APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — SET POINTS
ITEM
EXPANSION
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
COOL
COOLING SETPOINTS
CSP.1
Cooling Setpoint 1
XXXX.X
(deg F/deg C)
–20-70 F
(–29-21 C),
Default = 44.0
forcible
SETPOINT
csp1
25, 41,
55
CSP.2
Cooing Setpoint 2
XXXX.X
(deg F/deg C)
–20-70 F
(–29-21 C),
Default = 44.0
forcible
SETPOINT
csp2
25, 41,
55
CSP.3
Ice Setpoint
XXXX.X
(deg F/deg C)
–20-70 F
(–29-21 C),
Default = 44.0
forcible
SETPOINT
ice_sp
25, 41,
55
CRV1
Current No Reset Val
XX.X (mA)
0-20,
Default = 0
forcible
SETPOINT
v_cr_no
36
CRV2
Current Full Reset Val
XX.X (mA)
0-20,
Default = 0
forcible
SETPOINT
v_cr_fu
36
CRT1
Delta T No Reset Temp
XXX.X (
F/
C)
0-125 F
(0-69.4 C),
Default = 0
forcible
SETPOINT
dt_cr_no
35, 36
CRT2
Delta T Full Reset Temp
XXX.X (
F/
C)
0-125 F
(0-69.4 C),
Default = 0
forcible
SETPOINT
dt_cr_fu
35, 36
CRO1
OAT No Reset Temp
XXX.X
(deg F/deg C)
0-125 F
(–18-52 C),
Default = 14.0
forcible
SETPOINT
oatcr_no
CRO2
OAT Full Reset Temp
XXX.X
(deg F/deg C)
0-25 F
(–18-52 C),
Default = 14.0
forcible
SETPOINT
oatcr_fu
CRS1
Space T No Reset Temp
XXX.X
(deg F/deg C)
0-125 F
(–18-52 C),
Default = 14.0
forcible
SETPOINT
spacr_no
36
CRS2
Space T Full Reset Temp
XXX.X
(deg F/deg C)
0-125 F
(–18-52 C),
Default = 14.0
forcible
SETPOINT
spacr_fu
36
DGRC
Degrees Cool Reset
XX.X (
F/
C)
–30-30 F
(–16.7-16.7 C),
Default = 0
forcible
SETPOINT
cr_deg
35, 36
CAUT
Cool Changeover Setpt
XX.X
(deg F/deg C)
Default = 75.0
Not supported.
forcible
SETPOINT
cauto_sp
CRMP
Cool Ramp Loading
X.X
0.2-2.0
F
(0.1-1.1
C),
Default = 1.0
forcible
SETPOINT
cramp_sp
35
HEAT
HEATING SETPOINTS
HSP.1
Heating Setpoint 1
XXX.X
(deg F/deg C)
Default = 100
Not supported.
forcible
SETPOINT
HSP.1
HSP.2
Heating Setpoint 2
XXX.X
(deg F/deg C)
Default = 100
Not supported.
forcible
SETPOINT
HSP.2
HRV1
Current to Reset Val
XX.X (mA)
Default = 0
Not supported.
forcible
SETPOINT
v_hr_no
HRV2
Current Full Reset Val
XX.X (mA)
Default = 0
Not supported.
forcible
SETPOINT
v_hr_fu
HRT1
Delta T No Reset Temp
XXX.X (
F/
C)
Default = 0
Not supported.
forcible
SETPOINT
dt_hr_no
HRT2
Delta T Full Reset Temp
XXX.X (
F/
C)
Default = 0
Not supported.
forcible
SETPOINT
dt_hr_fu
HRO1
OAT No Reset Temp
XXX.X
(deg F/deg C)
Default = 14.0
Not supported.
forcible
SETPOINT
oathr_no
HRO2
OAT Full Reset Temp
XXX.X
(deg F/deg C)
Default = 14.0
Not supported.
forcible
SETPOINT
oathr_fu
DGRH
Degrees Heat Reset
XX.X (
F/
C)
Default = 0
Not supported.
forcible
SETPOINT
DGRH
HAUT
Heat Changeover Setpt
XX.X
(deg F/deg C)
Default = 64
Not supported.
forcible
SETPOINT
hauto_sp
HRMP
Heat Ramp Loading
X.X
Default = 1.0
Not supported.
forcible
SETPOINT
hramp_sp
MISC
MISC SETPOINTS
DLS1
Switch Limit Setpoint 1
XXX (%)
0-100,
Default = 100
forcible
SETPOINT
lim_sp1
39, 40
DLS2
Switch Limit Setpoint 2
XXX (%)
0-100,
Default = 100
forcible
SETPOINT
lim_sp2
39, 40
DLS3
Switch Limit Setpoint 3
XXX (%)
0-100,
Default = 100
forcible
SETPOINT
lim_sp3
W.SCT
Water Val Cond Stp
XXX.X
(deg F/deg C)
80-140 F
(26.7-60 C)
Not supported.
SETPOINT
w_sct_sp
46