background image

24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

23

Code 81-13 VFD System Fault - PFC
Code 81-53 VFD System Lockout - PFC

The  power  factor  correction  circuit  (PFC)  in  VFD  introduces  an
inductance which corrects the current phase shift inherent with powering
motors. This  in turn minimizes the  reactive  power  transmitted  back to
input power cables. This fault is set when the PFC circuit exceeds a peak
current limit when driving compressor. System will shut down and VFD
will  reset,  if  demand  persists,  system  will  attempt  to  resume  normal
operation. After 2 occurrences within 10 minutes, code 81-53 is set and
system is locked out for 4 hours. A power cycle will clear malfunction
lockout  timer.  Continued  malfunctions  indicate  high  current  situation.
This  is  likely  due  to  VFD  or  compressor  damage.  Measure  reactor(s)
resistance. As  reactor  charges  the  resistance  will  be  reduced  to  0.  If
measurement is open, replace reactor. Otherwise replace VFD.

Code 81-14 VFD System Fault - Unbalanced PFCM
Code 81-54 VFD System Lockout - Unbalance PFCM

Applicable to 4 and 5 ton models only with multiple reactors. This fault
occurs when current in PFCM circuits is not balanced. It is most likely
caused by a disconnected or faulty reactor. The VFD will shut down and
attempt  to  restart  after  each  occurrence  of  code  81-14.  After  2
occurrences within 10 minutes, code 81-54 is set and system is locked
out for 4 hours.
Disconnect and measure resistance of both reactors in system. As reactor
charges  the  resistance  will  be  reduced  to  0.  If  measurement  is  open,
replace reactor. Otherwise replace VFD.

Code 81-58 VFD System Lockout - Wiring Error

This fault occurs when the VFD senses that 1 or more of the compressor
wires are not connected to VFD. While this fault is active the system is
inoperable.  Check  compressor  wire  harness  at  each  end  and  ensure
connections  are  tight  fitting  and  wires  are  undamaged.  Perform
continuity test on compressor harness with DMM. Check resistance of
compressor  windings  at VFD  end  of  compressor  harness  to  ensure  no
windings are open. Refer to 

Table 4

 for compressor winding resistance

by outdoor model.

Code 82-11 VFD System Fault - Line Current Lim

The  VFD  monitors  input  current  and  will  limit  or  reduce  compressor
speed  if  the  current  rises  above  threshold.  Current  limits  are  model
specific. While  code  82-11  is  active  the VFD  will  continue  to  operate
compressor at a reduced or limited speed, while fan operation will not be
affected  directly.  This  code  will  clear  once  VFD  input  current  drops
below threshold. Low input voltage combined with high load is the most
likely  cause  of  this  code.  Check  system  for  overcharge  and
indoor/outdoor coil blockage as well as input voltage.

Code 82-13 VFD Reset with Power Dropout
Code 82-53 VFD Lockout - Reset with Power Drop

This code indicates the VFD has reset itself due to a line voltage loss.
When this code is set the PCM will complete a shutdown, reset the VFD,
and  restart  if  demand  is  still  present.  The  system  should  resume
operation after the 5 minute compressor protection time delay expires. 3
occurrences of code 82-13 within a 1 hour period will result in a code
82-53  and  2  hour  lockout.  Occasional  occurrences  of  this  code  may
happen  due  to  momentary  power  loss  or  electrical  noise  from  utility.
Check tightness of all line voltage connections. Loose connections can
cause momentary voltage drop due to vibration and trigger this fault. If
all  connections  are  tight,  additional  steps  involving  the  local  power
utility or addition of external power conditioner may be required.

Code 82-15 VFD Fault with Power Dropout
Code 82-55 VFD Lockout - Fault with Power Drop

This  code  indicates  the VFD  has  shutdown  due  to  a  line  voltage  loss.
When this code is set the PCM reset the VFD, and restart if demand is
still  present.  The  system  should  resume  operation  after  5  minute
compressor protection time delay expires. 4 occurrences of code 82-15

within a 1 hour period will result in a code 82-55 and 2 hour lockout.
Occasional  occurrences  of  this  code  may  happen  due  to  momentary
power loss or electrical noise from utility. This code can be paired with
other  codes  if  electrical  noise  is  present.  Check  tightness  of  all  line
voltage  connections.  Loose  connections  can  cause  momentary  voltage
drop due to vibration and trigger this fault. If all connections are tight,
additional steps involving the local power utility or addition of external
power conditioner may be required.

Code 82-16 VFD System Fault - Low Line Volt
Code 82-56 VFD System Lockout - Low Line Volt

The VFD monitors line voltage and will set code 82-16 if line voltage
drops  below  180VAC  peak.  When  code  82-16  occurs  the  system  will
shut down and reset VFD. System will attempt to resume operation once
5  minute  compressor  protection  timer  expires.  4  occurrences  of  code
82-16 in a 1 hour period will result in code 82-56 and will shut down
equipment  for  a  2  hour  lockout.  Measure  input  voltage  with  a  power
quality analyzer and contact power utility provider if necessary.

Code 82-17 VFD System Fault - High Line Volt
Code 82-57 VFD System Lockout - High Line Volt

The VFD monitors line voltage and will set code 82-17 if line voltage
rises above 410VAC peak. When code 82-17 is occurs the system will
remain operating as it is likely caused by a momentary voltage spike that
will  not  damage  the  VFD.  If  a  long  term  unsafe  high  voltage  event
occurs,  the  PCM  will  generate  a  15-94  and  shut  down  equipment.  10
events of code 82-17 in a 1 hour period will result in code 82-57 and will
shut down equipment for a 2 hour lockout. Measure input voltage with a
power quality analyzer and contact power utility provider if necessary.

Code 83-11 VFD Compressor Fault - Current 1
Code 83-12 VFD Compressor Fault - Current 2

The VFD monitors multiple compressor current conditions and will limit

or reduce compressor speed if the current rises above threshold. Current
limits are model specific. While codes are active the VFD will continue
to operate compressor at a reduced or limited speed, and fan operation

will  not  be  affected  directly.  This  code  will  clear  once  compressor
current drops below threshold. This code indicates the compressor may
have  minor  damage  and  requires  slightly  higher  torque  (current)  to

operate at desired rpm. If damage continues to worsen the compressor
may  cause  code  83-15,  83-55,  83-16,  and  83-56.  Check  system  for
overcharge  and  indoor/outdoor  coil  blockage  as  well  as  input  voltage.

Listen  to  compressor  during  operating  for  abnormal  noise  indicating
physical  damage.  If  code  persists  or  compressor  has  abnormal  noise,
replace compressor.

Code 83-15 VFD Compressor Fault - Current 3
Code 83-55 VFD Compressor Lockout - Current 3
Code 83-16 VFD Compressor Fault - Current 4
Code 83-56 VFD Compressor Lockout - Current 4

The VFD monitors multiple compressor current conditions and will limit
or reduce compressor speed if the current rises above threshold. Current
limits  are  model  specific.  Code  83-15,  83-16,  83-55,  and  83-56  will

result if the VFD is not capable of reducing compressor speed far enough
or  fast  enough  while  running.  This  code  will  shut  down  system  and
attempt restart after 5 minute compressor protection timer has expired. 2

instances  of  code  83-15/83-16  in  a  4  hour  period  will  result  in  code
83-55/83-56 and a 2 hour lockout. These codes indicate the compressor
requires higher torque (current) to operate at desired rpm. Check system
for overcharge and indoor/outdoor coil blockage as well as input voltage.

Check  wiring  from  VFD  to  compressor  for  poor  connections  causing
high current. Check compressor winding resistance against table. Listen
to compressor during operating for abnormal noise indicating physical

damage.  VFD  may  have  internal  damage  causing  high  current,  or
compressor may be damaged.

Summary of Contents for Infinity 24VNA6

Page 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Page 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Page 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Page 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Page 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Page 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Page 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Page 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Page 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Page 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Page 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Page 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Page 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Page 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Page 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Page 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Page 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Page 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Page 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Page 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Page 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Page 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Page 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Page 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Page 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 40: ...idential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with y...

Reviews: