background image

19

Figure 25

80% Low Gas Pressure Switch

L13F014

2” Brass Nipple

Low Gas
Pressure Switch

Female x Female x Male Tee

1/8” NPT Pipe Plug
For inlet pressure tap

Re

install pipe

plug after removal

INSTALL MANIFOLD

1. Refer to 

Figure 14

 and 

Figure 15

.

2. Align the orifices in the manifold assembly with the support

rings on the end of the burner.

3. Insert the orifices in the support rings of the burners.

Manifold mounting tabs should fit flush against the burner

box.

If manifold does not fit flush against the burner box, the burners
are not fully seated forward. Remove the manifold and check
burner positioning in the burner box assembly.

4. Attach the green/yellow wire and ground terminal to one of

the manifold mounting screws.

5. Install the remaining manifold mounting screws.
6. Connect the wires to the flame sensor and hot surface

igniter.

7. Connect the connector harness to gas valve.
8. Rewire unit low pressure switch (LPS) as follows:

a. Trace one of the orange wires previously disconnected

from the LGPS back to the NO terminals of the LPS.

b. Trace the other orange wire previously disconnected

from the LGPS back to its splice connection with the

yellow wire of the furnace wire harness. Disconnect

and discard this orange wire and the splice connection.

c. Connect the yellow wire of the furnace wire harness

(see “b” above) to the NO terminal of the LPS.

d. Refer to the furnace wiring diagram to ensure proper

location of wires.

Use only Propane-resistant pipe dope. DO NOT use Teflon tape.

9. Insert the gas pipe through the grommet in the casing.

Apply a thin layer of pipe dope to the threads of the pipe

and thread the pipe by into the gas valve.

Use a back-up wrench on the gas valve to prevent the valve from
rotating on the manifold or damaging the mounting to the burner
box.

10.  With a back-up wrench on the inlet boss of the gas valve,

finish tightening the gas pipe to the gas valve.

11. Turn gas on at electric switch on gas valve.

CHECK INLET GAS PRESSURE

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage.
DO NOT operate furnace more than one minute to check inlet

gas pressure, as conversion is not complete at this time.

This kit is to be used only when inlet gas pressure is between

4.5

in. w.c. and 13.6

in. w.c.

1. Verify manometer is connected to inlet pressure tap on gas

valve.

2. Turn on furnace power supply.

3. Turn gas supply manual shutoff valve to ON position.
4. Turn furnace gas valve switch to ON position.
5. Jumper R

W thermostat connections on control.

6. When main burners ignite, confirm inlet gas pressure is

between 4.5

in. w.c. and 13.6

in. w.c.

7. Remove jumper across R

W thermostat connections to

terminate call for heat.

8. Turn furnace gas valve switch to OFF position.
9. Turn gas supply manual shutoff valve to OFF position.

10. Turn off furnace power supply.

11. Remove manometer.

12. Apply pipe dope sparingly to the 1/8 in. (3 mm) NPT pipe

plug and install in the 1/8 in. (3 mm) tapped inlet pressure

tap opening in the gas valve. DO NOT over

tighten. Check

for gas leaks after gas supply has been turned on.

CHECK FURNACE AND MAKE

ADJUSTMENTS

!

WARNING

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could result in personal injury

and/or death.
NEVER test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for the

detection of leaks to check all connections. A fire or explosion

may result causing property damage, personal injury or loss of

life.

!

AVERTISSEMENT

RISQUE D’EXPLOSION ET D’INCENDIE

Le fait de ne pas suivre cet avertissement pourrait entraîner

des dommages corporels et / ou la mort.
Ne jamais examiner pour les fuites de gaz avec une flamme

vive. Utilisez plutôt un savon fait specifiquement pour la

détection des fuites de gaz pour verifier tous les connections.

Un incendie ou une explosion peut entrainer des dommages

matériels, des blessures ou la mort.

!

WARNING

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury,

death or property damage.
Gas supply MUST be shut off before disconnecting electrical

power and proceeding with conversion.

!

WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death or property damage.
Before installing, modifying, or servicing system, main electrical

disconnect switch must be in the OFF position and install a

lockout tag. There may be more than one disconnect switch.

Lock out and tag switch with a suitable warning label. Verify

proper operation after servicing.

1. Be sure main gas and electric supplies to furnace are off.
2. Remove 1/8-in. NPT pipe plug from manifold pressure tap

on downstream side of gas valve.

3. Attach manometer to manifold pressure tap on gas valve.

See 

Figure 24

.

4. Turn gas supply manual shutoff valve to ON position.

Summary of Contents for KGBPN42011SP

Page 1: ...n perform basic maintenance functions such as cleaning and replacing air filters Trained service personnel must perform all other operations When working on heating equipment observe precautions in th...

Page 2: ...ZW037 1 VALVE CVRSN KIT W R SPRING 92 0935 323267 701 1 PARTS ASSY 42 323267 702 1 PARTS ASSY 43 323267 703 1 PARTS ASSY 44 323267 704 1 PARTS ASSY 45 339851 701 1 LABEL KIT 339851 702 1 LABEL KIT 319...

Page 3: ...in yearly specific gravity average for local gas supply 3 Find installation altitude in Table 3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest...

Page 4: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3...

Page 5: ...625 43 3 7 42 3 2 42 3 3 42 3 4 650 43 3 5 43 3 6 43 3 7 43 3 8 675 44 3 7 44 3 8 43 3 4 43 3 5 10000 700 44 3 4 44 3 5 44 3 7 44 3 8 3048 725 44 3 2 44 3 3 44 3 4 44 3 5 Orifice numbers shown in BOLD...

Page 6: ...stment screw 5 Remove the Propane regulator spring white 6 Install the natural gas regulator spring silver 7 Install the regulator adjustment screw 8 Turn the adjusting screw clockwise in 8 5 full tur...

Page 7: ...its splice connection with the yellow wire of the furnace wire harness Disconnect and discard this orange wire and the splice connection c Connect the yellow wire of the furnace wire harness see b abo...

Page 8: ...3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest natural gas heat value and specific gravity in Table 3 5 Follow heat value line and specific...

Page 9: ...tion instructions Figure 12 Conversion Rating Plate Label A13070 LABEL APPLICATION 1 Fill in Conversion Responsibility Label 339851 205 and apply over Propane Conversion Responsibility Label Date name...

Page 10: ...amage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which could result in personal inju...

Page 11: ...fore installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than one disconnect switch Lock out and tag swit...

Page 12: ...er burner Low NOx models in downflow or horizontal positions must use Table 6 21 000 Btuh per burner See input listed on rating plate Use Table 5 22 000 Btuh per burner for models 58DLA 58PHA 58PHB 58...

Page 13: ...44 3 4 44 3 5 43 3 2 U S A 2001 to 3000 610 to 914 800 42 3 4 42 3 5 42 3 6 42 3 7 825 42 3 2 42 3 3 42 3 4 42 3 5 850 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43...

Page 14: ...25 43 2 9 43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 U S A 700...

Page 15: ...4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 U S A 3001 to 4000 914 to 1219...

Page 16: ...8 43 2 9 650 43 2 5 43 2 5 43 2 6 43 2 7 675 43 2 3 43 2 4 43 2 4 43 2 5 700 43 2 1 43 2 2 43 2 3 43 2 3 725 48 3 7 43 2 0 43 2 1 43 2 2 750 48 3 5 48 3 6 48 3 7 43 2 0 U S A 9001 to 10 000 2743 to 3...

Page 17: ...itch Lock out and tag switch with a suitable warning label Verify proper operation after servicing For J and G valves See Figure 24 1 Be sure gas and electrical supplies to furnace are off 2 Remove ca...

Page 18: ...re than one disconnect switch Lock out and tag switch with a suitable warning label Verify proper operation after servicing 1 Be sure main gas and electric supplies to furnace are off 2 Remove Low Gas...

Page 19: ...ressure tap on gas valve 2 Turn on furnace power supply 3 Turn gas supply manual shutoff valve to ON position 4 Turn furnace gas valve switch to ON position 5 Jumper R W thermostat connections on cont...

Page 20: ...ition 7 Jumper R and W thermostat connections to call for heat See Figure 13 8 Check manifold orifices for gas leaks when main burners ignite 9 Adjust gas manifold pressure Refer to Table 5 or Table 6...

Reviews: