10. Use field-supplied no. 10 self-drilling screws to attach

accessory to unit.
NOTE: Holes can be drilled in unit if self-drilling
screws are not used. Drill 8 holes for eight no. 10
screws used to attach accessory to unit. Using eight no.
10 screws, attach accessory to unit.

Be sure accessory has a watertight seal against unit
wall. Use standard 1/2-in. strain relief connectors
when running wiring through any hole in unit.
Repeat for all accessory germicidal lamps.

11. Wire accessory germicidal lamp to disconnect switch.

See Table 1 for wiring recommendations. Use UVC
resistant wire, outdoor duty, 14-gage ROMEX cable or
1/2-in. conduit for all wiring. Wire power, neutral, and
ground leads to disconnect switch. Do not ground to
unit. See Fig. 9. 
Route wiring away from indoor fan motor and coil sur-
faces. Strain relief bushings are required when routing
wire through panels. A 7/8-in. diameter hole is
required in top coil support bracket to route wiring to
disconnect switch. The 7/8-in. diameter hole may be
factory-drilled depending on when the unit was pro-
duced. Field-drilling of hole may be required.
When using ROMEX cable, accessories can be wired
in series. When using conduit, accessories cannot be
wired in series due to size of conduit, and an additional
7/8-in. diameter hole is required in top coil support
bracket for routing of conduit from both accessories.
See Fig. 6.
When connecting to terminals in accessory germicidal
lamp, strip end of wire 3/8-in. and push wire into ter-
minal. Ultra-violet lamps should be operated continu-

ously from power source. Lamps should not be
connected to indoor fan power source or any power
source where they would be cycled more than twice
per day.
NOTE: If door interlock switch is used, black power
lead will be connected to the door interlock switch wir-
ing (not to the disconnect switch).

12. Locate the germicidal bulb. DO NOT TOUCH

GLASS ON BULB. Grasp the bulb only by the base
(non-glass part). Clean the bulb using a lint free wipe
and isopropyl alcohol. Make sure O-ring on bulb is
toward the accessory and push into the 1-in. hole until
seated. Hold the bulb in place and lock into place by
installing the spring wire fastener to the lances on the
bulb.

13. Push on the power plug. Do not force. Rotate

90 degrees if necessary.

14. Affix the ultra-violet light warning label to the outside

of the unit, in plain sight, on all access doors. Replace
label when worn. See Fig. 10.

15. Test all circuits and return power to unit. Accessory

bulb should glow with a blue hue. If bulb cannot be
seen briefly back out bulb and view from safe distance.
Replace bulb when done. If bulb does not glow, check
wiring, safety interlock, or replace bulb.

Installation (48/50EJ,EK,EW,EY Units) — 

Perform the

following procedure to install the germicidal lamp:

1. Turn off all power to unit.
2. Install reflective material (field-supplied) in installa-

tion location if desired. Reflecting ultra-violet light
energy is recommended to enhance performance and
reduce shadows. Lining the installation area with alu-
minum or aluminum foil allows light energy to reflect
instead of being absorbed, increasing the effectiveness
of the germicidal lamp.

Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.

Fig. 6 — Disconnect Switch and Interlock Switch Installation — 

48/50HJ,TJ015-028 Units and 50HJQ014 and 016 Units

NOTE: Dimensions are in inches.

Summary of Contents for CRNEMAFX001A00

Page 1: ...s and microbial growth The Carrier germicidal lamps have been specifically de signed and optimized for 40 to 45 F high humidity operation in a moving airstream inside an HVAC unit The Carrier germi ci...

Page 2: ...le 1 Table 1 Wiring Recommendations 6 Any hinged potential access panel or door to the instal lation area must be interlocked with the accessory power source to turn the lamp off if the door is opened...

Page 3: ...e of part 2 On size 038 048 units use 4 bulbs spaced at 34 00 On size 054 068 units use 5 bulbs spaced at 34 00 3 Dimensions are in inches Fig 2 Germicidal Lamps Installation Location 48 50EJ EK EW EY...

Page 4: ...ll 1 in holes in unit where marked Fig 4 Germicidal Lamps Installation Location 48 50HJ TJ008 014 and 50HJQ008 012 Units NOTE Dimensions are in inches Fig 5 Accessory Dimensions NOTE Dimensions are in...

Page 5: ...an power source or any power source where they would be cycled more than twice per day NOTE If door interlock switch is used black power lead will be connected to the door interlock switch wir ing not...

Page 6: ...N 0 0 25 0 25 1 62 0 0 30 0 50 Fig 7 Disconnect Location 48 50HJ TJ015 028 Units and 50HJQ014 and 016 Units Fig 8 Field Fabricated Bracket for Door Interlock Switch 48 50HJ TJ015 028 Units and 50HJQ01...

Page 7: ...wired into the power Black lead between the disconnect switch and the junction box installed in Step 10 to break power to the accessory when the door is opened 7 Access doors may be equipped with a gl...

Page 8: ...ulb should glow with a blue hue If bulb cannot be seen briefly back out bulb and view from safe distance replace bulb when done If bulb does not glow check wiring safety interlock or replace bulb Inst...

Page 9: ...ll 0 406 in hole in unit z flange 1 75 in from end of door for pushbutton of interlock switch Push button will go through unit z flange and will be contacted by door See Fig 15 Use insulated sleeve te...

Page 10: ...season Bulb output can also be checked with a UVC radiometer Replace bulb when output falls to 70 of initial reading The following bulbs can safely be used with this accessory CRSGLTUB001A00 16 in tu...

Page 11: ...stallation 48 50HJ TJ008 014 and 50HJQ008 012 Units Shown Fig 16 Disconnect Switch Wiring Hole Location 48 50HJ TJ008 014 and 50HJQ008 012 Units Only NOTE Dimensions are in inches NOTES 1 Use 18 gage...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 734 Printed in U S A Form 48 50 51SI Pg 12 4 99 Replaces New Book 1 1 1 4 4 4 Tab 1a...

Reviews: