background image

20

5. Turn furnace gas valve switch to ON position.

6. Check all threaded pipe connections for gas leaks.

7. Turn on furnace power supply.

GAS INPUT RATE INFORMATION

See furnace rating plate for input rate. The input rate for natural

gas is determined by manifold pressure and orifice size.

Determine natural gas orifice size and manifold pressure for

correct input at installed altitude by using 

Table 5

 or 

Table 6

.

All models in all positions except Low NOx models in downflow

and horizontal positions use 

Table 5

 (22,000 Btuh per burner).

Low NOx models in downflow or horizontal positions must use

Table 6

 (21,000 Btuh per burner). See input listed on rating plate.

1. Obtain yearly heat

value average (at installed altitude) for

local gas supply.

2. Obtain yearly specific

gravity average for local gas supply.

3. Find installation altitude in  

Table 5

 or 

Table 6

.

For Canada altitudes of 2000 to 4500 ft., use U.S.A. Altitudes of

2001 to 3000 ft. in  

Table 5

 or 

Table 6

.

4. Find closest natural gas heat value and specific gravity in 

Table 5

 or 

Table 6

.

5. Follow heat

value line and specific

gravity line to point of

intersection to find orifice size and manifold pressure

setting.

The gas valve must be set for Low Heat first and then set for

High heat on two

stage and variable

speed furnaces. Furnace

gas input rate on rating plate is for installations at altitudes up to

2000 ft. (610 M).

In the U.S.A.

; the input rating for altitudes above 2000 ft. (610M)

must be reduced by 4 percent for each 1000 ft. (305 M) above

sea level.

In Canada

; the input rating must be derated by 5 percent for

altitudes of 2000 ft. (610 M) to 4500 ft. (1372 M) above sea level.

The Conversion Kit Rating Plate accounts for high altitude

derate.

SET GAS INPUT RATE

1. Make sure the gas supply is turned off to the furnace and

at the electric switch on the gas valve.

2. Remove the 1/8 in. (3 mm) NPT plug from the outlet

pressure tap on the gas valve.

3. Connect a manometer to the outlet pressure tap on gas

valve.

4. Turn on furnace power supply.

5. Turn gas supply manual shutoff valve to ON position.

6. Turn furnace gas valve switch to ON position.

7. Jumper R and W thermostat connections to call for heat.

(See 

Figure 13

)

8. Check manifold orifices for gas leaks when main burners

ignite.

9. Adjust gas manifold pressure. Refer to 

Table 5

 or 

Table 6

.

10. Remove cap that conceals the adjustment screw for the

gas valve regulator.

11. Turn adjusting screw counterclockwise (outwards) to

decrease manifold pressure or clockwise (inwards) to

increase manifold pressure.

Gas valve regulator seal cap MUST be in place when checking

input rate.

12. When correct input is obtained,main burner flame should

be clear blue, almost transparent. Be sure regulator seal

cap is in place when finished. See 

Figure 11

.

13. Remove jumper across R and W thermostat connections

to terminate call for heat.

14. Turn furnace gas valve control switch or control knob to

OFF position.

15. Turn off furnace power supply.
16. Remove manometer and replace manifold pressure tap

plug.

Use Propane gas resistant pipe dope to prevent gas leaks. DO

NOT use Teflon tape.

17. Turn furnace gas valve control switch or control knob to

ON position.

18. Turn on furnace power supply. Set room thermostat to call

for heat.

19. Check manifold pressure tap plug for gas leaks when main

burners ignite.

CHECKOUT

1. Observe unit operation through two complete heating

cycles.

2. See Sequence of Operation in furnace Installation, Start

up and Operating Instructions.

3. Set room thermostat to desired temperature.

After making the required manifold pressure adjustments, check

and adjust the furnace temperature rise per the furnace

installation instructions.

LABEL APPLICATION

1. Fill in Conversion Responsibility Label 339851

205 and

apply over Propane Conversion Responsibility Label.

Date, name, and address of organization making this

conversion are required. See 

Figure 26

.

2. Apply Conversion Rating Plate Label 339851

204 over

Propane Conversion Rating Plate Label. See 

Figure 19

.

3. Apply Gas Control Conversion Label over Propane Label

339851

202 to gas valve. (DO NOT use 339851

203,

which is similar.)

Figure 26

Conversion Responsibility Label

Copyright 2017 CAC / BDP 

D

  7310 W. Morris St. 

D

  Indianapolis, IN  46231

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog  No:  AG-KGBPN1SP-04

    

Replaces:

  AG

KGBPN1SP

03

Edition Date:  08/17

Summary of Contents for KGBPN42011SP

Page 1: ...n perform basic maintenance functions such as cleaning and replacing air filters Trained service personnel must perform all other operations When working on heating equipment observe precautions in th...

Page 2: ...ZW037 1 VALVE CVRSN KIT W R SPRING 92 0935 323267 701 1 PARTS ASSY 42 323267 702 1 PARTS ASSY 43 323267 703 1 PARTS ASSY 44 323267 704 1 PARTS ASSY 45 339851 701 1 LABEL KIT 339851 702 1 LABEL KIT 319...

Page 3: ...in yearly specific gravity average for local gas supply 3 Find installation altitude in Table 3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest...

Page 4: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3...

Page 5: ...625 43 3 7 42 3 2 42 3 3 42 3 4 650 43 3 5 43 3 6 43 3 7 43 3 8 675 44 3 7 44 3 8 43 3 4 43 3 5 10000 700 44 3 4 44 3 5 44 3 7 44 3 8 3048 725 44 3 2 44 3 3 44 3 4 44 3 5 Orifice numbers shown in BOLD...

Page 6: ...stment screw 5 Remove the Propane regulator spring white 6 Install the natural gas regulator spring silver 7 Install the regulator adjustment screw 8 Turn the adjusting screw clockwise in 8 5 full tur...

Page 7: ...its splice connection with the yellow wire of the furnace wire harness Disconnect and discard this orange wire and the splice connection c Connect the yellow wire of the furnace wire harness see b abo...

Page 8: ...3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest natural gas heat value and specific gravity in Table 3 5 Follow heat value line and specific...

Page 9: ...tion instructions Figure 12 Conversion Rating Plate Label A13070 LABEL APPLICATION 1 Fill in Conversion Responsibility Label 339851 205 and apply over Propane Conversion Responsibility Label Date name...

Page 10: ...amage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which could result in personal inju...

Page 11: ...fore installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than one disconnect switch Lock out and tag swit...

Page 12: ...er burner Low NOx models in downflow or horizontal positions must use Table 6 21 000 Btuh per burner See input listed on rating plate Use Table 5 22 000 Btuh per burner for models 58DLA 58PHA 58PHB 58...

Page 13: ...44 3 4 44 3 5 43 3 2 U S A 2001 to 3000 610 to 914 800 42 3 4 42 3 5 42 3 6 42 3 7 825 42 3 2 42 3 3 42 3 4 42 3 5 850 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43...

Page 14: ...25 43 2 9 43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 U S A 700...

Page 15: ...4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 U S A 3001 to 4000 914 to 1219...

Page 16: ...8 43 2 9 650 43 2 5 43 2 5 43 2 6 43 2 7 675 43 2 3 43 2 4 43 2 4 43 2 5 700 43 2 1 43 2 2 43 2 3 43 2 3 725 48 3 7 43 2 0 43 2 1 43 2 2 750 48 3 5 48 3 6 48 3 7 43 2 0 U S A 9001 to 10 000 2743 to 3...

Page 17: ...itch Lock out and tag switch with a suitable warning label Verify proper operation after servicing For J and G valves See Figure 24 1 Be sure gas and electrical supplies to furnace are off 2 Remove ca...

Page 18: ...re than one disconnect switch Lock out and tag switch with a suitable warning label Verify proper operation after servicing 1 Be sure main gas and electric supplies to furnace are off 2 Remove Low Gas...

Page 19: ...ressure tap on gas valve 2 Turn on furnace power supply 3 Turn gas supply manual shutoff valve to ON position 4 Turn furnace gas valve switch to ON position 5 Jumper R W thermostat connections on cont...

Page 20: ...ition 7 Jumper R and W thermostat connections to call for heat See Figure 13 8 Check manifold orifices for gas leaks when main burners ignite 9 Adjust gas manifold pressure Refer to Table 5 or Table 6...

Reviews: