87
MODES_cm_stat1
0=OFF (STATSTOP is STOP, no alarm),
1=CTLTEST (Controls Test is active),
2=PUMPDOWN (Pump down in Controls
Test is active), 3=LOCKOUT (Lockout in
Controls Test is active), 4=RECYCLE
(Recycle shutdown completed on low
load in effect; non-fault condition),
5=TRIPOUT (Shutdown completed due to
alarm fault condition), 6=TIMEOUT (Start-
to-start or stop-to-start timer is actively
counting down; non-fault condition),
7=PRESTART (Prestart check is active),
8=STARTUP (Normal Startup in
progress), 9=AUTORST (Auto Rapid
Startup in progress), 10=RAMPING
(Ramp loading in progress),
11=RUNNING (Normal running mode, no
override and not in demand),
12=OVERRIDE (Running with Override
active), 13=DEMAND (Running with
Demand Limit Active), 14=SHUTDOWN
(Shutdown compressor in progress),
15=FREECOOL (Free cooling in
progress), 16=CONDFLSH (Condenser
Flush in progress)
MV
9
RO
Comp1 Run State Status
OUTPUTS_ALE
BV
25
RO
Alert Relay
OUTPUTS_ALM
BV
24
RO
Alarm Relay
OUTPUTS_CHST_OUT
AV
51
RO
Chiller Stat Output mA
OUTPUTS_COMP_PSV
BV
39
RO
Purge Comp Valve
OUTPUTS_COMP_SR
BV
26
RO
Compressor Start Relay
OUTPUTS_COND_CV
BV
34
RO
Condenser Control Valve
OUTPUTS_COND_DCV
BV
37
RO
Condenser Drain Valve
OUTPUTS_COND_FCV
BV
48
RO
Condenser Filling Valve
OUTPUTS_COND_PSV
BV
38
RO
Purge Cond Valve
OUTPUTS_DIFF_OUT
AV
49
RO
Diffuser Output mA
OUTPUTS_DIS_PSV
BV
42
RO
Purge Discharge Valve
OUTPUTS_DRASVON
BV
40
RO
Purge Drainage Valve
OUTPUTS_ECON_IV
BV
33
RO
Economizer Isolation VLV
OUTPUTS_EVAP_CV
BV
35
RO
Evaporator Control Valve
OUTPUTS_EVAP_DCV
BV
36
RO
Evaporator Drain Valve
OUTPUTS_EXV_OUT
AV
53
RO
Oil EXV Output mA
OUTPUTS_FC_VALVE
BV
47
RO
Free Cooling Valve
OUTPUTS_GV1_DEC
BV
27
RO
Guide Vane 1 Decrease
OUTPUTS_GV1_INC
BV
28
RO
Guide Vane 1 Increase
OUTPUTS_GV1_OUT
AV
56
RO
Guide Vane1 Output
OUTPUTS_GV2_OUT
AV
57
RO
Guide Vane2 Output
OUTPUTS_HDPV_OUT
AV
50
RO
Head Pres Output mA
OUTPUTS_llc_exvt
AV
54
RO
Liquid Level EXV Target
OUTPUTS_OIL_HEAT
BV
29
RO
Oil Heater Relay
OUTPUTS_OIL_PUMP
BV
30
RO
Oil Pump Relay
OUTPUTS_op_vfd_t
AV
55
RO
Oil Pump VFD Target
OUTPUTS_PG_COMP
BV
44
RO
Purge Compressor
OUTPUTS_PG_HEAT
BV
45
RO
Purge Heater
OUTPUTS_PGAPUMP
BV
43
RO
Purge Vacuum Pump
OUTPUTS_REG_PSV
BV
41
RO
Purge Regeneration Valve
OUTPUTS_TFR_HIGH
BV
31
RO
Tower Fan Relay High
OUTPUTS_TFR_LOW
BV
32
RO
Tower Fan Relay Low
OUTPUTS_VFD_OUT
AV
52
RO
VFD Speed Output mA
OUTPUTS_VS_SV
BV
46
RO
Vapor Source SV
POWER_I_AMPS_A_I
AV
66
RO
Actual Line Current
POWER_I_AMPS_P_I
AV
67
RO
Percent Line Current
POWER_I_KW
AV
70
RO
Motor Kilowatts
POWER_I_ln_imb_v
AV
72
RO
Line Voltage Imbalance%
POWER_I_POW_FACT
AV
71
RO
Motor Power Factor
POWER_I_VOLT_A
AV
68
RO
Actual Line Voltage
POWER_I_VOLT_P
AV
69
RO
Percent Line Voltage
POWER_O_alm_code
AV
84
RO
VFD Alarm Code
POWER_O_amps_p_o
AV
74
RO
Percent VFD Load Current
POWER_O_bus_volt
AV
76
RO
DC Bus Voltage
POWER_O_enc_temp
AV
81
RO
VFD Enclosure Temp
POWER_O_inv_temp
AV
82
RO
Inverter Temperature
POWER_O_lrtem_sw
BV
54
RO
LR Temp Switch
POWER_O_MOT_FREQ
AV
75
RO
Motor Actual Frequency
POWER_O_motor_kw
AV
79
RO
Motor Kilowatts
POWER_O_motor_pf
AV
78
RO
Motor Power Factor
APPENDIX D — NETWORK CONFIGURATION (CONT)
OBJECT NAME
OBJECT TYPE
INSTANCE
OPTION
PV ACCESS