INSTALLATION

Location — 

Germicidal lamps are installed in the evaporator

section where they will have contact with the air stream and
moist surfaces. Refer to the installation locations provided in
Fig. 1-4. The stainless steel power supply section of the acces-
sory is installed on the outside of the unit and is waterproof.
See Fig. 5 for accessory dimensions.

Make sure site can be supplied with the necessary power re-

quirements. Ensure that there is adequate clearance for service.

Installation (48/50HJ,TJ015-028 Units and
50HJQ014, 016 Units) — 

Perform the following proce-

dure to install the germicidal lamp:

1. Turn off all power to unit.
2. Install reflective material (field-supplied) in installa-

tion location if desired. Reflecting ultra-violet light
energy is recommended to enhance performance and
reduce shadows. Lining the installation area with alu-
minum or aluminum foil allows light energy to reflect
instead of being absorbed, increasing the effectiveness
of the germicidal lamp.

3. Ultra violet light may damage certain plastics and

exposed non-UVC (Ultra Violet Radiation, C-Band)
protected wires. (Drain pans will not be damaged.)
Wrap exposed plastic and wiring with aluminum tape
or use metal conduit.

4. Mount field-provided light-switch disconnect switch

on unit hood. See Fig. 1, 6, and 7. Disconnect switch
should have a waterproof housing.

5. A separate source power supply must be routed to the

accessory germicidal lamp’s unit mounted disconnect
switch per applicable codes. Unit wiring and control
box connections should not be used. Refer to the Pack-
age Usage table for electrical characteristics of power
supply. Power source must be a suitable fused,
grounded, protected source with the correct voltage.
Other voltages will permanently damage the germi-
cidal lamp.
Wire per Table 1.

Table 1 — Wiring Recommendations

6. Any hinged potential access panel or door to the instal-

lation area must be interlocked with the accessory
power source to turn the lamp off if the door is opened.
Access doors should be labelled with appropriate
warnings about exposure to ultra-violet light.
A pushbutton door interlock switch (Carrier Part     No.
HR54ZA101) is required on all hinged access panels.
Use a field-fabricated and -installed bracket to mount
the door interlock switch to the unit corner post. See
Fig. 6 and 8. Use insulated sleeve terminals for con-
nection to interlock switch. The pushbutton door inter-
lock switch is not required on non-hinged access
panels. Door interlock switch should be located on the
side of the access door that opens. Locate the switch
near the top of the door so it will not be in a location
where it interferes with maintenance or service.
Run wiring into disconnect switch. Door interlock
switch should be wired into the power (Black) lead,
between the disconnect switch and the germicidal
lamp, to break power to the accessory when the door is
opened.

7. Access doors may be equipped with a glass or Lexan

®

window to view lamps. 
A glass or Lexan window will not pass ultra-violet
rays and is not a safety risk.

8. Using the accessory as a template, mark two 1-in.

insertion holes on the mounting surface. Mark 8 holes
for accessory mounting. See Fig. 1 and 5 for location.
The 1-in. holes are used for electrical connections and
the germicidal bulb. See Fig. 5.

WIRING

COLOR

Power

Black

Neutral

White

Ground

Green

BULB

1.50

UVC DISCONNECT
SWITCH

36.00

ECONOMIZER
HOOD

TYP

5.00

30.00

TYP

UNIT TOP
COVER

TYPICAL
INDOOR
FAN SECTION
(TOP VIEW)

STRAIN
RELIEF
BUSHING
REQ.

7/8"
HOLE

7/8" HOLE
(REQUIRED
FOR
CONDUIT
ONLY)

BULB

Fig. 1 — Germicidal Lamps Installation Location — 48/50HJ,TJ015-028 and 50HJQ014 and 016 Units

NOTES: 
1. Dimensions are in inches.
2. Dimensions are from out-

side edges.

3. Wiring is shown with

ROMEX cable. If conduit is
used, two holes in bracket
are used.

Summary of Contents for CRNEMAFX001A00

Page 1: ...s and microbial growth The Carrier germicidal lamps have been specifically de signed and optimized for 40 to 45 F high humidity operation in a moving airstream inside an HVAC unit The Carrier germi ci...

Page 2: ...le 1 Table 1 Wiring Recommendations 6 Any hinged potential access panel or door to the instal lation area must be interlocked with the accessory power source to turn the lamp off if the door is opened...

Page 3: ...e of part 2 On size 038 048 units use 4 bulbs spaced at 34 00 On size 054 068 units use 5 bulbs spaced at 34 00 3 Dimensions are in inches Fig 2 Germicidal Lamps Installation Location 48 50EJ EK EW EY...

Page 4: ...ll 1 in holes in unit where marked Fig 4 Germicidal Lamps Installation Location 48 50HJ TJ008 014 and 50HJQ008 012 Units NOTE Dimensions are in inches Fig 5 Accessory Dimensions NOTE Dimensions are in...

Page 5: ...an power source or any power source where they would be cycled more than twice per day NOTE If door interlock switch is used black power lead will be connected to the door interlock switch wir ing not...

Page 6: ...N 0 0 25 0 25 1 62 0 0 30 0 50 Fig 7 Disconnect Location 48 50HJ TJ015 028 Units and 50HJQ014 and 016 Units Fig 8 Field Fabricated Bracket for Door Interlock Switch 48 50HJ TJ015 028 Units and 50HJQ01...

Page 7: ...wired into the power Black lead between the disconnect switch and the junction box installed in Step 10 to break power to the accessory when the door is opened 7 Access doors may be equipped with a gl...

Page 8: ...ulb should glow with a blue hue If bulb cannot be seen briefly back out bulb and view from safe distance replace bulb when done If bulb does not glow check wiring safety interlock or replace bulb Inst...

Page 9: ...ll 0 406 in hole in unit z flange 1 75 in from end of door for pushbutton of interlock switch Push button will go through unit z flange and will be contacted by door See Fig 15 Use insulated sleeve te...

Page 10: ...season Bulb output can also be checked with a UVC radiometer Replace bulb when output falls to 70 of initial reading The following bulbs can safely be used with this accessory CRSGLTUB001A00 16 in tu...

Page 11: ...stallation 48 50HJ TJ008 014 and 50HJQ008 012 Units Shown Fig 16 Disconnect Switch Wiring Hole Location 48 50HJ TJ008 014 and 50HJQ008 012 Units Only NOTE Dimensions are in inches NOTES 1 Use 18 gage...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 734 Printed in U S A Form 48 50 51SI Pg 12 4 99 Replaces New Book 1 1 1 4 4 4 Tab 1a...

Reviews: