CL-5
Record Configuration Information
*Not supported.
TOUCH PILOT™
DESCRIPTION
NAVIGATOR
ITEM
NAVIGATOR™
SUBMODE
RANGE
DEFAULT
ENTRY
Cooling Setpoint 1
CSP.1
Set Point
COOL
XXX.X
44.0° F
Cooling Setpoint 2
CSP.2
Set Point
COOL
XXX.X
44.0° F
Cooling Ice Setpoint
CSP.3
Set Point
COOL
XXX.X
44.0° F
Current No Reset Value (Cooling)
CRV1
Set Point
COOL
XXX.X
0
Current Full Reset Value (Cooling)
CRV2
Set Point
COOL
XXX.X
0
Delta T No Reset Value (Cooling)
CRT1
Set Point
COOL
XXX.X
0
Delta T Full Reset Value (Cooling)
CRT2
Set Point
COOL
XXX.X
0
OAT No Reset Value (Cooling)
CRO1
Set Point
COOL
XXX.X
14.0° F
OAT Full Reset Value (Cooling)
CRO2
Set Point
COOL
XXX.X
14.0° F
Space T No Reset Value
CRS1
Set Point
COOL
XXX.X
14.0° F
Space T Full Reset Value
CRS2
Set Point
COOL
XXX.X
14.0° F
Cooling Reset Deg. Value
DGRC
Set Point
COOL
XX.X
0
Cool Changeover Setpoint
CAUT
Set Point
COOL
XXX.X
75° F
Cooling Ramp Loading
CRMP
Set Point
COOL
X.X
1.0
Heating Setpoint 1
HSP.1
Set Point
HEAT
XXX.X
100.0° F
Heating Setpoint 2
HSP.2
Set Point
HEAT
XXX.X
100.0° F
Current No Reset Value (Heating)
HRV1
Set Point
HEAT
XXX.X
0
Current Full Reset Value (Heating)
HRV2
Set Point
HEAT
XXX.X
0
Delta T No Reset Value (Heating)
HRT1
Set Point
HEAT
XXX.X
0
Delta T Full Reset Value (Heating)
HRT2
Set Point
HEAT
XXX.X
0
OAT No Reset Value (Heating)
HRO1
Set Point
HEAT
XXX.X
14.0° F
OAT Full Reset Value (Heating)
HRO2
Set Point
HEAT
XXX.X
14.0° F
Heating Reset Deg. Value
DGRH
Set Point
HEAT
XX.X
0
Heating Changeover Setpoint
HAUT
Set Point
HEAT
XX.X
64.0° F
Heat Ramp Loading
HRMP
Set Point
HEAT
X.X
1.0
Switch Limit Setpoint 1
DLS1
Set Point
MISC
XXX
100
Switch Limit Setpoint 2
DLS2
Set Point
MISC
XXX
100
Switch Limit Setpoint 3
DLS3
Set Point
MISC
XXX
100
Water Val Condensing Stp
W.SCT
Set Point
MISC
XXX.X
95.0° F
None (I/O Button)
OPER
Operating Modes
SLCT
X
—
Setpoint Select
SP.SE
Operating Modes
SLCT
X
—
Heal/Cool Select
HC.SE
Operating Modes
SLCT
X
COOLING