background image

5

The calibration of a valve that has leaked is generally 
lower than its original calibration. The new calibration may 
affect the operating range. To avoid a nuisance tripping or 
leaks, replace or re-calibrate the valve.

Periodic check of the relief valves: See paragraph 

“Maintenance safety considerations”. Provide a drain in 

the discharge circuit, close to each relief valve, to avoid an 
accumulation of condensate or rain water.

Ensure good ventilation, as accumulation of refrigerant in 
an enclosed space can displace oxygen and cause 
asphyxiation or explosions.

Inhalation of high concentrations of vapour is harmful and 
may cause heart irregularities, unconsciousness, or death.
Vapour is heavier than air and reduces the amount of 
oxygen available for breathing. These products cause eye 
and skin irritation. Decomposition products are hazardous.

1.2 - Equipment and components under pressure

The units are intended to be stored and operate in an 
environment where the ambient temperature must not be 
less than the lowest allowable temperature indicated on 

the nameplate. See section “Pressure vessels”.

1.3 - Maintenance safety considerations

The owner / operator shall keep an updated logbook of the 
refrigerating system.
In the logbook the following information shall be 
recorded:

• 

details of all maintenance and repair work;

• 

quantities and kind of (new, reused or recycled) 
refrigerant which have been charged on each 
occasion, and the quantities of refrigerant which have 
been transferred from the system on each occasion;

• 

analysis of a reused refrigerant, if available, the results 
of which shall also be kept in the log-book;

• 

source of the reused refrigerant;

• 

changes and replacements of components of the 
system;

• 

results of all periodic routine tests;

• 

record of significant periods of non-use.

The log-book shall either be kept by the owner / operator, 
or the data shall be stored in a computer, in which case the 
information shall be accessible to the competent person 
when servicing or testing.

Engineers working on the electric or refrigeration compo-

nents must be authorized, trained and fully qualified to do so.

All refrigerant circuit work must be carried out by a 

trained person, fully qualified to work on these units. He/

she must have been trained and be familiar with the 
equipment and the installation. All welding operations 

must be carried out by qualified specialists.

Before opening a refrigerant circuit, purge and consult the 
pressure gauges. Reclaim the refrigerant using a proper 
refrigerant reclaim device and reclaim cylinders. 

The units can also be lifted with slings, using only the 
designated lifting points marked on the unit.

 

 

Use slings with the correct capacity, and always follow 
the lifting instructions on the certified drawings supplied 
with the unit. 

Safety is only guaranteed, if these instructions are carefully 
followed. If this is not the case, there is a risk of failure 
and injuries to personnel.

DO NOT COVER ANY PROTECTION DEVICES. This 
applies to the relief valves (if used) in the refrigerant or 
heat transfer medium circuits, the fuse plugs and the 
pressure switches.

The external relief valves are designed and installed to 

ensure damage limitation in case of a fire. In accordance 

with the regulations applied for the design, the European 
directive on equipment under pressure and in accordance 
with the national usage regulations:

• 

These relief valves (and rupture disk if used) are not 
safety accessories but damage limitation accessories in 

case of a fire,

• 

The high pressure switches are the safety accessories.

The relief valve must only be removed if the fire risk is 

fully controlled and after checking that this is allowed by 
local regulations and authorities. This is the responsibility 
of the operator.

When the unit is subjected to fire, safety devices prevent 

rupture due to over-pressure by releasing refrigerant. The 

fluid may then be decomposed into toxic residues when 
subjected to the flame:

• 

Stay away from the unit

• 

Set up warnings and recommendations for personnel 

in charge to stop the fire.

• 

Fire extinguishers appropriate to the system and the 
refrigerant type must be easily accessible.

The external relief valves must be connected to discharge 
pipes for units installed in a room. Refer to the installation 
regulations, for example those of European standards EN-378.

These standards include a sizing method and examples for 

configuration and calculation. Under certain conditions 

they permit connection of several valves to the same 
discharge pipe.

These pipes must be installed in a way that ensures that 
people and property are not exposed to refrigerant leaks.

These fluids may be diffused in the air, but far away from 

any building air intake, or they must be discharged in a 
quantity that is appropriate for a suitably absorbing 
environment (Note that the R1234ze(E) refrigerant is 
heavier than air).

It is recommended to install an indicating device to show if 
part of the refrigerant has leaked from the valve. The 

presence of oil at the outlet orifice is a useful indicator that 
refrigerant has leaked. Keep this orifice clean to ensure 

that any leaks are obvious.

Summary of Contents for AquaForce PUREtec 30XAV-ZE 401

Page 1: ...ariable Speed Air Cooled Screw Chillers AquaForce PUREtec with R1234ze E 30XAV ZE 401 901 nominal cooling capacity 400 900 kW 50 hz Original document InsTallaTIon oPEraTIon and MaInTEnancE InsTrUcTIon...

Page 2: ...CAL CONNECTION 19 5 1 Power supply 19 5 2 Voltage phase imbalance 19 5 3 Power connection disconnect switch 19 5 4 Recommended wire sections 19 5 5 Power cable entry 19 5 6 Field control wiring 20 5 7...

Page 3: ...31 9 10 Fans 31 9 11 Electronic expansion valve EXV 32 9 12 Moisture indicator 32 9 13 Filter drier 32 9 14 Sensors 32 9 15 Service valve option 92 33 9 16 Variable frequency drive 33 10 options 34 1...

Page 4: ...oom installation Local building codes and safety standards shall be followed In absence of local codes and standards please refer to EN 378 2012 Safety requirements for substances classified A2 or to...

Page 5: ...the refrigerant using a proper refrigerant reclaim device and reclaim cylinders The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings with the...

Page 6: ...lue Reactivate HP soft See dedicated Quick test function CAUTION If the test leads to replacing the pressure switch it is necessary to recover the refrigerant charge these pressure switches are not in...

Page 7: ...n equipment failure carry out a refrigerant analysis at a specialist laboratory If required change the refrigerant following a procedure such as that described in NF E29 795 If the refrigerant circuit...

Page 8: ...d with dry nitrogen Refrigerant in contact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrig...

Page 9: ...use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is...

Page 10: ...ems and they do not require earthquake resistance Earthquake resistance has not been verified CAUTION Only use slings at the designated lifting points which are marked on the unit Before siting the un...

Page 11: ...the protection of moving parts Verify the accessibility for maintenance or repair and to check the piping Verify the status of the valves Verify the quality of the thermal insulation and of the vapou...

Page 12: ...he space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporator tube removal Water inlet for standard unit For options 100A 100C 1...

Page 13: ...e close to walls please refer to chapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see no...

Page 14: ...hapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporato...

Page 15: ...sory supplied loose at the time of purchase can be added NOTES Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings available on request F...

Page 16: ...rol Minimum capacity 10 10 10 10 10 10 10 Condensers All aluminium Micro Channel Heat Exchanger MCHE Fans Standard unit Axial FLYING BIRD IV fans with rotating shroud Quantity 9 10 12 14 16 18 20 Maxi...

Page 17: ...eration with maximum unit power input Values obtained at operation with maximum unit power input Values given on the unit nameplate When the machines are equipped with two power supplies circuit 1 is...

Page 18: ...transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power in...

Page 19: ...s to the general disconnect isolator switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see...

Page 20: ...01 2x240 1x185 260 XLPE 2x185 450 PVC 501 2x240 1x240 280 XLPE 2x240 480 PVC 551 2x240 1x240 250 XLPE 2x185 350 XLPE 651 2x240 2x240 1x150 1x150 260 XLPE 2x185 2x185 550 PVC 701 2x240 2x240 1 x 240 1...

Page 21: ...be protected against freeze by using a freeze protection solution by the installer For start ups with air temperature below 5 C the machine must be equipped with option 41A Evaporator water temperatu...

Page 22: ...upied mode 6 5 System minimum water volume Whichever the system the water loop minimum capacity is given by the formula Capacity Cap kW x N litres Application N Normal air conditioning 3 25 Process ty...

Page 23: ...ne month the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration CAUTION Filling completing and draining the water circuit charge must be done...

Page 24: ...93 3 Relief valve 4 Available pressure water pump 5 Water drain valve 6 Flow switch for the evaporator 7 Evaporator 8 Evaporator heater for freeze protection option 41A 41B 9 Heater for freeze protect...

Page 25: ...ow mandatory Elbow mandatory Elbow mandatory For installation that requires thicker insulation it is advised to use a pipe reduction or an elbow to avoid the closest component When straight pipe is no...

Page 26: ...tected by an antifreeze solution and will not be used during freezing weather conditions draining of the cooler and outdoor piping is mandatory Damage due to freezing is not covered by the warranty 7...

Page 27: ...h unit controls its own water pump If there is only one common pump and in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing co...

Page 28: ...r flow is limited Low pressure pumps options 116T 116U High pressure pumps options 116R 116S Available static pressure kPa Available static pressure kPa Flow rate L s Flow rate L s 0 20 40 60 80 100 1...

Page 29: ...ity calculations Units with hydronic module enable direct monitoring of flow rate and cooling capacity through IHM refer to 30XAV ZE control manual Fluid pressure is measured by pressure sensors fitte...

Page 30: ...ns or to complement them follow the guidance programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition of the coating paint to detect blistering resu...

Page 31: ...id line valve a filter drier two EXVs a plate heat exchanger as well as protection devices seal or valve At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the he...

Page 32: ...s 6 Nominal input frequency Hz 50 Nominal voltage V 400 Number of phases 3 Motor included in the application domain of the regulation 640 2009 amendment 4 2014 NO Sales leaflet for exemption Article 1...

Page 33: ...quency drive that allows adjustment the capacity of the compressor by varying the speed of the motor within the frequency range of 27 5 60 Hz Variable speed is produced by generating a controlled volt...

Page 34: ...water column evaporator side typically high buildings 401 901 Reversed evaporator water connections 107 Evaporator with reversed water inlet outlet Easy installation on sites with specific requirement...

Page 35: ...901 EMC classification C2 as per EN 61800 3 282 Additional RFI filters on the unit power line Reduces electromagnetic interferences Increase the variable frequency drive VFD immunity level according...

Page 36: ...ion change Removal or dismantling of the HVAC unit Any intervention due to a missed established mainte nance operation Any intervention covered by the warranty 11 STANDARD MAINTENANCE To ensure optima...

Page 37: ...t be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals 1 Application torque for tightening the clamp 2 Avoid contact between...

Page 38: ...ng the pressure at the filter service port and the oil pressure port The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop...

Page 39: ...s been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been...

Page 40: ...il corrective measures have been taken Check evaporator water loop Water loop volume litres Calculated volume litres 3 25 liters nominal kW capacity for air conditioning 6 5 liters nominal kW capacity...

Page 41: ...he temperatures and pressures have stabilised record the following Evaporator entering water Evaporator leaving water Ambient temperature Circuit A suction pressure Circuit B suction pressure Circuit...

Page 42: ...42...

Page 43: ...43...

Page 44: ...com www certiflash com Order No 10159 07 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Prin...

Reviews: