background image

19

5 - eleCTRICal CONNeCTION

Please refer to the certified dimensional drawings, supplied 

with the unit.

5.1 - Power supply

The power supply must conform to the specification on the 

chiller nameplate. The supply voltage must be within the 

range specified in the electrical data table. For connections 
refer to the wiring diagrams and the certified dimensional 

drawings.

WARNING: Operation of the chiller with an improper 
supply voltage or excessive phase imbalance constitutes 
abuse which will invalidate the Carrier warranty. If the 
phase imbalance exceeds 2% for voltage, or 10% for 
current, contact your local electricity supply at once and 
ensure that the chiller is not switched on until corrective 
measures have been taken.

5.2 - Voltage phase imbalance (%) 

100 x max. deviation from average voltage

Average voltage

example:

On a 400 V - 3 ph - 50 Hz supply, the individual phase 
voltages were measured to be:
AB = 406 V; BC = 399; AC = 394 V

Average voltage = (406 + 399 + 394)/3 = 1199/3
 

 

= 399.7 say 400 V

Calculate the maximum deviation from the 400 V average:

(AB) = 406 - 400 = 6 
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6 

The maximum deviation from the average is 6 V. The 
greatest percentage deviation is: 100 x 6/400 = 1.5 %

This is less than the permissible 2% and therefore acceptable.

5.3 - Power connection/disconnect switch

standard:

 -

30XAV-ZE 0401 to 0551 units have one 
connection point.

 -

30XAV-ZE 0651 to 0901 units have two 
connection points (one with option 81).

Motor

5.4 - recommended wire sections

Wire sizing is the responsibility of the installer, and depends 
on the characteristics and regulations applicable to each 
installation site. The following is only to be used as a guide-
line, and does not make Carrier in any way liable. After 

wire sizing has been completed, using the certified 

dimensional drawing, the installer must ensure easy 

connection and define any modifications necessary on site.

The connections provided as standard for the field-supplied 

power entry cables to the general disconnect/isolator switch 
are designed for the number and type of wires, listed in 
column 2 of the table on the next page.

The calculations are based on the maximum machine 
current (see electrical data tables).

The calculations of favourable and unfavourable cases are 
based on the maximum current for each unit (see electrical 
data tables). For the design the standardised installation 
methods in accordance with IEC 60364 are used: PVC  
(70 °C) or XLPE (90 °C) insulated cables with copper core; 
arrangement to comply with table 52c of the above standard. 
The maximum temperature is 46 °C. The given maximum 
length is calculated to limit the voltage drop to 5%.

IMPORTANT: Before connection of  the main power 
cables (L1 - L2 - L3) on the terminal block, it is imperative 
to check the phase rotation of the 3 phases before 
proceeding to the connection on then terminal block or 
the main disconnect/isolator switch.

5.5 - Power cable entry

The power cables can enter the 30XAV-ZE control box 
from below or from the unit side: refer to unit drawings. 
For 30XAV-ZE unit sizes 401 to 901 the control box that 
includes the power supply cable connection terminal is 
located in the lower part of the unit. In this case the 
control box is raised by 120 mm compared to the lowest 
point of the chassis. 

The cable entry point depends on the unit configuration:
1.  Unit raised from the ground (e.g. installation on sup-

port rails): It is recommended to enter the power cables 
from below the control box. A removable aluminium 
plate below the control box allows introduction of the 
cables.

2.  Unit placed on the ground: For power cable entry from 

below the control box ensure that the cable bend radius 
is compatible with the connection space available 
in the control box. If not, an aluminium plate on the 
control box face allows introduction of the cables.

For units with three circuits with option 81 (single power 
connection point) the connection must be made from below 
the unit.

IMPORTANT: Check the cable bend radius for cable entry 
into a control box, located in the lower part of the unit.

Refer to the certified dimensional drawing for the unit.

Summary of Contents for AquaForce PUREtec 30XAV-ZE 401

Page 1: ...ariable Speed Air Cooled Screw Chillers AquaForce PUREtec with R1234ze E 30XAV ZE 401 901 nominal cooling capacity 400 900 kW 50 hz Original document InsTallaTIon oPEraTIon and MaInTEnancE InsTrUcTIon...

Page 2: ...CAL CONNECTION 19 5 1 Power supply 19 5 2 Voltage phase imbalance 19 5 3 Power connection disconnect switch 19 5 4 Recommended wire sections 19 5 5 Power cable entry 19 5 6 Field control wiring 20 5 7...

Page 3: ...31 9 10 Fans 31 9 11 Electronic expansion valve EXV 32 9 12 Moisture indicator 32 9 13 Filter drier 32 9 14 Sensors 32 9 15 Service valve option 92 33 9 16 Variable frequency drive 33 10 options 34 1...

Page 4: ...oom installation Local building codes and safety standards shall be followed In absence of local codes and standards please refer to EN 378 2012 Safety requirements for substances classified A2 or to...

Page 5: ...the refrigerant using a proper refrigerant reclaim device and reclaim cylinders The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings with the...

Page 6: ...lue Reactivate HP soft See dedicated Quick test function CAUTION If the test leads to replacing the pressure switch it is necessary to recover the refrigerant charge these pressure switches are not in...

Page 7: ...n equipment failure carry out a refrigerant analysis at a specialist laboratory If required change the refrigerant following a procedure such as that described in NF E29 795 If the refrigerant circuit...

Page 8: ...d with dry nitrogen Refrigerant in contact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrig...

Page 9: ...use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is...

Page 10: ...ems and they do not require earthquake resistance Earthquake resistance has not been verified CAUTION Only use slings at the designated lifting points which are marked on the unit Before siting the un...

Page 11: ...the protection of moving parts Verify the accessibility for maintenance or repair and to check the piping Verify the status of the valves Verify the quality of the thermal insulation and of the vapou...

Page 12: ...he space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporator tube removal Water inlet for standard unit For options 100A 100C 1...

Page 13: ...e close to walls please refer to chapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see no...

Page 14: ...hapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporato...

Page 15: ...sory supplied loose at the time of purchase can be added NOTES Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings available on request F...

Page 16: ...rol Minimum capacity 10 10 10 10 10 10 10 Condensers All aluminium Micro Channel Heat Exchanger MCHE Fans Standard unit Axial FLYING BIRD IV fans with rotating shroud Quantity 9 10 12 14 16 18 20 Maxi...

Page 17: ...eration with maximum unit power input Values obtained at operation with maximum unit power input Values given on the unit nameplate When the machines are equipped with two power supplies circuit 1 is...

Page 18: ...transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power in...

Page 19: ...s to the general disconnect isolator switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see...

Page 20: ...01 2x240 1x185 260 XLPE 2x185 450 PVC 501 2x240 1x240 280 XLPE 2x240 480 PVC 551 2x240 1x240 250 XLPE 2x185 350 XLPE 651 2x240 2x240 1x150 1x150 260 XLPE 2x185 2x185 550 PVC 701 2x240 2x240 1 x 240 1...

Page 21: ...be protected against freeze by using a freeze protection solution by the installer For start ups with air temperature below 5 C the machine must be equipped with option 41A Evaporator water temperatu...

Page 22: ...upied mode 6 5 System minimum water volume Whichever the system the water loop minimum capacity is given by the formula Capacity Cap kW x N litres Application N Normal air conditioning 3 25 Process ty...

Page 23: ...ne month the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration CAUTION Filling completing and draining the water circuit charge must be done...

Page 24: ...93 3 Relief valve 4 Available pressure water pump 5 Water drain valve 6 Flow switch for the evaporator 7 Evaporator 8 Evaporator heater for freeze protection option 41A 41B 9 Heater for freeze protect...

Page 25: ...ow mandatory Elbow mandatory Elbow mandatory For installation that requires thicker insulation it is advised to use a pipe reduction or an elbow to avoid the closest component When straight pipe is no...

Page 26: ...tected by an antifreeze solution and will not be used during freezing weather conditions draining of the cooler and outdoor piping is mandatory Damage due to freezing is not covered by the warranty 7...

Page 27: ...h unit controls its own water pump If there is only one common pump and in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing co...

Page 28: ...r flow is limited Low pressure pumps options 116T 116U High pressure pumps options 116R 116S Available static pressure kPa Available static pressure kPa Flow rate L s Flow rate L s 0 20 40 60 80 100 1...

Page 29: ...ity calculations Units with hydronic module enable direct monitoring of flow rate and cooling capacity through IHM refer to 30XAV ZE control manual Fluid pressure is measured by pressure sensors fitte...

Page 30: ...ns or to complement them follow the guidance programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition of the coating paint to detect blistering resu...

Page 31: ...id line valve a filter drier two EXVs a plate heat exchanger as well as protection devices seal or valve At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the he...

Page 32: ...s 6 Nominal input frequency Hz 50 Nominal voltage V 400 Number of phases 3 Motor included in the application domain of the regulation 640 2009 amendment 4 2014 NO Sales leaflet for exemption Article 1...

Page 33: ...quency drive that allows adjustment the capacity of the compressor by varying the speed of the motor within the frequency range of 27 5 60 Hz Variable speed is produced by generating a controlled volt...

Page 34: ...water column evaporator side typically high buildings 401 901 Reversed evaporator water connections 107 Evaporator with reversed water inlet outlet Easy installation on sites with specific requirement...

Page 35: ...901 EMC classification C2 as per EN 61800 3 282 Additional RFI filters on the unit power line Reduces electromagnetic interferences Increase the variable frequency drive VFD immunity level according...

Page 36: ...ion change Removal or dismantling of the HVAC unit Any intervention due to a missed established mainte nance operation Any intervention covered by the warranty 11 STANDARD MAINTENANCE To ensure optima...

Page 37: ...t be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals 1 Application torque for tightening the clamp 2 Avoid contact between...

Page 38: ...ng the pressure at the filter service port and the oil pressure port The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop...

Page 39: ...s been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been...

Page 40: ...il corrective measures have been taken Check evaporator water loop Water loop volume litres Calculated volume litres 3 25 liters nominal kW capacity for air conditioning 6 5 liters nominal kW capacity...

Page 41: ...he temperatures and pressures have stabilised record the following Evaporator entering water Evaporator leaving water Ambient temperature Circuit A suction pressure Circuit B suction pressure Circuit...

Page 42: ...42...

Page 43: ...43...

Page 44: ...com www certiflash com Order No 10159 07 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Prin...

Reviews: