APPENDIX C — CCN TABLES (cont)
CONFIGURATION TABLES (cont)
*Not supported.
†Only condenser pump sequence 1 is supported.
NOTES:
1. Flow checked if pump off needed when a command is sent to the primary
pump to prevent cooler from freezing in winter conditions. Command will
set the cooler flow switch to closed while the controls stop the cooler
pump. The controls may then generate an alarm. If this decision is active,
the cooler flow switch is not checked when the cooler pump is stopped.
2. If cooling reset select set point has been selected the set point based on
4-20mA input signal through
Comfort
Link™ control, then a 4-20 mA reset
function shall be ignored. Configuration 3 (4-20mA Control) and 4 (Space
Temperature) shall require an Energy Management Module.
3. Configuration 2 (4-20mA Control) shall require an Energy Management
Module. Configuration 1 Switch Demand limit provides 3 step demand limit
if an Energy Management Module is present. Otherwise, only one step is
allowed.
4. Reverse Alarms Relay configuration will be deenergized when an alarm
and alert relay is present and will be energized when no alarm is present.
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
USER
Circuit Loading Sequence
0-3
0=Auto,
1=A Lead
2=B Lead,
3 =C Lead
0
lead_cir
Staged Loading Sequence
No/Yes
No
seq_typ
Ramp Loading Select
No/Yes
No
ramp_sel
Unit Off to On Delay
1-15
1
min
off_on_d
Condenser Pumps Sequence
0-4†
0
hpumpseq
Cooler Pumps Sequence
0-4
0=No Pump
1=One Pump Only
2=Two Pumps Auto
3=Pump#1 Manual
4=Pump#2 Manual
0
cpumpseq
Pump Auto Rotation Delay
24-3000
48
hours
pump_del
Pump Sticking Protection
No/Yes
No
pump_per
Stop Pump During Standby
No/Yes
No
pump_sby
Flow Checked if Pump Off
No/Yes
No
pump_loc
Auto Changeover Select*
No/Yes
No
auto_sel
Cooling Reset Select
0-4
0
cr_sel
Heating Reset Select*
0-4
1 =OAT*,
0=None
2=Delta T,
3=4-20mA Control
4=Space Temp
0
hr_sel
Demand Limit Type Select
0-2
0=None
1=Switch Control
2=4-20mA Control
0
lim_sel
mA For 100% Demand Limit
0-20
0
ma
lim_mx
mA For 0% Demand Limit
0-20
10
ma
lim_ze
Current Limit Select
No/Yes
No
curr_sel
Current Limit at 100%
0 to 2000
2000
amps
curr_ful
Heating OAT Threshold*
-4-32
5
°F
heat_th
Free Cooling Delta T Th*
14.4-27
18
°F
free_dt
Full Load Timeout
20-300
30
min
fc_tmout
HSM Both Command Select
No/Yes
No
both_sel
NIGHT CONTROL
Start Hour
00:00-24:00
00:00
nh_start
End Hour
00:00-24:00
00:00
nh_end
Capacity Limit
0-100
100
%
nh_limit
Ice Mode Enable
No/Yes
No
ice_cnfg
Reverse Alarms Relay
No/Yes
No
al_rever
Cooler pump off in heat
No/Yes
No
stopheat
Cond pump off in cool
No/Yes
No
stopcool