According to the Regulation No. 327/2011 implementing directive 2009/125/EC with regard to ecodesign requirements
for fans driven by motors with an electric input power between 125 W and 500 kilowatts.
Product
30XaV-ZE
Global fan efficiency
%
41
Measurement category
A
Efficiency category
Static
Energy efficiency target N(2015)
N(2015) 40
Efficiency level at the optimum efficiency point
45.7
Variable frequency drive
YES
Year of manufacture
See label on the unit
Fan manufacturer
Simonin
Motor manufacturer
Leroy Somer
Fan reference
00PSG000000100A
Motor reference
00PPG000494700A
Nominal power of the motor
kW
1.84
Flow rate
m
3
/s
4.15
Pressure
at optimum energy efficiency
Pa
170
Speed
rpm
950
Specific ratio
1.002
Relevant information to facilitate the disassembly, recycling or removal of the product at the end of the life
See Maintenance Manual
Relevant information to minimise the impact on the environment
See Maintenance Manual
According to the Regulation No. 640/2009 and amendment 4/2014 implementing directive 2005/32/CE with regard to
ecodesign requirement for electric motor.
Motor type
asynchronous
Number of poles
6
Nominal input frequency
Hz
50
Nominal voltage
V
400
Number of phases
3
Motor included in the application domain of the regulation 640/2009 & amendment 4/2014
NO
Sales leaflet for exemption
Article 1.2.c).(ii)
Ambient air temperature for which the motor is specifically designed
°C
70
9.11 - Electronic expansion valve (EXV)
The EXV is equipped with a stepper motor (2785 to 3690
steps, depending on the model) that is controlled via the
EXV board.
The EXV is also equipped with a sightglass that permits
verification of the mechanism movement and the presence
of the liquid seal.
9.12 - Moisture indicator
Located on the EXV, permits control of the unit charge
and indicates moisture in the circuit. The presence of
bubbles in the sight-glass indicates an insufficient charge
or non-condensables in the system. The presence of
moisture changes the colour of the indicator paper in the
sight-glass.
9.13 - filter drier
The role of the filter drier is to keep the circuit clean and
moisture-free. The moisture indicator shows, when it is
necessary to change the element. A difference in tempera-
ture between the filter inlet and outlet shows that the
element is dirty.
9.14 - sensors
The unit uses thermistors and pressure transducers to
monitor and control the operation of the system. Refer the
Touch Pilot Control IOM for more detailed information.