APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Surge Correction
LEGEND
*Default value is shown only if configurable in this table.
Protective Limit
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: CFGSURGE
PIC6 PATH: Main Menu
Configuration Menu
Surge Correction
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Surge Line Configuration
0=PR, 1=Delta T
sgl_cfg
0 to 1
0
RW
2
IGV1 Pos Configuration
0-Degree, 1=Percentage
gv1c_sel
0 to 1
0
RW
3
Surge Delta Tsmax
dts_max
0.0 to 150.0
70.0
°F
RW
4
Surge Delta Tsmin
dts_min
0.0 to 150.0
45.0
°F
RW
5
PR at Full Load Opening
pr_ful
1.0000 to 5.0000
3.0000
RW
6
PR at Min. Opening
pr_min
1.0000 to 5.0000
1.5000
RW
7
IGV1 Minimum Position
gv1_pmin
0 to 100
5
%
RW
8
IGV1 Full Load Position
gv1_pful
0 to 100
100
%
RW
9
Surge Line Offset
sgl_off
1.0 to 3.0
2.0
°F
RW
10
Surge Lower Deadband
sql_hoff
0.5 to 3.0
1.5
°F
RW
11
Surge Upper Deadband
sql_hoff
0.1 to 3.0
1.5
°F
RW
12
Surge Line Shape Factor
sgl_shfh
–1.000 to 0.000
–0.010
RW
13
Surge Line Speed Factor
sgl_spdf
0.00 to 3.00
2.00
RW
14
Surge Delay Time
surg_del
0 to 120
15
sec
RW
15
Surge Time Period
surge_t
7 to 10
8
min
RW
16
Surge Delta Amps
%
surge_a
5 to 40
20
%
RW
17
Rampdown Factor
rd_fact
0 to 1
0.1
RW
18
GV1 Close Step Surge
gvstp_sg
1.0 to 3.0
2.0
%
RW
19
VFD Speed Step Surge
vfdstpsg
1.0 to 5.0
1.5
%
RW
20
EC Valve Step Surge
hbpstsg
1.0 to 10.0
4.0
%
RW
21
Surge Profile Offset
sgl_pro
0.0 to 5.0
0.0
^F
RW
22
High Efficiency Mode
high_eff
DISABLE/ENABLE
DISABLE
RW
23
Surge Al Enable
sal_enb
DISABLE/ENABLE
DISABLE
RW
24
GV Jumpover Option
gv_skip
DISABLE/ENABLE
DISABLE
RW
RW —
Read/Write
CCN TABLE NAME: CFGLIMIT
PIC6 PATH: Main Menu
Configuration Menu
Protective Limit
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Evap Approach Alert
evap_al
0.5 to 15
5
°F
RW
2
Cond Approach Alert
cond_al
0.5 to 15
6
°F
RW
3
Evap Override Delta T
ert_ovdt
2 to 5
3
°F
RW
4
Evap Refrig Trippoint
ert_trip
0 to 40
33
°F
RW
5
Hi Evap Press Override DV
ep_ovdv
20 to 56
55
psi
RW
6
Hi Evap Press Cutout DV
ep_cut
59 to 60.3
59
psi
RW
7
Cond Pre Override DV 44
cpov_dl
18 to 57.3
27
psi
RW
8
Cond Pre Cutout DV 44
cpcut_dl
30 to 60.3
30
psi
RW
9
Cond Pre Override DV 72
cpov_dh
20.0 to 56.0
55.0
psi
RW
10
Cond Pre Cutout DV 72
cpcut_dh
59.0 to 60.3
59.0
psi
RW
11
Condenser Freeze Point
tb_trip2
210 to 220
220
°F
RW
12
Comp Discharge Alert
dgt_alrt
125 to 200
200
°F
RW
13
Comp Motor Temp Override
mt_over
150 to 200
200
°F
RW
14
Comp Bearing Alert DV
tb_alt3
90.0 to 120.0
104.0
°F
RW
15
Comp Bearing Trip DV
tb_trip3
121.0 to 150.0
122.0
°F
RW
16
Minimum Brine LWT
bri_min
10 to 34
34
°F
RW
17
Heating LWT Protect Set
lwtp_sp
41 to 50
42.8
°F
RW
18
Evap Flow Delta P Cutout
evap_cut
0.5 to 50
5
psig
RW
19
Cond Flow Delta P Cutout
cond_cut
0.5 to 50
5
psig
RW
20
Cond Hi Flow DP Limit
cond_val
0.5 to 50
50
psig
RW
21
Cond Hi Flow Alarm
cond_alm
DISABLE/ENABLE
DISABLE
RW
RW —
Read/Write