117
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — OPERATING MODE
*Up to six current operating modes will be displayed.
NOTE: See Operating Modes starting on page 54.
MODE — ALARMS
*Expanded display will be actual alarm description.
†History of up to five past alarms will be displayed.
**History of fifty past alarms will be displayed.
ITEM
EXPANSION*
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
SLCT
OPERATING CONTROL TYPE
OPER
Operating Control Type
Switch Ctrl
Time Sched
CCN Control
Default = Switch
Ctrl
forcible
N/A
N/A
24, 25
SP.SE
Setpoint Select
Setpoint Occ
Setpoint1
Setpoint2
4-20mA Setp
Dual Setp Sw
Default =
Setpoint Occ
forcible
N/A
N/A
25-27,
32
HC.SE
Heat Cool Select
Cooling
Heating
Auto Chgover
Heat Cool Sw
Default = Cooling
Not supported.
Not supported.
Not supported.
forcible
GENUNIT
HC_SEL
25
MODE*
OPERATING MODES
MD01
First Active Mode
0-32
MODES
MD02
Second Active Mode
0-32
MODES
MD03
Third Active Mode
0-32
MODES
MD04
Fourth Active Mode
0-32
MODES
MD05
Fifth Active Mode
0-32
MODES
MD06
Sixth Active Mode
0-32
MODES
ITEM
EXPANSION*
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
R.ALM
RESET ALL CURRENT ALARM
NO/YES
forcible
N/A
N/A
ALRM†
CURRENTLY ACTIVE ALARMS
Current Alarm 1
GENUNIT
alarm_1
Current Alarm 2
GENUNIT
alarm_2
Current Alarm 3
GENUNIT
alarm_3
Current Alarm 4
GENUNIT
alarm_4
Current Alarm 5
GENUNIT
alarm_5
H.ALM**
ALARM HISTORY
Alarm History #1
ALRMHIST
alm_history_01
Alarm History #2
ALRMHIST
alm_history_02
Alarm History #49
ALRMHIST
alm_history_49
Alarm History #50
ALRMHIST
alm_history_50