background image

31

9.7.5 - Corrosion allowances

Gas side: 0 mm

Heat exchange fluid side: 1 mm for tubular plates in lightly 

alloyed steels, 0 mm for stainless steel plates or plates with 
copper-nickel or stainless steel protection.

9.7.6 - evaporator

30XAV-ZE chillers use a flooded multi-tube evaporator. The 

water circulates in the tubes and the refrigerant is on the 
outside in the shell. One vessel is used to serve both 
refrigerant circuits. There is a centre tube sheet which 
separates the two refrigerant circuits. The tubes are 3/4” 
diameter copper with an enhanced surface inside and out. 
There is just one water circuit with two water passes (one 
pass when 100C is selected).

The evaporator has been tested and stamped in accordance 
with the applicable pressure code. The maximum maximum 
standard relative operating pressure is 2100 kPa for  
refrigerant side and 1000 kPa for water side. These pressures 
can be different depending on the regulation and the code 
applied.

The evaporator has a thermal insulation of 19 mm thick 

polyurethane foam, aluminium cladding may be fitted as 

an option and is equipped with a water vent and purge. 

The water connection of the heat exchanger is a Victaulic 
connection. As an option the evaporator is available with 
freeze protection (evaporator freeze protection option).

The products that may be added for thermal insulation of 
the containers during the water piping connection procedure 
must be chemically neutral in relation to the materials and 
coatings to which they are applied. This is also the case for 
the products originally supplied by Carrier.

9.7.7 - oil separator

In these units, the oil separator is a pressure vessel that is 
mounted under the outside vertical condenser coils. 
Discharge gas at the compressor outlet is directed towards 
the bottom of the oil separator and most of the oil separates 
from the gas by strong deceleration and by gravity. The gas 

then flows through a wire mesh screen where the remaining 
oil is separated by coalescence and flows to the bottom of 

the vessel. The gas is now free from oil and leaves the 
vessel at the top towards the condenser.

The oil separator is equipped with a trace heater regulated 
by the unit controls.

9.7.8 - assembly function

The assembly function includes a liquid line valve, a filter 

drier, two EXVs, a plate heat exchanger as well as 
protection devices (seal or valve).
At the condenser outlet a part of the liquid is expanded via 
the secondary EXV in one of the heat exchanger port and 
then returns as gas at the compressor economiser. This 
expansion increases the sub-cooling of the bulk of the 

liquid refrigerant which then flows into the evaporator via 

the main EXV.  This increases both the capacity and 

efficiency of the system.

9.8 - high-pressure safety switch

30XAV-ZE units are equipped with high-pressure safety 
switches.

In accordance with the applicable code the high-pressure 
switches with manual reset, called PZH (former DBK), may 
be backed up by high-pressure switches that require 
resetting with a tool. The high-pressure switches that 
require resetting with a tool are called PZHH (former 
SDBK). If a PZHH cuts out,  the corresponding PZH in 
the same compressor is faulty and must be replaced. The 
PZHH must be reset with a blunt tool with a diameter of 
less than 6 mm. Insert this tool into the opening on the 
pressure switch and push the reset. 

These pressure switches are located at the discharge of each 
compressor.

9.9 - condensers

30XAV-ZE coils are all-aluminium micro-channel 
condensers.  

9.10 - fans

The fans are axial Flying Bird fans equipped with rotating
shroud and made of composite recyclable material. Each

motor is fixed with transverse supports. The motors are

three-phase, with permanently lubricated bearings and
insulation class F (level IP55).

All fans in the same refrigerant circuit are controlled by 
one or two variable speed drives. Therefore, they operate 
together at the same rotational speed. The rotational speed 
at full load or partial load of each circuit is controlled by 
an algorithm that continuously optimises the condensing 

temperature to obtain the best energy efficiency (EER) 

whatever the operating conditions.

9.10.1 - fan motor electrical protection

The motors of a same circuit are electrically protected by 
the variable frequency drive in case of short-circuit, locked 
rotor or general overload. Each variable frequency drive 
follows a variable current characteristic, based on the 
frequency from 5 to 50 Hz and the number of fans 
controlled.

In case of fan failure (in open circuit), the variable 
frequency drive will automatically detect the problem and 
send an alert to the user interface. Refer to the 30XAV-ZE 

control manual for the list of alarms specific to this option.

Summary of Contents for AquaForce PUREtec 30XAV-ZE 401

Page 1: ...ariable Speed Air Cooled Screw Chillers AquaForce PUREtec with R1234ze E 30XAV ZE 401 901 nominal cooling capacity 400 900 kW 50 hz Original document InsTallaTIon oPEraTIon and MaInTEnancE InsTrUcTIon...

Page 2: ...CAL CONNECTION 19 5 1 Power supply 19 5 2 Voltage phase imbalance 19 5 3 Power connection disconnect switch 19 5 4 Recommended wire sections 19 5 5 Power cable entry 19 5 6 Field control wiring 20 5 7...

Page 3: ...31 9 10 Fans 31 9 11 Electronic expansion valve EXV 32 9 12 Moisture indicator 32 9 13 Filter drier 32 9 14 Sensors 32 9 15 Service valve option 92 33 9 16 Variable frequency drive 33 10 options 34 1...

Page 4: ...oom installation Local building codes and safety standards shall be followed In absence of local codes and standards please refer to EN 378 2012 Safety requirements for substances classified A2 or to...

Page 5: ...the refrigerant using a proper refrigerant reclaim device and reclaim cylinders The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings with the...

Page 6: ...lue Reactivate HP soft See dedicated Quick test function CAUTION If the test leads to replacing the pressure switch it is necessary to recover the refrigerant charge these pressure switches are not in...

Page 7: ...n equipment failure carry out a refrigerant analysis at a specialist laboratory If required change the refrigerant following a procedure such as that described in NF E29 795 If the refrigerant circuit...

Page 8: ...d with dry nitrogen Refrigerant in contact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrig...

Page 9: ...use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is...

Page 10: ...ems and they do not require earthquake resistance Earthquake resistance has not been verified CAUTION Only use slings at the designated lifting points which are marked on the unit Before siting the un...

Page 11: ...the protection of moving parts Verify the accessibility for maintenance or repair and to check the piping Verify the status of the valves Verify the quality of the thermal insulation and of the vapou...

Page 12: ...he space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporator tube removal Water inlet for standard unit For options 100A 100C 1...

Page 13: ...e close to walls please refer to chapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see no...

Page 14: ...hapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporato...

Page 15: ...sory supplied loose at the time of purchase can be added NOTES Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings available on request F...

Page 16: ...rol Minimum capacity 10 10 10 10 10 10 10 Condensers All aluminium Micro Channel Heat Exchanger MCHE Fans Standard unit Axial FLYING BIRD IV fans with rotating shroud Quantity 9 10 12 14 16 18 20 Maxi...

Page 17: ...eration with maximum unit power input Values obtained at operation with maximum unit power input Values given on the unit nameplate When the machines are equipped with two power supplies circuit 1 is...

Page 18: ...transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power in...

Page 19: ...s to the general disconnect isolator switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see...

Page 20: ...01 2x240 1x185 260 XLPE 2x185 450 PVC 501 2x240 1x240 280 XLPE 2x240 480 PVC 551 2x240 1x240 250 XLPE 2x185 350 XLPE 651 2x240 2x240 1x150 1x150 260 XLPE 2x185 2x185 550 PVC 701 2x240 2x240 1 x 240 1...

Page 21: ...be protected against freeze by using a freeze protection solution by the installer For start ups with air temperature below 5 C the machine must be equipped with option 41A Evaporator water temperatu...

Page 22: ...upied mode 6 5 System minimum water volume Whichever the system the water loop minimum capacity is given by the formula Capacity Cap kW x N litres Application N Normal air conditioning 3 25 Process ty...

Page 23: ...ne month the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration CAUTION Filling completing and draining the water circuit charge must be done...

Page 24: ...93 3 Relief valve 4 Available pressure water pump 5 Water drain valve 6 Flow switch for the evaporator 7 Evaporator 8 Evaporator heater for freeze protection option 41A 41B 9 Heater for freeze protect...

Page 25: ...ow mandatory Elbow mandatory Elbow mandatory For installation that requires thicker insulation it is advised to use a pipe reduction or an elbow to avoid the closest component When straight pipe is no...

Page 26: ...tected by an antifreeze solution and will not be used during freezing weather conditions draining of the cooler and outdoor piping is mandatory Damage due to freezing is not covered by the warranty 7...

Page 27: ...h unit controls its own water pump If there is only one common pump and in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing co...

Page 28: ...r flow is limited Low pressure pumps options 116T 116U High pressure pumps options 116R 116S Available static pressure kPa Available static pressure kPa Flow rate L s Flow rate L s 0 20 40 60 80 100 1...

Page 29: ...ity calculations Units with hydronic module enable direct monitoring of flow rate and cooling capacity through IHM refer to 30XAV ZE control manual Fluid pressure is measured by pressure sensors fitte...

Page 30: ...ns or to complement them follow the guidance programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition of the coating paint to detect blistering resu...

Page 31: ...id line valve a filter drier two EXVs a plate heat exchanger as well as protection devices seal or valve At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the he...

Page 32: ...s 6 Nominal input frequency Hz 50 Nominal voltage V 400 Number of phases 3 Motor included in the application domain of the regulation 640 2009 amendment 4 2014 NO Sales leaflet for exemption Article 1...

Page 33: ...quency drive that allows adjustment the capacity of the compressor by varying the speed of the motor within the frequency range of 27 5 60 Hz Variable speed is produced by generating a controlled volt...

Page 34: ...water column evaporator side typically high buildings 401 901 Reversed evaporator water connections 107 Evaporator with reversed water inlet outlet Easy installation on sites with specific requirement...

Page 35: ...901 EMC classification C2 as per EN 61800 3 282 Additional RFI filters on the unit power line Reduces electromagnetic interferences Increase the variable frequency drive VFD immunity level according...

Page 36: ...ion change Removal or dismantling of the HVAC unit Any intervention due to a missed established mainte nance operation Any intervention covered by the warranty 11 STANDARD MAINTENANCE To ensure optima...

Page 37: ...t be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals 1 Application torque for tightening the clamp 2 Avoid contact between...

Page 38: ...ng the pressure at the filter service port and the oil pressure port The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop...

Page 39: ...s been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been...

Page 40: ...il corrective measures have been taken Check evaporator water loop Water loop volume litres Calculated volume litres 3 25 liters nominal kW capacity for air conditioning 6 5 liters nominal kW capacity...

Page 41: ...he temperatures and pressures have stabilised record the following Evaporator entering water Evaporator leaving water Ambient temperature Circuit A suction pressure Circuit B suction pressure Circuit...

Page 42: ...42...

Page 43: ...43...

Page 44: ...com www certiflash com Order No 10159 07 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Prin...

Reviews: