3. Ultra violet light may damage certain plastics and

exposed non-UVC protected wires. (Drain pans will
not be damaged.) Wrap exposed plastic and wiring
with aluminum tape or use metal conduit.

4. Mount field-provided light-switch disconnect switch

on unit. See Fig. 11 for location. Disconnect switch
should have a waterproof housing.

5. A separate source power supply must be routed to the

accessory germicidal lamp’s unit mounted disconnect
switch per applicable codes. Unit wiring and control
box connections should not be used. Refer to the Pack-
age Usage table for electrical characteristics of power
supply. Power source must be a suitable fused,
grounded, protected source with the correct voltage.
Other voltages will permanently damage the germi-
cidal lamp.
Wire per Table 1.

6. Any hinged potential access panel or door to the instal-

lation area must be interlocked with the accessory
power source to turn the lamp off if the door is opened.
Access doors should be labelled with appropriate
warnings about exposure to ultra-violet light.
A pushbutton door interlock switch (Carrier Part No.
HR54ZA101) is required on all hinged access panels.
Use a field-fabricated and -installed bracket to mount
the door interlock switch. See Fig. 8. Use insulated
sleeve terminals for connection to interlock switch.
The pushbutton door interlock switch is not required
on non-hinged access panels. Door interlock switch
should be located on the side of the access door that
opens. Locate the switch near the top of the door so it
will not be in a location where it interferes with main-
tenance or service.
Run wiring into disconnect switch. Door interlock
switch should be wired into the power (Black) lead,
between the disconnect switch and the junction box
(installed in Step 10), to break power to the accessory
when the door is opened.

7. Access doors may be equipped with a glass or Lexan

®

window to view lamps. A glass or Lexan window will
not pass ultra-violet rays and is not a safety risk.

8. Using the accessory as a template, mark two 1-in.

insertion holes on the mounting surface. Mark 8 holes
for accessory mounting. See Fig. 2 for location. The
1-in. holes are used for electrical connections and the
germicidal bulb. See Fig. 5.

9. Drill 1-in. holes where marked.

10. Use field-supplied no. 10 self-drilling screws to attach

accessory to unit.

NOTE: Holes can be drilled in unit if self-drilling
screws are not used. Drill 8 holes for eight no. 10
screws used to attach accessory to unit. Using eight no.
10 screws, attach accessory to unit.

Be sure accessory has a watertight seal against unit
wall. Use standard 1/2-in. strain relief connectors
when running wiring through any hole in unit.

Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.

UVC EXPOSURE HAZARD

RISQUE D'EXPOSITION AUX UVC

Turn off power to UVC lights before servicing or repairing.

Never expose unprotected eyes or skin to the UVC light.

This unit contains high energy ultraviolet C-band (UVC) germicidal
lamps which can cause serious temporary eye and skin irritation.

Couper l'alimentation des lampes UVC avant l'entretien ou les
reparations.
Cet appareil contient des lampes germicides haute energie a ultra-violets
de bande C (UVC), qui peuvent causer l'irritation momentanee grave des
yeux et de la peau.
Ne jamais exposer les yeux ou la peau non proteges a la lumiere UVC.

CU000135

WARNING

!

AVERTISSEMENT

!

`

`

`

`

`

`

`

`

Fig. 10 — Warning Label

TO DISCONNECT

SWITCH OR

JUNCTION

BOX

BLK

WHT

GRN

GRN

GRN

Fig. 9 — Accessory Wiring

Summary of Contents for CRNEMAFX001A00

Page 1: ...s and microbial growth The Carrier germicidal lamps have been specifically de signed and optimized for 40 to 45 F high humidity operation in a moving airstream inside an HVAC unit The Carrier germi ci...

Page 2: ...le 1 Table 1 Wiring Recommendations 6 Any hinged potential access panel or door to the instal lation area must be interlocked with the accessory power source to turn the lamp off if the door is opened...

Page 3: ...e of part 2 On size 038 048 units use 4 bulbs spaced at 34 00 On size 054 068 units use 5 bulbs spaced at 34 00 3 Dimensions are in inches Fig 2 Germicidal Lamps Installation Location 48 50EJ EK EW EY...

Page 4: ...ll 1 in holes in unit where marked Fig 4 Germicidal Lamps Installation Location 48 50HJ TJ008 014 and 50HJQ008 012 Units NOTE Dimensions are in inches Fig 5 Accessory Dimensions NOTE Dimensions are in...

Page 5: ...an power source or any power source where they would be cycled more than twice per day NOTE If door interlock switch is used black power lead will be connected to the door interlock switch wir ing not...

Page 6: ...N 0 0 25 0 25 1 62 0 0 30 0 50 Fig 7 Disconnect Location 48 50HJ TJ015 028 Units and 50HJQ014 and 016 Units Fig 8 Field Fabricated Bracket for Door Interlock Switch 48 50HJ TJ015 028 Units and 50HJQ01...

Page 7: ...wired into the power Black lead between the disconnect switch and the junction box installed in Step 10 to break power to the accessory when the door is opened 7 Access doors may be equipped with a gl...

Page 8: ...ulb should glow with a blue hue If bulb cannot be seen briefly back out bulb and view from safe distance replace bulb when done If bulb does not glow check wiring safety interlock or replace bulb Inst...

Page 9: ...ll 0 406 in hole in unit z flange 1 75 in from end of door for pushbutton of interlock switch Push button will go through unit z flange and will be contacted by door See Fig 15 Use insulated sleeve te...

Page 10: ...season Bulb output can also be checked with a UVC radiometer Replace bulb when output falls to 70 of initial reading The following bulbs can safely be used with this accessory CRSGLTUB001A00 16 in tu...

Page 11: ...stallation 48 50HJ TJ008 014 and 50HJQ008 012 Units Shown Fig 16 Disconnect Switch Wiring Hole Location 48 50HJ TJ008 014 and 50HJQ008 012 Units Only NOTE Dimensions are in inches NOTES 1 Use 18 gage...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 734 Printed in U S A Form 48 50 51SI Pg 12 4 99 Replaces New Book 1 1 1 4 4 4 Tab 1a...

Reviews: