NOTE: If door interlock switch is used, black power
lead will be connected to the door interlock switch wir-
ing (not to the disconnect switch).

11. Locate the germicidal bulb. DO NOT TOUCH

GLASS ON BULB. Grasp the bulb only by the base
(non-glass part). Clean the bulb using a lint free wipe
and isopropyl alcohol. Make sure O-ring on bulb is
toward the accessory and push into the 1-in. hole until
seated. Hold the bulb in place and lock into place by
installing the spring wire fastener to the lances on the
bulb.

12. Push on the power plug. Do not force. Rotate

90 degrees if necessary.

13. Affix the ultra-violet light warning label to the outside

of the unit, in plain sight, on all access doors. Replace
label when worn. See Fig. 10.

14. Test all circuits and return power to unit. Accessory

bulb should glow with a blue hue. If bulb cannot be
seen briefly back out bulb and view from safe distance.
replace bulb when done. If bulb does not glow, check
wiring, safety interlock, or replace bulb.

MAINTENANCE

Disconnect all power before performing any maintenance

or service.

Bulbs need periodic replacement to maintain design specifi-

cations. Replace bulbs after 6000 hours of operation or 1 year,
whichever comes first. For best performance, replace bulbs at
the beginning of each cooling season.

Bulb output can also be checked with a UVC radiometer.

Replace bulb when output falls to 70% of initial reading

The following bulbs can safely be used with this accessory:

• CRSGLTUB001A00 (16-in. tube)
• CRSGLTUB002A00 (20-in. tube)
• CRSGLTUB003A00 (24-in. tube)
• CRSGLTUB004A00 (30-in. tube)
• CRSGLTUB005A00 (36-in. tube)

Other bulbs may plug into the accessory, but they should not

be used. Non-approved bulbs will overheat bulb and power
source. Normal operation temperature for the bulb is 80 F. Nor-
mal operation temperature for the power source is 125 F.

OPERATION

While lit, bulb color should be light blue. If bulb color

changes to red or flickers, replace the bulb. Bulbs that are not
light blue will not emit ultra-violet radiation and will not kill
harmful bacteria or fungi.

Fiberglass filter media are recommended for operation of

HVAC when filters are exposed to ultra-violet lamps. Polyester
or cotton filters are subject to ultra-violet degradation and are
not recommended.

Use only specified high-output, low temperature bulbs with
this accessory. Use of a lower wattage or incorrect bulb can
result in damage to accessory or bulb. Correct bulbs have a
blue end cap.

7.0

6.1

3.5

.25

.59

2.875

.25

.31
2 PLACES

2.32

.32

ROUND SHARP
CORNERS
2 PLACES

2.37

.875

1.46

ROUND SHARP
CORNERS
2 PLACES

1

.25
4 PLACES

4

18 GA GALVANIZED
STEEL OR
EQUIVALENT

Fig. 13 — Disconnect Switch Field-Fabricated Mounting Bracket

(48/50HJ,TJ004-007 and 50HJQ004-007 Units Only)

NOTE: Dimensions are in inches.

Summary of Contents for CRNEMAFX001A00

Page 1: ...s and microbial growth The Carrier germicidal lamps have been specifically de signed and optimized for 40 to 45 F high humidity operation in a moving airstream inside an HVAC unit The Carrier germi ci...

Page 2: ...le 1 Table 1 Wiring Recommendations 6 Any hinged potential access panel or door to the instal lation area must be interlocked with the accessory power source to turn the lamp off if the door is opened...

Page 3: ...e of part 2 On size 038 048 units use 4 bulbs spaced at 34 00 On size 054 068 units use 5 bulbs spaced at 34 00 3 Dimensions are in inches Fig 2 Germicidal Lamps Installation Location 48 50EJ EK EW EY...

Page 4: ...ll 1 in holes in unit where marked Fig 4 Germicidal Lamps Installation Location 48 50HJ TJ008 014 and 50HJQ008 012 Units NOTE Dimensions are in inches Fig 5 Accessory Dimensions NOTE Dimensions are in...

Page 5: ...an power source or any power source where they would be cycled more than twice per day NOTE If door interlock switch is used black power lead will be connected to the door interlock switch wir ing not...

Page 6: ...N 0 0 25 0 25 1 62 0 0 30 0 50 Fig 7 Disconnect Location 48 50HJ TJ015 028 Units and 50HJQ014 and 016 Units Fig 8 Field Fabricated Bracket for Door Interlock Switch 48 50HJ TJ015 028 Units and 50HJQ01...

Page 7: ...wired into the power Black lead between the disconnect switch and the junction box installed in Step 10 to break power to the accessory when the door is opened 7 Access doors may be equipped with a gl...

Page 8: ...ulb should glow with a blue hue If bulb cannot be seen briefly back out bulb and view from safe distance replace bulb when done If bulb does not glow check wiring safety interlock or replace bulb Inst...

Page 9: ...ll 0 406 in hole in unit z flange 1 75 in from end of door for pushbutton of interlock switch Push button will go through unit z flange and will be contacted by door See Fig 15 Use insulated sleeve te...

Page 10: ...season Bulb output can also be checked with a UVC radiometer Replace bulb when output falls to 70 of initial reading The following bulbs can safely be used with this accessory CRSGLTUB001A00 16 in tu...

Page 11: ...stallation 48 50HJ TJ008 014 and 50HJQ008 012 Units Shown Fig 16 Disconnect Switch Wiring Hole Location 48 50HJ TJ008 014 and 50HJQ008 012 Units Only NOTE Dimensions are in inches NOTES 1 Use 18 gage...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 734 Printed in U S A Form 48 50 51SI Pg 12 4 99 Replaces New Book 1 1 1 4 4 4 Tab 1a...

Reviews: