APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Modes
LEGEND
*Default value is shown only if configurable in this table.
Setpoint
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: MODES
PIC6 PATH: Main Menu
Modes
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Normal Shutdown
shut_nor
NO/YES
RO
2
Recycle Shutdown
shut_rcy
NO/YES
RO
3
Alarm Shutdown
shut_alm
NO/YES
RO
4
Recycle Startup
str_rcy
NO/YES
RO
5
Temperature Ramping
tmp_ramp
NO/YES
RO
6
Load Ramping
ld_ramp
NO/YES
RO
7
IGV1 Inhibiting
gv1_inh
NO/YES
RO
8
Ice Building
ice_act
NO/YES
RO
9
Ice Build Terminated
ice_term
NO/YES
RO
10
Ice Build Recy Startup
ice_rcy
NO/YES
RO
11
Ramp Loading
ramp_act
NO/YES
RO
12
Demand Limit
dem_act
NO/YES
RO
13
VFD Rampdown
vfdrpact
NO/YES
RO
14
Demand Limit Inhibit
dem_inh
NO/YES
RO
15
Evaporator Frozen
evapfrze
NO/YES
RO
16
Condenser Frozen
condfrze
NO/YES
RO
17
Recycle Shutdown Done
rcysh_cm
NO/YES
RO
18
NonRecycle Shutdown Done
nrysh_cm
NO/YES
RO
19
In Alarm
alm_act
NO/YES
RO
20
In Override
over_act
NO/YES
RO
21
Purge Active
pg_act
NO/YES
RO
22
Comp 1 Run State Val
cm_stat1
Integer
RO
RO —
Read Only
CCN TABLE NAME: SETPOINT
PIC6 PATH: Main Menu
Setpoint
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Cooling ECW Setpoint
ecw_sp
15.0 to 120.0
60.0
°F
RW
2
Cooling LCW Setpoint
lcw_sp
10.0 to 120.0
45.0
°F
RW
3
Heating ECDW Setpoint
ecdw_sp
63.0 to 150.0
104.0
°F
RW
4
Heating LCDW Setpoint
lcdw_sp
68.0 to 150.0
113.0
°F
RW
5
Ice Build Setpoint
ice_sp
15.0 to 60.0
40.0
°F
RW
6
Base Limit Demand
dem_base
10.0 to 100.0
100.0
%
RW
7
EWT Control Option
EWT_OPT
DISABLE/ENABLE
DISABLE
RW
RW —
Read/Write