Repeat for all accessory germicidal lamps. There may
be 3, 4, or 5 lamps required.
Install a standard 4 x 4 junction box in the unit near the
disconnect switch. Wire the disconnect switch to the
junction box. Connect power (black), neutral (white),
and ground (green) wiring.
NOTE: If door interlock switch is used, power (black)
lead will be connected to the door interlock switch.

11. Wire all accessory germicidal lamps to junction box.

See Fig. 9 and 12. See Table 1 for wiring recommenda-
tions. Use UVC resistant wire, outdoor duty, 14-gage
ROMEX cable or 1/2-in. conduit for all wiring. Wire
power, neutral, and ground leads to disconnect switch.
Do not ground to unit. When connecting to terminals
in accessory germicidal lamp, strip end of wire 3/8-in.
and push wire into terminal. Ultra-violet lamps should
be operated continuously from power source. Lamps
should not be connected to indoor fan power source or
any power source where they would be cycled more
than twice per day.

12. Locate the germicidal bulb. DO NOT TOUCH

GLASS ON BULB. Grasp the bulb only by the base
(non-glass part). Clean the bulb using a lint free wipe
and isopropyl alcohol. Make sure O-ring on bulb is
toward the accessory and push into the 1-in. hole until
seated. Hold the bulb in place and lock into place by
installing the spring wire fastener to the lances on the
bulb.

13. Push on the power plug. Do not force. Rotate

90 degrees if necessary.

14. Affix the ultra-violet light warning label to the outside

of the unit, in plain sight, on all access doors. Replace
label when worn. See Fig. 10.

15. Test all circuits and return power to unit. Accessory

bulb should glow with a blue hue. If bulb cannot be
seen briefly back out bulb and view from safe distance.
replace bulb when done. If bulb does not glow, check
wiring, safety interlock, or replace bulb.

Installation (48/50HJ,TJ004-014 Units and
50HJQ004-012 Units) — 

Perform the following proce-

dure to install the germicidal lamp:

1. Turn off all power to unit.
2. Install reflective material (field-supplied) in installa-

tion location if desired. Reflecting ultra-violet light
energy is recommended to enhance performance and
reduce shadows. Lining the installation area with alu-
minum or aluminum foil allows light energy to reflect
instead of being absorbed, increasing the effectiveness
of the germicidal lamp.

3. Ultra violet light may damage certain plastics and

exposed non-UVC protected wires. (Drain pans will
not be damaged.) Wrap exposed plastic and wiring
with aluminum tape or use metal conduit.

4. Mount field-provided light-switch disconnect switch

on unit. Disconnect switch should have a waterproof
housing. 

Size 004-007 Units:
A field-supplied bracket is required to mount the light-
switch disconnect on size 004-007 units. Perform the
following procedure to install the disconnect switch:

a. Remove two screws from unit top cover flange,

located above accessory installation location. Save
screws.

b. Fabricate disconnect mounting switch bracket. See

Fig. 13 for bracket dimensions and details.

c. Drill hole in side panel of unit for disconnect wir-

ing. See Fig. 14 for hole dimensions.

Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.

5.25

16.00

UVC
DISCONNECT
BOX

024-034 UNIT SHOWN

NOTES: 
1. Unless otherwise specified all

dimensions are to outside of
part.

2. Dimensions are in inches.

Fig. 11 — Disconnect Switch Location — 48/50EJ,EK,EW,EY Units

Summary of Contents for CRNEMAFX001A00

Page 1: ...s and microbial growth The Carrier germicidal lamps have been specifically de signed and optimized for 40 to 45 F high humidity operation in a moving airstream inside an HVAC unit The Carrier germi ci...

Page 2: ...le 1 Table 1 Wiring Recommendations 6 Any hinged potential access panel or door to the instal lation area must be interlocked with the accessory power source to turn the lamp off if the door is opened...

Page 3: ...e of part 2 On size 038 048 units use 4 bulbs spaced at 34 00 On size 054 068 units use 5 bulbs spaced at 34 00 3 Dimensions are in inches Fig 2 Germicidal Lamps Installation Location 48 50EJ EK EW EY...

Page 4: ...ll 1 in holes in unit where marked Fig 4 Germicidal Lamps Installation Location 48 50HJ TJ008 014 and 50HJQ008 012 Units NOTE Dimensions are in inches Fig 5 Accessory Dimensions NOTE Dimensions are in...

Page 5: ...an power source or any power source where they would be cycled more than twice per day NOTE If door interlock switch is used black power lead will be connected to the door interlock switch wir ing not...

Page 6: ...N 0 0 25 0 25 1 62 0 0 30 0 50 Fig 7 Disconnect Location 48 50HJ TJ015 028 Units and 50HJQ014 and 016 Units Fig 8 Field Fabricated Bracket for Door Interlock Switch 48 50HJ TJ015 028 Units and 50HJQ01...

Page 7: ...wired into the power Black lead between the disconnect switch and the junction box installed in Step 10 to break power to the accessory when the door is opened 7 Access doors may be equipped with a gl...

Page 8: ...ulb should glow with a blue hue If bulb cannot be seen briefly back out bulb and view from safe distance replace bulb when done If bulb does not glow check wiring safety interlock or replace bulb Inst...

Page 9: ...ll 0 406 in hole in unit z flange 1 75 in from end of door for pushbutton of interlock switch Push button will go through unit z flange and will be contacted by door See Fig 15 Use insulated sleeve te...

Page 10: ...season Bulb output can also be checked with a UVC radiometer Replace bulb when output falls to 70 of initial reading The following bulbs can safely be used with this accessory CRSGLTUB001A00 16 in tu...

Page 11: ...stallation 48 50HJ TJ008 014 and 50HJQ008 012 Units Shown Fig 16 Disconnect Switch Wiring Hole Location 48 50HJ TJ008 014 and 50HJQ008 012 Units Only NOTE Dimensions are in inches NOTES 1 Use 18 gage...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 734 Printed in U S A Form 48 50 51SI Pg 12 4 99 Replaces New Book 1 1 1 4 4 4 Tab 1a...

Reviews: