77
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Evap Pressure Sensor
LEGEND
Cond Pressure Sensor
LEGEND
Evap Entering Water P
LEGEND
CCN TABLE NAME: PRSCAL01
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Evap Pressure Sensor
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Evap Pressure Sensor
2
Calibration Enable
cal_en
DISABLE/ENABLE
DISABLE
RW
3
Calibration Completed
cal_st
NO/YES
NO
RO
4
Calibrated Slope
cal_s
RO
5
Calibrated Intercept
cal_i
RO
6
Current Pressure
cur_pres
psig
RO
7
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (10-30PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL02
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Cond Pressure Sensor
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Cond Pressure Sensor
2
Calibration Enable
cal_en
DISABLE/ENABLE
DISABLE
RW
3
Calibration Completed
cal_st
NO/YES
NO
RO
4
Calibrated Slope
cal_s
RO
5
Calibrated Intercept
cal_i
RO
6
Current Pressure
cur_pres
psig
RO
7
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (10-30PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL07
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Evap Entering Water P
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Evap Entering Water P
2
Calibration Enable
cal_en
DISABLE/ENABLE
DISABLE
RW
3
Calibration Completed
cal_st
NO/YES
NO
RO
4
Calibrated Slope
cal_s
RO
5
Calibrated Intercept
cal_i
RO
6
Current Pressure
cur_pres
psig
RO
7
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only