background image

9

d. Attach field-supplied disconnect switch and field-

supplied 4-in. length of ROMEX cable to the
mounting bracket.

e. Slip flange of mounting bracket under top cover

flange, between top cover and side of unit. Line up
holes in mounting bracket with screw holes in unit.

f. With screws removed in Step a, attach mounting

bracket to unit.

g. Connect ROMEX cable to unit. Seal penetration

with RTV sealant to prevent rain water from being
drawn into the unit.

Size 008-014 Units:
A mounting bracket is not required. Disconnect switch
mounts directly onto the unit. See Fig. 15 and 16 for
location of disconnect switch on size 008-014 units.
Drill 0.875-in. hole in side of unit for wiring to discon-
nect switch. See Fig. 16 for wiring hole location.
Match up wiring hole in disconnect switch with wiring
hole drilled into side of unit. Mount disconnect switch
to unit with 4 self-tapping screws (field-provided).
Seal disconnect switch housing with RTV sealant to
prevent rain water from being drawn into the unit.

5. A separate source power supply must be routed to the

accessory germicidal lamp’s unit mounted disconnect
switch per applicable codes. Unit wiring and control
box connections should not be used. Refer to the Pack-
age Usage table for electrical characteristics of power
supply. Power source must be a suitable fused,
grounded, protected source with the correct voltage.
Other voltages will permanently damage the germi-
cidal lamp.
Wire per Table 1.

6. Any hinged potential access panel or door to the instal-

lation area must be interlocked with the accessory
power source to turn the lamp off if the door is opened.
Access doors should be labelled with appropriate
warnings about exposure to ultra-violet light.
A pushbutton door interlock switch (Carrier Part No.
HR54ZA101) is required on all hinged access panels.
Use a field-fabricated and -installed bracket to mount
the door interlock switch. See Fig. 17 and 18. Drill
0.406-in. hole in unit z-flange 1.75-in. from end of
door for pushbutton of interlock switch. Push button
will go through unit z-flange and will be contacted by
door. See Fig. 15.

Use insulated sleeve terminals for connection to inter-
lock switch. The pushbutton door interlock switch is
not required on non-hinged access panels. Door inter-
lock switch should be located on the side of the access
door that opens. Locate the switch near the top of the
door so it will not be in a location where it interferes
with maintenance or service.
Run wiring into disconnect switch. Door interlock
switch should be wired into the power (Black) lead,
between the disconnect switch and the germicidal
lamp, to break power to the accessory when the door is
opened.

7. Using the accessory as a template, mark two 1-in.

insertion holes on the mounting surface. Mark 8 holes
for accessory mounting. See Fig. 3 and 4 for location.
The 1-in. holes are used for electrical connections and
the germicidal bulb. See Fig. 5.

8. Drill 1-in. holes in unit where marked.
9. Use field-supplied No. 10 self-drilling screws to attach

accessory to unit.
NOTE: Holes can be drilled in unit if self-drilling
screws are not used. Drill 8 holes for eight no. 10
screws used to attach accessory to unit. Using eight no.
10 screws provided, attach accessory to unit. 

Be sure accessory has a watertight seal against unit
wall. Use standard 1/2-in. strain relief connectors
when running wiring through any hole in unit.

10. Wire accessory germicidal lamp to disconnect switch.

See Table 1 for wiring recommendations. Use UVC
resistant wire, outdoor duty, 14-gage ROMEX cable or
1/2-in. conduit for all wiring. Wire power, neutral, and
ground leads to disconnect switch. Do not ground to
unit. Ultra-violet lamps should be operated continu-
ously from power source. Lamps should not be con-
nected to indoor fan power source or any power source
where they would be cycled more than twice per day.

Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.

Fig. 12 — Junction Box Installation — 48/50EJ,EK,EW,EY Units (48EJ024 Shown)

Summary of Contents for CRNEMAFX001A00

Page 1: ...s and microbial growth The Carrier germicidal lamps have been specifically de signed and optimized for 40 to 45 F high humidity operation in a moving airstream inside an HVAC unit The Carrier germi ci...

Page 2: ...le 1 Table 1 Wiring Recommendations 6 Any hinged potential access panel or door to the instal lation area must be interlocked with the accessory power source to turn the lamp off if the door is opened...

Page 3: ...e of part 2 On size 038 048 units use 4 bulbs spaced at 34 00 On size 054 068 units use 5 bulbs spaced at 34 00 3 Dimensions are in inches Fig 2 Germicidal Lamps Installation Location 48 50EJ EK EW EY...

Page 4: ...ll 1 in holes in unit where marked Fig 4 Germicidal Lamps Installation Location 48 50HJ TJ008 014 and 50HJQ008 012 Units NOTE Dimensions are in inches Fig 5 Accessory Dimensions NOTE Dimensions are in...

Page 5: ...an power source or any power source where they would be cycled more than twice per day NOTE If door interlock switch is used black power lead will be connected to the door interlock switch wir ing not...

Page 6: ...N 0 0 25 0 25 1 62 0 0 30 0 50 Fig 7 Disconnect Location 48 50HJ TJ015 028 Units and 50HJQ014 and 016 Units Fig 8 Field Fabricated Bracket for Door Interlock Switch 48 50HJ TJ015 028 Units and 50HJQ01...

Page 7: ...wired into the power Black lead between the disconnect switch and the junction box installed in Step 10 to break power to the accessory when the door is opened 7 Access doors may be equipped with a gl...

Page 8: ...ulb should glow with a blue hue If bulb cannot be seen briefly back out bulb and view from safe distance replace bulb when done If bulb does not glow check wiring safety interlock or replace bulb Inst...

Page 9: ...ll 0 406 in hole in unit z flange 1 75 in from end of door for pushbutton of interlock switch Push button will go through unit z flange and will be contacted by door See Fig 15 Use insulated sleeve te...

Page 10: ...season Bulb output can also be checked with a UVC radiometer Replace bulb when output falls to 70 of initial reading The following bulbs can safely be used with this accessory CRSGLTUB001A00 16 in tu...

Page 11: ...stallation 48 50HJ TJ008 014 and 50HJQ008 012 Units Shown Fig 16 Disconnect Switch Wiring Hole Location 48 50HJ TJ008 014 and 50HJQ008 012 Units Only NOTE Dimensions are in inches NOTES 1 Use 18 gage...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 734 Printed in U S A Form 48 50 51SI Pg 12 4 99 Replaces New Book 1 1 1 4 4 4 Tab 1a...