APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Bearing Inlet Pressure
LEGEND
Bearing Outlet Pressure
LEGEND
Pump Outlet Pressure
LEGEND
Temp Sensor Calib
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: PRSCAL12
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Bearing Inlet Pressure
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Pump Input Press Cali
cal_en
DISABLE/ENABLE
DISABLE
RW
2
Calibration Completed
cal_st
NO/YES
NO
RO
3
Calibrated Slope
cal_s
RO
4
Calibrated Intercept
cal_i
RO
5
Current Pressure
cur_pres
psig
RO
6
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (10-30PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO
—
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL13
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Bearing Outlet Pressure
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Pump Input Press Cali
cal_en
DISABLE/ENABLE
DISABLE
RW
2
Calibration Completed
cal_st
NO/YES
NO
RO
3
Calibrated Slope
cal_s
RO
4
Calibrated Intercept
cal_i
RO
5
Current Pressure
cur_pres
psig
RO
6
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (10-30PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO
—
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL14
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Pump Outlet Pressure
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Pump Input Press Cali
cal_en
DISABLE/ENABLE
DISABLE
RW
2
Calibration Completed
cal_st
NO/YES
NO
RO
3
Calibrated Slope
cal_s
RO
4
Calibrated Intercept
cal_i
RO
5
Current Pressure
cur_pres
psig
RO
6
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (10-30PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO
—
Read Only
RW —
Read/Write
CCN TABLE NAME: TEMP_CAL
PIC6 PATH: Main Menu
Maintenance Menu
Temp Sensor Calib
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Entering Chilled Water
ECW
°F
RO
2
ECW Sensor Raw Temp
ECW_RAW
°F
RO
3
ECW Temperature Offset
ECW_OFF
–2.0 to 2.0
0
^F
RW
4
Leaving Chilled Water
LCW
°F
RO
5
LCW Sensor Raw Temp
LCW_RAW
°F
RO
6
LCW Temperature Offset
LCW_OFF
–2.0 to 2.0
0
^F
RW
7
Entering Condenser Water
ECDW
°F
RO
8
ECDW Sensor Raw Temp
ECDW_RAW
°F
RO
9
ECDW Temperature Offset
ECDW_OFF
–2.0 to 2.0
0
^F
RW
10
Leaving Condenser Water
LCDW
°F
RO
11
LCDW Sensor Raw Temp
LCDW_RAW
°F
RO
12
LCDW Temperature Offset
LCDW_OFF
–2.0 to 2.0
0
^F
RW
RO
—
Read Only
RW —
Read/Write