7.3 - flow detection

Evaporator flow switch and chilled water pump interlock

IMPORTANT: It is mandatory that the water flow switch 
must be energised while the machine is in operation. 
Failure to follow this instruction will void the Carrier 
guarantee.

The water flow switch is installed on the evaporator water 

inlet and adjusted by the controls, based on unit size and 
application. If adjustment is necessary, it must be carried 

out by qualified personnel trained by Carrier Service.

Terminals 34 and 35 are provided for field installation of 

the chilled water pump interlock (auxiliary contact for pump 
operation to be wired on site).

7.4 - Evaporator water box bolt tightening

The evaporator is of the shell and tube type with 
removable water boxes to facilitate cleaning. Re-tightening 
or tightening must be done in accordance with the 
illustration below.

Water box tightening sequence

legend:

Sequence 1 : 1 2 3 4

Tightening torque

Sequence 2 : 5 6 7 8

Bolt size 

Sequence 3 : 9 10 11 12

M16 - 171 - 210 Nm

Sequence 4 : 13 14 15 16

NOTE: Before this operation we recommend draining the 
circuit and disconnecting the pipes to be sure that the bolts 
are correctly and uniformly tightened.

7.5 - freeze protection

The evaporator, the pipes and the hydronic module pump 
might be damage by freeze. The components of the unit 
(evaporator and hydronic module) will be protected by 
following the recommendations below. Protection of the 
remainder of the system is the responsability of the 
installer. Damage due to freezing is not covered by the 
warranty.

7.5.1 - standard machine

If the chiller or the water piping is in an area where the 
ambient temperature can fall below 0 °C it is 
recommended to add an antifreeze solution (45% 
maximum, 40% in case of unit with hydronic module) to 
protect the unit and the water piping to a temperature of 
10 K below the lowest temperature likely to be reached at 

the installation site. Use only antifreeze solutions, 

approved for heat exchanger duty. If the system is not 
protected by an antifreeze solution and will not be used 
during freezing weather conditions, draining of the cooler 
and outdoor piping is mandatory. Damage due to freezing 
is not covered by the warranty.

7.5.2 - optional evaporator freeze protection (30XaV-Ze)

In cases where it is not possible to apply the recommenda-
tions in paragraph 7.5.1, the units can be equipped with 
heaters to protect the evaporator against freeze (option 
41A or 41B with hydronic kit). The antifreeze solution and 
heaters can be combined.

Freeze protection of units with hydronic modules requires 
that water circulates in the hydraulic circuit. The unit 
mounted pump will start, automatically, periodically.

To verify that the heater circuit is 'live'. See Chapter - 
“Standard maintenance”.

IMPORTANT: Depending on the climatic conditions in 
your area you must:
• 

Add ethylene glycol with an adequate concentration 
to protect the installation up to a temperature of 10 
K below the lowest temperature likely to occur at the 
installation site.

• 

If the unit is not used for an extended period, it is 
recommended to drain it, and as a safety precaution 
add ethylene glycol to the heat exchanger, using the 
drain point located near the water inlet connection 
(a purge connec-tion is available somewhere on the 
heat exchanger water box in case the machine is not 
perfectly level).

• 

At the start of the next season, refill the unit with water 
and add an inhibitor.

• 

For the installation of auxiliary equipment, the instal-
ler must comply with basic regulations, especially for 
minimum and maximum flow rates, which must be 
between the values listed in the operating limit table 
(application data).

 

7.6 - Protection against cavitation (with option 116)

To ensure the durability of pumps fitted with hydronic 

modules, the control algorithm of 30XAV-ZE units 
includes protection against cavitation. A pressure below 80 
kPa will prevent the unit from starting, or will cause a 
shutdown.  
To obtain an adequate pressure, it is recommended:

• 

to pressurise the hydronic circuit between 100 kPa 
(1 bar) and 400 kPa (4 bars) maximum at the pump 
inlet

• 

to clean the hydronic circuit during water filling or 
during its modification

• 

to regularly clean the screen filter.

Summary of Contents for AquaForce PUREtec 30XAV-ZE 401

Page 1: ...ariable Speed Air Cooled Screw Chillers AquaForce PUREtec with R1234ze E 30XAV ZE 401 901 nominal cooling capacity 400 900 kW 50 hz Original document InsTallaTIon oPEraTIon and MaInTEnancE InsTrUcTIon...

Page 2: ...CAL CONNECTION 19 5 1 Power supply 19 5 2 Voltage phase imbalance 19 5 3 Power connection disconnect switch 19 5 4 Recommended wire sections 19 5 5 Power cable entry 19 5 6 Field control wiring 20 5 7...

Page 3: ...31 9 10 Fans 31 9 11 Electronic expansion valve EXV 32 9 12 Moisture indicator 32 9 13 Filter drier 32 9 14 Sensors 32 9 15 Service valve option 92 33 9 16 Variable frequency drive 33 10 options 34 1...

Page 4: ...oom installation Local building codes and safety standards shall be followed In absence of local codes and standards please refer to EN 378 2012 Safety requirements for substances classified A2 or to...

Page 5: ...the refrigerant using a proper refrigerant reclaim device and reclaim cylinders The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings with the...

Page 6: ...lue Reactivate HP soft See dedicated Quick test function CAUTION If the test leads to replacing the pressure switch it is necessary to recover the refrigerant charge these pressure switches are not in...

Page 7: ...n equipment failure carry out a refrigerant analysis at a specialist laboratory If required change the refrigerant following a procedure such as that described in NF E29 795 If the refrigerant circuit...

Page 8: ...d with dry nitrogen Refrigerant in contact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrig...

Page 9: ...use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is...

Page 10: ...ems and they do not require earthquake resistance Earthquake resistance has not been verified CAUTION Only use slings at the designated lifting points which are marked on the unit Before siting the un...

Page 11: ...the protection of moving parts Verify the accessibility for maintenance or repair and to check the piping Verify the status of the valves Verify the quality of the thermal insulation and of the vapou...

Page 12: ...he space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporator tube removal Water inlet for standard unit For options 100A 100C 1...

Page 13: ...e close to walls please refer to chapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see no...

Page 14: ...hapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporato...

Page 15: ...sory supplied loose at the time of purchase can be added NOTES Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings available on request F...

Page 16: ...rol Minimum capacity 10 10 10 10 10 10 10 Condensers All aluminium Micro Channel Heat Exchanger MCHE Fans Standard unit Axial FLYING BIRD IV fans with rotating shroud Quantity 9 10 12 14 16 18 20 Maxi...

Page 17: ...eration with maximum unit power input Values obtained at operation with maximum unit power input Values given on the unit nameplate When the machines are equipped with two power supplies circuit 1 is...

Page 18: ...transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power in...

Page 19: ...s to the general disconnect isolator switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see...

Page 20: ...01 2x240 1x185 260 XLPE 2x185 450 PVC 501 2x240 1x240 280 XLPE 2x240 480 PVC 551 2x240 1x240 250 XLPE 2x185 350 XLPE 651 2x240 2x240 1x150 1x150 260 XLPE 2x185 2x185 550 PVC 701 2x240 2x240 1 x 240 1...

Page 21: ...be protected against freeze by using a freeze protection solution by the installer For start ups with air temperature below 5 C the machine must be equipped with option 41A Evaporator water temperatu...

Page 22: ...upied mode 6 5 System minimum water volume Whichever the system the water loop minimum capacity is given by the formula Capacity Cap kW x N litres Application N Normal air conditioning 3 25 Process ty...

Page 23: ...ne month the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration CAUTION Filling completing and draining the water circuit charge must be done...

Page 24: ...93 3 Relief valve 4 Available pressure water pump 5 Water drain valve 6 Flow switch for the evaporator 7 Evaporator 8 Evaporator heater for freeze protection option 41A 41B 9 Heater for freeze protect...

Page 25: ...ow mandatory Elbow mandatory Elbow mandatory For installation that requires thicker insulation it is advised to use a pipe reduction or an elbow to avoid the closest component When straight pipe is no...

Page 26: ...tected by an antifreeze solution and will not be used during freezing weather conditions draining of the cooler and outdoor piping is mandatory Damage due to freezing is not covered by the warranty 7...

Page 27: ...h unit controls its own water pump If there is only one common pump and in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing co...

Page 28: ...r flow is limited Low pressure pumps options 116T 116U High pressure pumps options 116R 116S Available static pressure kPa Available static pressure kPa Flow rate L s Flow rate L s 0 20 40 60 80 100 1...

Page 29: ...ity calculations Units with hydronic module enable direct monitoring of flow rate and cooling capacity through IHM refer to 30XAV ZE control manual Fluid pressure is measured by pressure sensors fitte...

Page 30: ...ns or to complement them follow the guidance programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition of the coating paint to detect blistering resu...

Page 31: ...id line valve a filter drier two EXVs a plate heat exchanger as well as protection devices seal or valve At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the he...

Page 32: ...s 6 Nominal input frequency Hz 50 Nominal voltage V 400 Number of phases 3 Motor included in the application domain of the regulation 640 2009 amendment 4 2014 NO Sales leaflet for exemption Article 1...

Page 33: ...quency drive that allows adjustment the capacity of the compressor by varying the speed of the motor within the frequency range of 27 5 60 Hz Variable speed is produced by generating a controlled volt...

Page 34: ...water column evaporator side typically high buildings 401 901 Reversed evaporator water connections 107 Evaporator with reversed water inlet outlet Easy installation on sites with specific requirement...

Page 35: ...901 EMC classification C2 as per EN 61800 3 282 Additional RFI filters on the unit power line Reduces electromagnetic interferences Increase the variable frequency drive VFD immunity level according...

Page 36: ...ion change Removal or dismantling of the HVAC unit Any intervention due to a missed established mainte nance operation Any intervention covered by the warranty 11 STANDARD MAINTENANCE To ensure optima...

Page 37: ...t be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals 1 Application torque for tightening the clamp 2 Avoid contact between...

Page 38: ...ng the pressure at the filter service port and the oil pressure port The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop...

Page 39: ...s been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been...

Page 40: ...il corrective measures have been taken Check evaporator water loop Water loop volume litres Calculated volume litres 3 25 liters nominal kW capacity for air conditioning 6 5 liters nominal kW capacity...

Page 41: ...he temperatures and pressures have stabilised record the following Evaporator entering water Evaporator leaving water Ambient temperature Circuit A suction pressure Circuit B suction pressure Circuit...

Page 42: ...42...

Page 43: ...43...

Page 44: ...com www certiflash com Order No 10159 07 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Prin...

Reviews: