background image

8

10. Turn gas supply manual shutoff valve to OFF position.

11. Turn off furnace power supply.

12. Remove manometer and on some models remove

pressure tap fitting.

13. On some models, apply pipe dope sparingly to the end of

inlet gas pipe plug and install into the unused end of

1/8

in. (3 mm) tee. Or, on some models, tighten set screw

on inlet tower pressure tap with a 3/32

in. hex wrench.

See 

Figure 8

.

CHECK FURNACE AND MAKE

ADJUSTMENTS

!

WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for the

detection of leaks to check all connections. A fire or explosion

may result causing property damage, personal injury or loss of

life.

!

AVERTISSEMENT

RISQUE D’EXPLOSION ET D’INCENDIE

Le non-respect des avertissements de sécurité pourrait

d’entraîner des blessures graves, la mort ou des dommages

matériels.
Ne jamais utiliser une flamme nue por vérifier la présence des

fuites de gaz. Pour la vérification de tous les joints, utiliser

plutôt une solution savonneuse commerciale fabriquée

spécifiquement pur la détection des fuites de gaz. Un incendie

ou une explosion peut entraîner des dommages matériels, des

blessures ou la mort.

1. Be sure main gas and electric supplies to furnace are off.
2. On some models, remove 1/8-in. (3 mm) NPT pipe plug

from manifold pressure tap on outlet end of gas valve. Or,

on some models, loosen set screw on manifold tower

pressure tap no more than one full turn with a 3/32

in. hex

wrench.

3. Attach manometer to manifold pressure tap on gas valve.

(See 

Figure 8

)

4. Turn gas supply manual shutoff valve to ON position.
5. Turn furnace gas valve switch to ON position.

GAS INPUT RATE INFORMATION

See furnace rating plate on blower door for input rate. The input

rate for natural gas is determined by manifold pressure and

orifice size.
Determine natural gas orifice size and manifold pressure for

correct input at installed altitude by using 

Table 3

.

1. Obtain yearly heat

value average (at installed altitude) for

local gas supply.

2. Obtain yearly specific

gravity average for local gas supply.

3. Find installation altitude in 

Table 3

.

For Canada altitudes of 2000 to 4500 ft., use U.S.A. Altitudes of
2001 to 3000 ft. in 

Table 3

.

4. Find closest natural gas heat value and specific gravity in

Table 3

.

5. Follow heat

value line and specific

gravity line to point of

intersection to find orifice size and manifold pressure

setting.

Furnace gas input rate on rating plate is for installations at

altitudes up to 2000 ft. (610 M).

In the U.S.A.

; the input rating for altitudes above 2000 ft. (610M)

must be reduced by 2 percent for each 1000 ft. (305 M) above

sea level.

In Canada

; the input rating must be derated by 5 percent for

altitudes of 2000 ft. (610 M) to 4500 ft. (1372 M) above sea level.
The Conversion Kit Rating Plate accounts for high altitude

derate.

SET GAS INPUT RATE

!

WARNING

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could result in personal injury

and/or death.
NEVER test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for the

detection of leaks to check all connections. A fire or explosion

may result causing property damage, personal injury or loss of

life.

!

AVERTISSEMENT

RISQUE D’EXPLOSION ET D’INCENDIE

Le fait de ne pas suivre cet avertissement pourrait entraîner

des dommages corporels et / ou la mort.
Ne jamais examiner pour les fuites de gaz avec une flamme

vive. Utilisez plutôt un savon fait specifiquement pour la

détection des fuites de gaz pour verifier tous les connections.

Un incendie ou une explosion peut entrainer des dommages

matériels, des blessures ou la mort.

1. Jumper R and W thermostat connections to call for heat.

(See 

Figure 13

)

2. Check manifold orifices for gas leaks when main burners

ignite.

3. Adjust gas manifold pressure. Refer to 

Table 3

.

4. Remove cap that conceals the gas valve regulator

adjustment screw.

5. Turn adjusting screw counterclockwise (out) to decrease

manifold pressure or clockwise (in) to increase manifold

pressure.

6. Replace gas valve regulator seal cap.
7. Verify manifold pressure is correct. Refer to 

Table 3

.

Figure 11

Burner Flame

Burner Flame

Burner

Manifold

A11461

Gas valve regulator seal cap MUST be in place when checking
input rate. When correct input is obtained, main burner flame
should be clear blue, almost transparent (See 

Figure 11

). Be

sure regulator seal cap is in place when finished.

8. Remove jumper across R and W thermostat connections

to terminate call for heat.

9. Turn furnace gas valve control switch or control knob to

OFF position.

Summary of Contents for KGBPN42011SP

Page 1: ...n perform basic maintenance functions such as cleaning and replacing air filters Trained service personnel must perform all other operations When working on heating equipment observe precautions in th...

Page 2: ...ZW037 1 VALVE CVRSN KIT W R SPRING 92 0935 323267 701 1 PARTS ASSY 42 323267 702 1 PARTS ASSY 43 323267 703 1 PARTS ASSY 44 323267 704 1 PARTS ASSY 45 339851 701 1 LABEL KIT 339851 702 1 LABEL KIT 319...

Page 3: ...in yearly specific gravity average for local gas supply 3 Find installation altitude in Table 3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest...

Page 4: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3...

Page 5: ...625 43 3 7 42 3 2 42 3 3 42 3 4 650 43 3 5 43 3 6 43 3 7 43 3 8 675 44 3 7 44 3 8 43 3 4 43 3 5 10000 700 44 3 4 44 3 5 44 3 7 44 3 8 3048 725 44 3 2 44 3 3 44 3 4 44 3 5 Orifice numbers shown in BOLD...

Page 6: ...stment screw 5 Remove the Propane regulator spring white 6 Install the natural gas regulator spring silver 7 Install the regulator adjustment screw 8 Turn the adjusting screw clockwise in 8 5 full tur...

Page 7: ...its splice connection with the yellow wire of the furnace wire harness Disconnect and discard this orange wire and the splice connection c Connect the yellow wire of the furnace wire harness see b abo...

Page 8: ...3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest natural gas heat value and specific gravity in Table 3 5 Follow heat value line and specific...

Page 9: ...tion instructions Figure 12 Conversion Rating Plate Label A13070 LABEL APPLICATION 1 Fill in Conversion Responsibility Label 339851 205 and apply over Propane Conversion Responsibility Label Date name...

Page 10: ...amage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which could result in personal inju...

Page 11: ...fore installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than one disconnect switch Lock out and tag swit...

Page 12: ...er burner Low NOx models in downflow or horizontal positions must use Table 6 21 000 Btuh per burner See input listed on rating plate Use Table 5 22 000 Btuh per burner for models 58DLA 58PHA 58PHB 58...

Page 13: ...44 3 4 44 3 5 43 3 2 U S A 2001 to 3000 610 to 914 800 42 3 4 42 3 5 42 3 6 42 3 7 825 42 3 2 42 3 3 42 3 4 42 3 5 850 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43...

Page 14: ...25 43 2 9 43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 U S A 700...

Page 15: ...4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 U S A 3001 to 4000 914 to 1219...

Page 16: ...8 43 2 9 650 43 2 5 43 2 5 43 2 6 43 2 7 675 43 2 3 43 2 4 43 2 4 43 2 5 700 43 2 1 43 2 2 43 2 3 43 2 3 725 48 3 7 43 2 0 43 2 1 43 2 2 750 48 3 5 48 3 6 48 3 7 43 2 0 U S A 9001 to 10 000 2743 to 3...

Page 17: ...itch Lock out and tag switch with a suitable warning label Verify proper operation after servicing For J and G valves See Figure 24 1 Be sure gas and electrical supplies to furnace are off 2 Remove ca...

Page 18: ...re than one disconnect switch Lock out and tag switch with a suitable warning label Verify proper operation after servicing 1 Be sure main gas and electric supplies to furnace are off 2 Remove Low Gas...

Page 19: ...ressure tap on gas valve 2 Turn on furnace power supply 3 Turn gas supply manual shutoff valve to ON position 4 Turn furnace gas valve switch to ON position 5 Jumper R W thermostat connections on cont...

Page 20: ...ition 7 Jumper R and W thermostat connections to call for heat See Figure 13 8 Check manifold orifices for gas leaks when main burners ignite 9 Adjust gas manifold pressure Refer to Table 5 or Table 6...

Reviews: