65
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Quick Test Menu
Navigation: MAIN MENU
19DV QUICK TEST
19DV Quick Test
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: QCK_DV
PIC6 PATH: Main Menu
19DV Quick Test
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Quick Test Enable
QCK_TEST
0 to 1
0
RW
2
Quick Test Oil/Ref Pump
Q_OILP
0 to 1
0
RW
3
Oil/Ref Pres Test Passed
OP_PASS
0 to 1
RO
4
Oil/Ref Pump Delta Press
OIL_PDQ
psi
RO
5
Guide Vane 2 Tested Pos
Q_GV2POS
0 to 100
0
%
RW
6
Quick Test Condenser CV
Q_CONDSV
OFF/ON
OFF
RW
7
Quick Test Evaporator CV
Q_EVAPSV
OFF/ON
OFF
RW
8
QCK TST Evap Drain CV
Q_OPRLUB
OFF/ON
OFF
RW
9
QCK TST Cond Drain CV
Q_PRELUB
OFF/ON
OFF
RW
10
Quick Test Purge Comp SV
Q_CMPSV
OFF/ON
OFF
RW
11
Quick Test Pumpout SV
Q_POPSV
OFF/ON
OFF
RW
12
QCK TST Drainage SV
Q_DROPR
OFF/ON
OFF
RW
13
Quick Test Rege SV
Q_RGPSV
OFF/ON
OFF
RW
14
Quick Test Discharge SV
Q_DCPSV
OFF/ON
OFF
RW
15
Quick Test Vaccum Pump
Q_PVPSV
OFF/ON
OFF
RW
16
Quick Test Purge Comp
Q_PCPSV
OFF/ON
OFF
RW
17
Quick Test Purge Heater
Q_PHPSV
OFF/ON
OFF
RW
18
Quick Test Idle Drain SV
Q_IDLE
OFF/ON
OFF
RW
19
QCK TST Liq Bypass VLV
Q_ECBP
OFF/ON
OFF
RW
20
QCK TST Eco Isolation
Q_ECONIV
OFF/ON
ON
RW
21
QCK TST Cond Filling VLV
Q_CONDCV
OFF/ON
OFF
RW
22
Quick Test Free Cooling
Q_FCMODE
OFF/ON
OFF
RW
23
Motor Rotation Check
Q_MRC
DISABLE/ENABLE
DISABLE
RW
24
Check State
IDLE=0, PreLub=1, Rotat=2, PosLub=3, End=4
Q_MRC_ST
0 to 4
RO
RO —
Read Only
RW —
Read/Write