121
APPENDIX C — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
*Not supported.
NOTE: Disable quick test: all the quick test parameters shall be reset to 0.
*Not supported.
NOTE: Disable quick test: all the quick test parameters shall be reset to 0.
*Yes = service test function enable.
†0 = capacity frozen (unchanged).
1 = capacity increase.
2 = capacity decrease.
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
QCK_TST1
Quick Test Enable
no/Yes
—
Q_TSTRQ
forcible
Circuit A EXV Position
0 - 100
%
Q_EXVA
forcible
Circuit B EXV Position
0 - 100
%
Q_EXVB
forcible
Circuit C EXV Position
0 - 100
%
Q_EXVC
forcible
Cir A Economizer EXV Pos
0 - 100
%
Q_ECO_A
forcible
Cir B Economizer EXV Pos
0 - 100
%
Q_ECO_B
forcible
Cir C Economizer EXV Pos
0 - 100
%
Q_ECO_C
forcible
Circuit A Fan Stages
0-10
—
Q_FAN_A
forcible
Circuit B Fan Stages
0-10
—
Q_FAN_B
forcible
Circuit C Fan Stages
0-10
—
Q_FAN_C
forcible
Circuit A Head Press Speed
0 - 100
%
Q_VFANA
forcible
Circuit B Head Press Speed
0 - 100
%
Q_VFANB
forcible
Circuit C Head Press Speed
0 - 100
%
Q_VFANC
forcible
Circuit A Oil Heater
Off/On
—
Q_HT_A
forcible
Circuit A Oil Solenoid
Off/On
—
Q_OILS_A
forcible
Circuit A Slide Valve 1
Off/On
—
Q_SLI_1A
forcible
Circuit A Slide Valve 2
Off/On
—
Q_SLI_2A
forcible
Cir A Heater Ball Valve
Off/On
—
Q_BVL_A
forcible
Cir A Hot Gas Bypass
Off/On
—
Q_HGBP_A
forcible
Cir A DGT Cool Solenoid
Off/On
—
Q_CDGT_B
forcible
Circuit B Oil Heater
Off/On
—
Q_HT_B
forcible
Circuit B Oil Solenoid
Off/On
—
Q_OILS_B
forcible
Circuit B Slide Valve 1
Off/On
—
Q_SLI_1B
forcible
Circuit B Slide Valve 2
Off/On
—
Q_SLI_2B
forcible
Cir A Heater Ball Valve
Off/On
—
Q_BVL_B
forcible
Cir B Hot Gas Bypass
Off/On
—
Q_HGBP_B
forcible
Cir B DGT Cool Solenoid
Off/On
—
Q_CDGT_B
forcible
Circuit C Oil Heater
Off/On
—
Q_HT_C
forcible
Circuit C Oil Solenoid
Off/On
—
Q_OILS_C
forcible
Circuit C Slide Valve 1
Off/On
—
Q_SLI_1C
forcible
Circuit C Slide Valve 2
Off/On
—
Q_SLI_2C
forcible
Cir C Heater Ball Valve
Off/On
—
Q_BVL_C
forcible
Cir C Hot Gas Bypass
Off/On
—
Q_HGBP_C
forcible
Cooler Heater Output
Off/On
—
Q_CL_HT
forcible
Water Exchanger Pump 1
Off/On
—
Q_PMP1
forcible
Water Exchanger Pump 2
Off/On
—
Q_PMP2
forcible
Condenser Pump 1
Off/On
—
Q_HPMP1
forcible
Condenser Pump 2*
Off/On
—
Q_HPMP2
forcible
Chiller Ready Output
Off/On
—
Q_READY
forcible
Chiller Running Output
Off/On
—
Q_RUN
forcible
Cir A Running Output
Off/On
—
Q_RUN_A
forcible
Cir B Running Output
Off/On
—
Q_RUN_B
forcible
Cir C Running Output*
Off/On
—
Q_RUN_C
forcible
Chiller Capacity in 0-10v
0 – 10.0
volt
Q_CATO
forcible
Customer Shutdown Out
Off/On
—
Q_SHUT
forcible
Alarm Relay Output
Off/On
—
Q_ALARM
forcible
Alert Relay Output
Off/On
—
Q_ALERT
forcible
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
QCK_TST2*
Quick Test Enable
no/Yes
—
Q_TSTRQ
forcible
Air Cond Enter Valve A
Off/On
—
Q_HREA_A
forcible
Air Cond Leaving Valv A
Off/On
—
Q_HRLA_A
forcible
Water Cond Enter Valv A
Off/On
—
Q_HREW_A
forcible
Water Cond Leav Valve A
Off/On
—
Q_HRLW_A
forcible
Air Cond Enter Valve B
Off/On
—
Q_HREA_B
forcible
Air Cond Leaving Valv B
Off/On
—
Q_HRLA_B
forcible
Water Cond Enter Valv B
Off/On
—
Q_HREW_B
forcible
Water Cond Leav Valve B
Off/On
—
Q_HRLW_B
forcible
HR Condenser Heater
Off/On
—
Q_CD_HT
forcible
4 way Valve Circuit A
Off/On
—
Q_RV_A
forcible
4 way Valve Circuit B
Off/On
—
Q_RV_B
forcible
Free Cooling Heater
On/Off
—
Q_FC_HTR
forcible
Free Cool A EXV Position
0 - 100
%
Q_FCEXVA
forcible
Free Cool B EXV Position
0 - 100
%
Q_FCEXVB
forcible
Free Cool A Ball Valve
Off/On
—
Q_FCBVL_A
forcible
Free Cool B Ball Valve
Off/On
—
Q_FCBVL_B
forcible
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
SERV_TST
Service Test Enable*
no/Yes
—
Q_STREQ
forcible
Compressor A Output
Off/On
—
Q_CPA
forcible
Slide Valve Capacity A
0 - 2†
—
Q_SLIA
forcible
Compressor B Output
Off/On
—
Q_CPB
forcible
Slide Valve Capacity B
0 - 2†
—
Q_SLIB
forcible
Compressor C Output
Off/On
—
Q_CPC
forcible
Slide Valve Capacity C
0 - 2†
—
Q_SLIC
forcible