Table 49 — Alarm Codes (cont)
LEGEND
PREFIX
CODE
SUFFIX
CODE
ALARM
NUMBER
ALARM DESCRIPTION
REASON FOR ALARM
ACTION TAKEN
BY CONTROL
RESET
TYPE
PROBABLE CAUSE
P
40
108
Circuit A — Repeated low
suction temp overrides
Multiple capacity
overrides due to low satu-
rated suction temperature
Circuit shut down
Automatic
Inaccurate
transducer, faulty EXV,
low refrigerant charge,
plugged or restricted
liquid line filter drier.
41
109
Circuit B — Repeated low
suction temp overrides
43
111
Low entering water tempera-
ture in heating
Not supported
—
—
—
73
112
Condenser pump #1 default
—
None
Manual
Faulty contacts, wiring
error or low control
voltage. Configuration
error.
74
113
Condenser pump #2 default
78
114
Circuit A High Discharge
Temperature
Discharge gas tempera-
ture is higher than 212 F
for more than 90 seconds
Circuit shut down
Manual
Faulty transducer/high
pressure switch, low/
restricted condenser
flow
79
115
Circuit B High Discharge
Temperature
81
117
Circuit A Low Economizer
Pressure
The economizer pressure
is below the suction pres-
sure more than 14.5 psi
for more than 10 seconds
Circuit shut down
Manual
Faulty transducer,
faulty main base board,
faulty wiring, closed
suction service valve,
faulty EXV
82
118
Circuit B Low Economizer
Pressure
87
120
Circuit A Slide Valve Control
Unverifiable
If 100% load current is
less than 1.1 times of
30% load current, or for
1 minute when active
cooling setpoint is
greater than 32 F.
None
Manual
Slide valve stuck, inac-
curate initial current
reading
88
121
Circuit B Slide Valve Control
Unverifiable
90
123
Cooler flow switch set point
configuration failure
—
None Manual
Configuration
error
91
124
Cooler flow switch failure
Flow switch open
Unit shut down
Manual if unit
is running,
automatic
otherwise
Faulty flow switch, low
cooler flow, faulty
wiring, faulty cooler
pump, faulty main base
board
Sr
nn
128
Service maintenance alert
Number # nn
Field programmed
elapsed time has expired
for maintenance time
None
Manual
Maintenance required
A1, B1
01
132-01,
133-01
Compressor Motor tempera-
ture too high
Compressor temperature
higher than 232 F for
more than 90 seconds
Circuit shut down
Manual
Economizer EXV fail-
ure (350,400 only),
faulty CPM board,
low refrigerant charge
02
132-02,
133-02
Compressor Motor tempera-
ture out of range
Compressor temperature
reading out of the range of
–40 F to 245 F
Circuit shut down
Manual
Faulty thermistor, faulty
wiring, faulty CPM
board
03
132-03,
133-03
Compressor High pressure
switch protection
HPS input on CPM board
open
Circuit shut down
Manual, press
reset button on
HPS
Loss of condenser air
flow, operation beyond
compressor envelope,
faulty high pressure
switch, faulty wiring,
faulty CPM board
04
132-04,
133-04
Compressor Over current
CPM board detects high
motor current compared
with MTA setting
Circuit shut down
Manual
Operating beyond
compressor envelope,
incorrect configuration
05
132-05,
133-05
Compressor Locked rotor
CPM board detects locked
rotor current compared
with MTA setting
Circuit shut down
Manual
Compressor motor fail-
ure, unloader slide
valve failure, compres-
sor mechanical failure
06
132-06,
133-06
Compressor Phase loss L1
CPM board detects cur-
rent unbalance greater
than 65% for more than
1 second
Circuit shut down
Manual
Blown fuse, wiring
error, loose terminals
07
132-07,
133-07
Compressor Phase loss L2
08
132-08,
133-08
Compressor Phase loss L3
09
132-09,
133-09
Compressor Low current
alarm
CPM detects motor cur-
rent less than a certain
percentage of the MTA
setting, compressor not
operating
Circuit shut down
Manual
Power supply discon-
nected, blown fuse,
wiring error, contact
deenergized, faulty
current toroid high
pressure switch trip.
CCN
—
Carrier Comfort Network
®
MLV
—
Minimum Load Valve
CPM
—
Compressor Protection Module
MOP —
Maximum Operating Pressure
EMM
—
Energy Management Module
MTA
—
Must Trip Amps
EWT
—
Entering Water Temperature
SST
—
Saturated Suction Temperature
EXV
—
Electronic Expansion Valve
UL
—
Underwriters Laboratories
HPS
—
High Pressure Switch