24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

Variable Frequency Drive (VFD)

The  VFD  converts  single  phase  60  Hz  line  power  into  a  variable
frequency,  variable  voltage,  3-phase  output  to  drive  the  compressor  at
the speed requested by the control system.  This function is performed
by  first  converting  the  incoming  line  power  to  an  intermediate  high
voltage DC supply.  The high voltage DC supply is then converted to a
3-phase  output  by  a  variable  frequency  inverter  for  driving  the
compressor.  The VFD also provides high voltage DC supply power to
the fan motor.
The  VFD  contains  numerous  protection  modes  for  maximizing
reliability  and  preventing  faults  in  wiring  or  the  compressor  and  fan
components from causing failures within the VFD.

VFD Filter Board

The VFD filter board blocks electrical noise generated within the VFD
from back-feeding onto the line power feed to the equipment. It contains
non-replaceable  fuses  which  will  protect  the  VFD  in  the  event  of  a
severe power surge condition.

Reactors

Reactors are part of the VFD incoming power conversion circuit.  The
reactors  enable  boosting  of  incoming  line  power  when  necessary  and
also provide power factor correction.

High Pressure Switch (HPS)

The HPS is a normally closed switch connected to VFD control circuitry.
The  HPS  opens  when  the  compressor  discharge  pressure  reaches  670
psig.  When the switch opens, a control input to the VFD is disabled and
causes  the  compressor  and  fan  to  shut  down.    When  compressor
discharge pressure decreases to 470 psig, the switch closes and allows
equipment operation to resume.

Compressor Brushless Permanent Magnet Motor 
(BPM)

The  compressor  uses  a  highly  efficient,  brushless  permanent  magnet
motor.  Motor speed is synchronized to, and controlled by the frequency
of the drive provided by the VFD.

VFD + Compressor BPM

Compressor runs at variable speeds controlled by the VFD.
The  VFD  controls  acceleration  and  deceleration  speeds  of  the
compressor.  Speed changes are typically limited to 60 rpm per second.
The VFD will automatically limit compressor speed if compressor load
current reaches operating limits.

Fan Brushless Permanent Magnet Motor (BPM)

The  fan  uses  a  highly  efficient,  brushless  permanent  magnet  motor.
Motor speed is synchronized to, and controlled by an on-board variable
frequency  inverter  (VFI)  integrated  with  the  motor  and  located  within
the motor housing.  The VFI uses the high voltage DC supply provided
by the VFD to drive the fan, and a low voltage control signal from the
VFD to determine fan speed.  The fan provides a feedback signal to the
VFD indicating fan speed.

VFD + Fan BPM

The  fan  runs  at  a  variable  speed  over  a  range  of  200  rpm  to  800  rpm
depending on air movement requirements.
The  fan  on-board  VFI  will  automatically  limit  fan  speed  if  fan  load
current reaches operating limits.

Crankcase Heater

Some  equipment  has  a  crankcase  heater  band  installed  around  the
compressor  case  near  the  bottom  of  the  compressor.  The  heater  is
energized when the outdoor ambient temperature drops below 65°F and
is de-energized when the outdoor ambient temperature goes above 85°F.
Heating the compressor prevents liquid refrigerant from accumulating in
the compressor by ensuring that the compressor is not the coldest part of
the  system.  The  crankcase  heater  operates  independently  of  indoor
equipment  and  System  Control  and  functions  as  needed  any  time  the
outdoor equipment is powered.
Some  equipment  has  an  internal  stator  heating  function  without  a
crankcase  heater.    The  compressor  windings  will  occasionally  be
energized  during  the  OFF  cycle  to  start  the  stator  heat  operation,  thus
maintaining  a  sump  temperature  that  is  essential  for  compressor
reliability.    The  compressor  will  not  run  during  this  process.    The
equipment  that  utilizes  the  stator  heating  function  does  not  include  a
crankcase heater, have PCM SW version 5.0 or higher, and utilizes new
VFD  hardware  and  software.    The  VFD  part  numbers  HR46VP002,
HR46VQ002, and HR46VR002 include the stator heating function.  
With  either  crankcase  heating  or  stator  heating  the  system  must  be
powered on for a minimum of 24 hours prior to starting the system to
ensure that liquid refrigerant is not present in the compressor.

CONTROL SUB-SYSTEM

The  control  sub-system  provides  the  connection  point  for  low  voltage
field  communication  and  control  wiring.  The  control  sub-system
controls all operation of the equipment.

Primary Control Module (PCM)

The PCM is the heart of the equipment control system.  The PCM is the
connection point for all control components except for the high pressure
switch and crankcase heater (when present).
The  PCM  receives  equipment  control  requests  from  a  communicating
Infinity  Control  or  from  a  non-communicating  control  (traditional
thermostat) in an emergency operating mode.
The PCM receives signals from numerous sensors, including:
• 4 thermistors: OAT, OCT, OST, PDT
• 2 pressure transducers: SPT, DPT.
The PCM controls numerous actuators and signals, including:
• 3 control solenoids: PEV, RVS and LLS
• 2 electronic expansion valves: EXV-H, EXV-VI
• VFD Control Interface
• Emergency Mode 24VAC Control Signals: O and W
The PCM performs numerous diagnostics and supports 120 diagnostic
codes.  Each of these codes is described in the Troubleshooting section.
Diagnostics cover the following:
• Line voltage and communication
• Equipment configuration (model plug, etc.)
• Compressor and fan operation
• Sensors
• Actuators
The  PCM  contains  indicators  and  displays  to  provide  operating  status
and conditions.  The PCM also supports communication with the Carrier
Service  Tech  App  through  the  Bluetooth  Module  which  provides
detailed diagnostic information and reprogramming capability.

Summary of Contents for Infinity 24VNA6

Page 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Page 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Page 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Page 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Page 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Page 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Page 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Page 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Page 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Page 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Page 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Page 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Page 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Page 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Page 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Page 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Page 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Page 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Page 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Page 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Page 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Page 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Page 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Page 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Page 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...