background image

24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

19

Code 33-15 Compressor Low Discharge Shutdown
Code 33-55 Compressor Low Discharge Lockout

Code 33-15 will become active if compressor is running and discharge
pressure is below the lower safe operating boundary for a period of time.
Discharge low pressure boundary only applies to the 5 ton model. Active
envelope  management  will  attempt  to  modify  system  operation  to
correct this condition before fault is set, but once time limit beyond the
limit is exceeded the system will shutdown. 6 occurrences of code 33-15
within 2 hours will result in code 33-55 and 2 hour lockout.
Low  discharge  pressure  can  be  caused  by  malfunctioning  reversing
valve,  low  charge,  missing  or  stuck  TXV/EXV,  or  compressor  not
operating properly.

Code 34-11 Compressor High Temp Limiting
Code 34-58 Compressor High Temp Lockout

Code  34-11  will  be  set  when  discharge  temperature  exceeds  230F
measured near the compressor. Low charge or very high superheat are
contributors  to  this  fault  condition.  For  each  occurrence  of  34-11,  the
next startup will  operate at  a  25%  reduction in capacity. Each hour of
operation  without  additional  faults  will  allow  system  to  increase
available  capacity  by  25%.  Once  the  system  is  running  at  minimum
capacity and discharge temperature exceeds 230F, code 34-58 will occur
and shut down system for 2 hours.

Code 35-11 Compressor High Compress Limiting
Code 35-58 Compressor High Compression Lockout

Code 35-11 occurs when the high compression boundary is crossed and
AEM cannot adjust system operation to reduce compression ratio. For
each  occurrence  of  35-11,  the  next  startup  will  operate  at  a  25%
reduction in capacity. Each hour of operation without additional faults
will  allow  system  to  increase  available  capacity  by  25%.  Once  the
system  is  running  at  minimum  capacity  and  the  high  compression
boundary is crossed, code 35-58 will occur and shut down system for 2
hours.  High  compression  ratio  can  be  the  result  of  overcharge  or  coil
blockage/loss of airflow across heat exchanger.

Code 36-15 Compressor Low Compress Shutdown
Code 36-55 Compressor Low Compression Lockout

Code 36-15 occurs when the low compression boundary is crossed and
AEM  cannot  adjust  system  operation  to  increase  compression  ratio.
Before  this  fault  is  set,  AEM  will  automatically  reduce  outdoor  fan
speed (cooling only) to increase CR, then increase compressor speed. 4
occurrences of code 36-15 within 2 hours will result in code 36-55 and 2
hour lockout. Low compression ratio can be a result of compressor not
increasing pressure adequately or low system charge.

Code 38-13 VFD Compressor Fault - Start Fail
Code 38-53 VFD Compressor Lockout - Start Fail

Code  38-13  originates  in  VFD  after  additional  compressor  starting
failures. While this code is active the unit opens PEV in an attempt to
equalize  pressure  across  compressor  and  continue  start  retries. After  3
consecutive  code  38-13,  malfunction  38-53  will  be  set  with  a  2  hour
lockout
Check compressor wiring for secure connections, wire damage, and wire

order.  This  code  indicates  that  the  VFD  is  not  able  to  rotate  the
compressor  rotor  enough  to  complete  starting  process,  indicating
compressor  damage  or  high  pressure  differential.  If  malfunctions
continue  to  be  generated  and  technician  confirms  pressure  differential

across compressor is <40psi, replace compressor.

Code 38-18 High Diff Pressure Start Disable

Attempting  to  start  the  compressor  against  a  high  pressure  differential
may  result  in  start  failures  with  an  otherwise  healthy  compressor. The
PEV  is  included  to  ensure  compressor  will  never  start  against  a  high
pressure  differential. This  fault  will  become  active  if  a  demand  exists
and  the  PEV  is  not  successful  in  lowering  pressure  differential  below

100psi. The  fault  will  clear  and  unit  will  start  normally  once  pressure
differential is below 100psi and demand is still present.
The most likely cause of this fault is a non-functioning PEV. Possibly the
PEV suffered a mechanical failure, or the coil is not mounted to PEV.
Verify  PEV  coil  is  attached  to  PEV  valve  body.  If  coil  is  attached  to
body, replace PEV harness and coil first, and PEV body if problem is not
fixed.

Code 38-31 VFD Compressor Fault - Estimator
Code 38-71 VFD Compressor Lockout - Estimator

The VFD  Estimator  is  used  in  the  compressor  starting  process. While
this  fault  is  active  the  PEV  will  open  and  compressor  will  continue
attempts at restarting. Three continuous code 38-31 will result in code
38-71 malfunction and 4 hour lockout. Repeated malfunctions indicate
high starting torque and possible compressor damage. First, ensure the
VFD model and compressor models are correct for unit being serviced as
incorrect  compressor  motor  parameters  will  not  allow  the  VFD  to
complete  the  starting  process  correctly.  If  all  parts  are  correct  for  the
model being serviced, compressor damage exists and should be replaced.

Code 38-54 Compressor No Pump Lockout

This diagnostic checks to ensure the compressor is running in the correct
direction and pumping properly. Once the compressor speed is >400rpm,
the compressor has up to 30 seconds to increase the pressure differential
(discharge  pressure  -  suction  pressure)  by  20psi.  If  this  pressure
differential  is  not  met,  code  38-54  sets  by  locking  operation  for  30
minutes.
The most likely cause of this fault is the compressor leads being wired
incorrectly. Check  wire colors against  wiring diagram to ensure UVW
wires are attached to the correct terminals. Less likely but still possible is
compressor motor  shaft  breakage  allowing  compressor  motor  to  rotate
but is disconnected from compression mechanism.
Fan Motor Faults General Info
The fan motor used on these models require 5 wires. 240~373 VDC is
supplied  through  Pin  1  of  3  pin  connector  (VDC)  and  Pin  1  of  4  pin
connector (GND). Pin 2 of 4 pin connector is Vcc signal for IC power

supply  (~15Vdc).  Pin  3  of  4  pin  connector  is  Vsp  signal,  which  is
0-5VDC input speed  control. Pin 4 of 4 pin is FG or feedback signal,
sending rpm information back to VFD. The motor is controlled using a

closed  loop  control  where  variable  speed  is  increased  or  decreased  by
VFD depending on the RPM command from PCM to VFD along with
actual  RPM  information  read  through  FG  pin.  Use 

Table 7

  to  confirm

damaged electronics within fan motor. Note - winding resistance cannot
be  measured  on  fan  motor  due  to  embedded  electronics.  Note  -
resistances  are  approximate,  temperature  may  affect  measurements  so

only declare motor bad if results differ greatly from values in 

Table 4

.

Though  the  fan  motor  has  internal  current  protection,  an  external
replaceable  fuse  is  located  on  VFD  for  short  circuit  protection.  See

wiring diagram for fuse replacement specifications.

Code 39-13 Fan Start Failure
Code 39-53 Fan Start Failure Lockout

When a demand startup begins a fan speed is commanded to VFD. After
25 seconds of FG (fan speed feedback signal) = 0, the PCM will reset the
VFD and try to start fan again. After 3 VFD resets Code 39-13 will be
set. PCM will continue to reset VFD a total of 6 times before declaring
code 39-53 and locking out for 1 hour. A successful fan start will reset
the fan start failed counter.
Inspect  all  wiring  and  connectors  for  damage  and  loose  connections.
Check for fan blade blockage and free spin. Check external fan fuse. If
no  physical  blockage  is  present  and  fuse  is  not  open,  ohm  motor  and
replace if necessary.

Summary of Contents for Infinity 24VNA6

Page 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Page 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Page 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Page 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Page 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Page 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Page 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Page 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Page 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Page 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Page 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Page 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Page 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Page 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Page 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Page 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Page 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Page 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Page 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Page 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Page 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Page 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Page 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Page 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Page 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 40: ...idential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with y...

Reviews: