSING FURNACES

Table 2

MODEL NUMBERS BEGINNING WITH:

59SC2

59SC5

59SE5

59SP2

59SP5

912S

915S

922S

925S

PG92S

PG95S

*   Except 26,000 BTUH models.

INSTALLATION

1. Set room thermostat to lowest setting or “OFF”
2. Disconnect power at external disconnect, fuse or circuit

breaker.

3. Turn off gas at external shut

off or gas meter.

4. Remove outer doors and set aside.
5. Turn electric switch on gas valve to OFF.

MANIFOLD/ORIFICE/BURNER

REMOVAL

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage or

improper operation.

Label all wires prior to disconnection when servicing controls.

!

PRUDENCE

D’EQUIPEMENT D’OPERATION

Toute erreur de câblage peut être une source de danger et de

panne.

Lors des opérations d’entretien des commandes, étiqueter tous

les fils avant de les déconnecter.

Figure 1

Representative Furnace Drawing

REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.

A170154

RATING PLATE NOT SHOWN

(LOCATED ON BLOWER DOOR)

GAS VALVE

MAIN LIMIT SWITCH

(BEHIND GAS VALVE)

REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.

ELECTRICAL JUNCTION

BOX (IF REQUIRED, 
LOCATION MAY VARY)

MEDIA CABINET

OPERATING INSTRUCTIONS

NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE 

OPERATING INSTRUCTIONS 

INSIDE DOOR FIGURE).

FURNACE

CONTROL
BOARD

MANUAL RESET

ROLLOUT SWITCH

FLAME

SENSOR

MANUAL RESET

ROLLOUT SWITCH

GAS BURNER

HOT SURFACE

IGNITER

INDUCER MOTOR

ASSEMBLY

BLOWER AND

MOTOR

CAPACITOR/

POWER CHOKE
(IF USED)

BLOWER DOOR

SAFETY SWITCH

1. Disconnect the gas pipe from gas valve and remove pipe

from the furnace casing. See 

Figure 1

.

Use a back

up wrench on the gas valve to prevent the valve

from rotating on the manifold or damaging the mounting to the

burner box. See 

Figure 2

 and 

Figure 3

.

Summary of Contents for KGBPN42011SP

Page 1: ...n perform basic maintenance functions such as cleaning and replacing air filters Trained service personnel must perform all other operations When working on heating equipment observe precautions in th...

Page 2: ...ZW037 1 VALVE CVRSN KIT W R SPRING 92 0935 323267 701 1 PARTS ASSY 42 323267 702 1 PARTS ASSY 43 323267 703 1 PARTS ASSY 44 323267 704 1 PARTS ASSY 45 339851 701 1 LABEL KIT 339851 702 1 LABEL KIT 319...

Page 3: ...in yearly specific gravity average for local gas supply 3 Find installation altitude in Table 3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest...

Page 4: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3...

Page 5: ...625 43 3 7 42 3 2 42 3 3 42 3 4 650 43 3 5 43 3 6 43 3 7 43 3 8 675 44 3 7 44 3 8 43 3 4 43 3 5 10000 700 44 3 4 44 3 5 44 3 7 44 3 8 3048 725 44 3 2 44 3 3 44 3 4 44 3 5 Orifice numbers shown in BOLD...

Page 6: ...stment screw 5 Remove the Propane regulator spring white 6 Install the natural gas regulator spring silver 7 Install the regulator adjustment screw 8 Turn the adjusting screw clockwise in 8 5 full tur...

Page 7: ...its splice connection with the yellow wire of the furnace wire harness Disconnect and discard this orange wire and the splice connection c Connect the yellow wire of the furnace wire harness see b abo...

Page 8: ...3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest natural gas heat value and specific gravity in Table 3 5 Follow heat value line and specific...

Page 9: ...tion instructions Figure 12 Conversion Rating Plate Label A13070 LABEL APPLICATION 1 Fill in Conversion Responsibility Label 339851 205 and apply over Propane Conversion Responsibility Label Date name...

Page 10: ...amage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which could result in personal inju...

Page 11: ...fore installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than one disconnect switch Lock out and tag swit...

Page 12: ...er burner Low NOx models in downflow or horizontal positions must use Table 6 21 000 Btuh per burner See input listed on rating plate Use Table 5 22 000 Btuh per burner for models 58DLA 58PHA 58PHB 58...

Page 13: ...44 3 4 44 3 5 43 3 2 U S A 2001 to 3000 610 to 914 800 42 3 4 42 3 5 42 3 6 42 3 7 825 42 3 2 42 3 3 42 3 4 42 3 5 850 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43...

Page 14: ...25 43 2 9 43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 U S A 700...

Page 15: ...4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 U S A 3001 to 4000 914 to 1219...

Page 16: ...8 43 2 9 650 43 2 5 43 2 5 43 2 6 43 2 7 675 43 2 3 43 2 4 43 2 4 43 2 5 700 43 2 1 43 2 2 43 2 3 43 2 3 725 48 3 7 43 2 0 43 2 1 43 2 2 750 48 3 5 48 3 6 48 3 7 43 2 0 U S A 9001 to 10 000 2743 to 3...

Page 17: ...itch Lock out and tag switch with a suitable warning label Verify proper operation after servicing For J and G valves See Figure 24 1 Be sure gas and electrical supplies to furnace are off 2 Remove ca...

Page 18: ...re than one disconnect switch Lock out and tag switch with a suitable warning label Verify proper operation after servicing 1 Be sure main gas and electric supplies to furnace are off 2 Remove Low Gas...

Page 19: ...ressure tap on gas valve 2 Turn on furnace power supply 3 Turn gas supply manual shutoff valve to ON position 4 Turn furnace gas valve switch to ON position 5 Jumper R W thermostat connections on cont...

Page 20: ...ition 7 Jumper R and W thermostat connections to call for heat See Figure 13 8 Check manifold orifices for gas leaks when main burners ignite 9 Adjust gas manifold pressure Refer to Table 5 or Table 6...