24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

35

REFRIGERATION SYSTEM

Refrigerant

In an air conditioning and heat pump system, refrigerant transfers heat
from  one  place  to  another.  The  condenser  is  the  outdoor  coil  in  the
cooling mode and the evaporator is the indoor coil. 
In a heat pump, the condenser is the indoor coil in the heating mode and
the evaporator is the outdoor coil. 
In  the  typical  air  conditioning  mode,  compressed  hot  gas  leaves  the

compressor  and  enters  the  condensing  coil. As  gas  passes  through  the
condenser  coil,  it  rejects  heat  and  condenses  into  liquid.  The  liquid
leaves condensing unit through liquid line and enters metering device at

evaporator  coil.  As  it  passes  through  metering  device,  it  becomes  a
gas-liquid mixture. As it passes through indoor coil, it absorbs heat and
the refrigerant moves to the compressor and is again compressed to hot

gas, and cycle repeats.

Compressor Oil

Servicing Systems on Roofs With Synthetic 
Materials

Polyvinyl  ether  (PVE)  compressor  lubricants  are  known  to  cause  long
term  damage  to  some  synthetic  roofing  materials.  Exposure,  even  if
immediately cleaned up, may cause embrittlement (leading to cracking)
to occur in one year or more. When performing any service which may
risk exposure of compressor oil to the roof, take appropriate precautions
to protect roofing. Procedures which risk oil leakage include but are not
limited  to  compressor  replacement,  repairing  refrigerants  leaks,
replacing  refrigerant  components  such  as  filter  drier,  pressure  switch,
metering device, coil, accumulator, or reversing valve.

Synthetic Roof Precautionary Procedure

1. Cover  extended  roof  working  area  with  an  impermeable

polyethylene (plastic) drop cloth or tarp. Cover an approximate 10
x 10 ft area.

2. Cover area in front of the unit service panel with a terry cloth shop

towel  to  absorb  lubricant  spills  and  prevent  run-offs,  and  protect

drop cloth from tears caused by tools or components.

3. Place  terry  cloth  shop  towel  inside  unit  immediately  under

component(s) to be serviced and prevent lubricant run-offs through
the louvered openings in the base pan.

4. Perform required service.
5. Remove  and  dispose  of  any  oil  contaminated  material  per  local

codes.

Brazing

This  section  on  brazing  is  not  intended  to  teach  a  technician  how  to
braze.  There  are  books  and  classes  which  teach  and  refine  brazing
techniques. The basic points below are listed only as a reminder.
Definition: The joining and sealing of metals using a nonferrous metal
having a melting point over 800°F/426.6°C.
Flux: A cleaning solution applied to tubing or wire before it is brazed.
Flux improves the strength of the brazed connection.
When  brazing  is  required  in  the  refrigeration  system,  certain  basics
should be remembered. The following are a few of the basic rules.

1. Clean joints make the best joints. To clean:

– Remove  all  oxidation  from  surfaces  to  a  shiny  finish  before

brazing.

– Remove all flux residue with brush and water while material is still

hot.

2. Silver brazing alloy is used on copper-to-brass, copper-to-steel, or

copper-to-copper. Flux is required when using silver brazing alloy.
Do not use low temperature solder.

3. Fluxes should be used carefully. Avoid excessive application and do

not allow fluxes to enter into the system.

4. Brazing  temperature  of  copper  is  proper  when  it  is  heated  to  a

minimum  temperature  of  800°F  and  it  is  a  dull  red  color  in
appearance.

Service Valves and Pumpdown

Service  valves  provide  a  means  for  holding  original  factory  charge  in
outdoor  unit  prior  to  hookup  to  indoor  coil.  They  also  contain  gauge
ports for  measuring system pressures and  provide  shutoff convenience
for certain types of repairs. 
The service valve is a front-seating valve, which has a service port that
contains a Schrader fitting. The service port is always pressurized after
the valve is moved off the front-seat position.
The  service  valves  in  the  outdoor  unit  come  from  the  factory
front-seated. This means that the refrigerant charge is isolated from the
line-set connection ports.  The interconnecting tubing (line set) can be
brazed  to  the  service  valves  using  industry  accepted  methods  and
materials. Consult local codes.
Before  brazing  the  line  set  to  the  valve,  the  belled  ends  of  the  sweat
connections  on  the  service  valves  must  be  cleaned  so  that  no  brass
plating  remains  on  either  the  inside  or  outside  of  the  bell  joint.  To
prevent  damage  to  the  valve  and/or  cap  “O”    ring,  use  a  wet  cloth  or
other  acceptable  heat-sinking  material  on  the  valve  before  brazing. To
prevent damage to the unit, use a metal barrier between brazing area and
unit.
After the brazing operation and the refrigerant tubing and evaporator coil
have  been  evacuated,  the  valve  stem  can  be  turned  counterclockwise
until  back-seats,  which  releases  refrigerant  into  tubing  and  evaporator
coil. The system can now be operated.
The service valve-stem cap is tightened to 20 ±  2 ft/lb torque and the
service-port caps to 9 ±  2 ft/lb torque. The seating surface of the valve
stem has a knife-set edge against which the caps are tightened to attain a
metal-to-metal seal. 

WARNING

!

UNIT OPERATION AND SAFETY HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  or
equipment damage.
Puronr  refrigerant  which  has  higher  pressures  than  R-22  and  other
refrigerants. No other refrigerant may be used in this system. Gauge set,
hoses, and recovery system must be designed to handle Puronr. If you
are unsure consult the equipment manufacturer.

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
The  compressor  in  a  Puron  system  uses  a  polyvinyl  ether  (PVE)  oil.
This  oil  is  extremely  hygroscopic,  meaning  it  absorbs  water  readily.
PVE oils can absorb 15 times as much water as other oils designed for
HCFC  and  CFC  refrigerants. Take  all  necessary  precautions  to  avoid
exposure of the oil to the atmosphere. 

WARNING

!

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  or
equipment damage.
Never attempt to make repairs to existing service valves. Unit operates
under high pressure. Damaged seats and o-rings should not be replaced.
Replacement of entire service valve is required.  Service valve must be
replaced by properly trained service technician.

Summary of Contents for Infinity 24VNA6

Page 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Page 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Page 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Page 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Page 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Page 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Page 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Page 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Page 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Page 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Page 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Page 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Page 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Page 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Page 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Page 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Page 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Page 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Page 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Page 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Page 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Page 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Page 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Page 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Page 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 40: ...idential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with y...