64
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Quick Test Menu
Navigation: MAIN MENU
QUICK TEST
Quick Test
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: QCK_TEST
PIC6 PATH: Main Menu
Quick Test
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Quick Test Enable
QCK_TEST
0 to 1
0
RW
2
Quick Test Oil/Ref Pump
Q_OILP
0 to 1
0
RW
3
Oil/Ref Pres Test Passed
OP_PASS
0 to 1
RO
4
Oil/Ref Pump Delta Press
OIL_PDQ
psi
RO
5
Quick Test Head Val Pos
Q_HDP
0 to 100
0
%
RW
6
Quick Test Chiller Stat
Q_CHST
4 to 20
4
mA
RW
7
Guide Vane 1 Tested Pos
Q_GV1POS
0 to 100
0
%
RW
8
Guide Vane 2 Tested Pos
Q_GV2POS
0 to 100
0
%
RW
9
Guide Vane 1 Actual Pos
Q_GV1ACT
%
RO
10
EC Valve Tested Pos
Q_HGBP_T
0 to 100
0
%
RW
11
Quick Test Alarm Output
Q_ALM
OFF/ON
OFF
RW
12
Quick Test Alert Output
Q_ALE
OFF/ON
OFF
RW
13
Quick Test Cond Pump
Q_CDWP
OFF/ON
OFF
RW
14
Condenser Water Flow
CDW_FLOW
YES/NO
RO
15
Quick Test Chilled Pump
Q_CHWP
OFF/ON
OFF
RW
16
Chilled Water Flow
CHW_FLOW
YES/NO
RO
17
Condenser Water Delta T
CDW_DT
–22.2 to 136.1
F
RO
18
Chilled Water Delta T
CHW_DT
–22.2 to 136.1
F
RO
19
Quick Test LLC EXV
Q_LLCEXV
0 to 100
0
%
RW
20
Quick Test VFD Cooling
Q_VFDCOL
OFF/ON
OFF
RW
21
Quick Test Free Cooling
Q_FCMODE
OFF/ON
OFF
RW
22
Quick Test Lo Tower Fan
Q_LOWFAN
OFF/ON
OFF
RW
23
Quick Test Hi Tower Fan
Q_HIFAN
OFF/ON
OFF
RW
RO —
Read Only
RW —
Read/Write