Criteria for Trip
— The criteria are tested whether the circuit is
ON or OFF. The alarm is generated if one of the following
criteria is met:
1. If the voltage as sensed by the MBB is 0 vdc, which
corresponds to the Navigator™ display of –7 psi
(–48.3 kPa).
2. The circuit is ON in cooling mode and the Saturated
Suction Temperature (
Saturated Suction Temp,
SST
)
for the circuit is greater than the Entering Water Tempera-
ture and EXV opening is less than 50% for more than
60 seconds.
Action to be Taken
— The circuit is shut down immediately, or
not allowed to start.
Reset Method
1. Automatic, once the transducer voltage is greater than
0 vdc, which corresponds to the Navigator display of a
value greater than –7 psi (–48.3 kPa).
2. Automatic once the circuit’s saturated suction tempera-
ture is lower than the Entering Water Temperature by 3° F
(1.6° C). If this criterion trips the alarm 3 times within a
24-hour period, the alarm changes to a manual reset.
Possible Causes
— If this condition is encountered, check the
following items:
• sensor wiring to Main Base Board
• board for a faulty channel
• faulty transducer
• faulty entering water temperature sensor
Reclaim Pumpdown Pressure Transducer
Alarm 32 — Circuit A (Pr.07)
Alarm 33 — Circuit B (Pr.08)
NOTE: Alarms 30 and 31 are not used or supported. If this
condition is encountered, confirm machine configuration.
Oil Pressure Transducer
Alarm 34 — Circuit A (Pr.10)
Alarm 35 — Circuit B (Pr.11)
Criteria for Trip
— The criteria are tested whether the circuit is
ON or OFF. The alarm is generated if one of the following cri-
teria is met:
1. If the voltage as sensed by the CPM board is 0 vdc,
which corresponds to the Navigator display of –7 psi
(–48.3 kPa).
2. The circuit is OFF and outside air temperature is below
35.6 F (2 C).
3. The circuit is OFF and the fluid type is brine.
Action to be Taken
— The circuit is shut down immediately, or
not allowed to start.
Reset Method
— Automatic, once the transducer voltage is
greater than 0 vdc.
Possible Causes
— If this condition is encountered, check the
following items:
• sensor wiring to CPM board
• board for a faulty channel
• faulty transducer
• plugged oil filter
• faulty oil solenoid valve coil
• stuck oil solenoid valve
• confirm unit configuration
Economizer Pressure Transducer Failure (sizes
175,200,350,400 only)
Alarm 37 — Circuit A (Pr. 13)
Alarm 38 — Circuit B (Pr. 14)
Criteria for Trip
— The criteria are tested whether the circuit is
ON or OFF. The alarm is generated if the voltage as sensed by
the MBB or Fan Board C is 0 vdc, which corresponds to the
Navigator display of –7 psi (–48.3 kPa).
Action to be Taken
— The circuit is shut down immediately, or
not allowed to start.
Reset Method
—
Automatic, once the transducer voltage is
greater than 0 vdc, which corresponds to the Navigator display
of a value greater than –7 psi (–48.3 kPa).
Possible Causes
— If this condition is encountered, check the
following items:
• sensor wiring to EXV Board
• EXV board for a faulty channel
• faulty transducer
• faulty economizer EXV or EXV wiring
• faulty economizer EXV channel on the board
• closed or partially closed suction service valve
• confirm unit configuration
Loss of Communication with Compressor Board
Alarm 53 — Compressor Board A (Co.A1)
Alarm 54 — Compressor Board B (Co.B1)
Criteria for Trip
— The alarm criterion is tested whether the
unit is ON or OFF. If communication with the Compressor
Protection Module Board (CPM) is lost for a period of 10 sec-
onds, the alarm will be generated.
Action to be Taken
— The affected compressor will be shut
down.
Reset Method
— Automatic, if communication is established.
If called for, the compressor will start normally.
Possible Causes
— If this condition is encountered, check the
following items:
• power supply to the affected CPM board
• address of the CPM
• local equipment network (LEN) wiring
• confirm unit configuration
Loss of Communication with EXV Board
Alarm 56 — Circuit A, EXV Board 1 (Co.E1)
Alarm 57 — Circuit B, EXV Board 2 (Co.E2)
Criteria for Trip
— The alarm criterion is tested whether the
unit is ON or OFF. If communication with EXV1 or 2 is lost
for a period of 10 seconds, the alarm will be triggered.
Action to be Taken
— If running, Circuit A or B will shut
down normally. If Circuit A or B is not operating, it will not be
allowed to start.
Reset Method
— Automatic, if communication is established,
the unit will start normally.
Possible Causes
— If this condition is encountered, check the
following items:
• power supply to EXV1 or 2
• address of the EXV board
• local equipment network (LEN) wiring
• confirm unit configuration