86
PERFORMANCE DATA —50HJQ (CONT)
COOLING CAPACITIES (CONT)
50HJQ007 (6 Tons)
Temp (F)
Indoor Entering Air — Cfm/BF
Temp (F)
Outdoor
1800/0.06
2100/0.066
2400/0.071
3000/0.088
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Ewb (F)
Entering Air
(Edb)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
TC
83.2 77.6 71.6 67.9 84.7 79.8 73.6 71.5 85.9 81.0 75.0 74.3 88.4 82.9 78.4 78.3
75
SHC
39.7 50.4 60.6 66.6 41.6 54.3 65.9 70.1 43.4 57.6 70.6 72.8 47.2 63.9 76.9 76.8
75
kW
4.90 4.78 4.69 4.63 4.94 4.84 4.71 4.69 4.97 4.86 4.74 4.73 5.04 4.91 4.81 4.81
TC
81.5 75.5 69.0 64.8 83.2 77.3 71.1 69.4 84.5 78.5 72.7 72.2 86.2 80.8 76.5 76.5
85
SHC
39.2 49.8 59.6 63.6 41.4 53.5 65.0 68.0 43.3 56.9 69.7 70.8 47.1 64.1 75.0 75.0
85
kW
5.45 5.34 5.23 5.16 5.49 5.36 5.27 5.23 5.52 5.38 5.29 5.27 5.57 5.45 5.36 5.36
TC
78.8 72.5 64.1 61.8 80.9 74.5 67.0 66.1 82.0 76.0 69.9 69.9 83.7 78.1 74.2 74.1
95
SHC
38.4 48.6 57.4 60.6 40.8 52.6 63.2 64.8 42.8 56.4 68.3 68.5 46.8 63.7 72.7 72.7
95
kW
6.03 5.91 5.79 5.73 6.09 5.96 5.84 5.82 6.11 6.00 5.89 5.89 6.16 6.05 5.96 5.96
TC
76.2 69.5 58.6 57.8 77.9 71.3 63.4 63.1 79.3 72.7 67.2 67.2 81.1 74.5 71.3 71.2
105
SHC
37.6 47.4 55.0 56.6 39.9 51.4 61.4 61.9 42.2 55.3 65.9 65.9 46.5 62.5 69.9 69.9
105
kW
6.69 6.56 6.40 6.38 6.73 6.61 6.45 6.44 6.77 6.64 6.51 6.51 6.82 6.67 6.57 6.57
TC
72.5 65.1 54.8 54.7 74.3 67.8 58.6 58.6 75.6 69.1 63.2 63.2 77.3 70.9 68.4 68.4
115
SHC
36.3 45.8 53.2 53.6 38.7 50.2 57.4 57.5 41.1 54.0 62.0 62.0 45.5 61.3 67.1 67.1
115
kW
7.37 7.24 7.08 7.07 7.43 7.30 7.16 7.16 7.48 7.34 7.21 7.21 7.52 7.38 7.32 7.32
50HJQ008 (7
1
/
2
Tons)
Temp (F)
Indoor Entering Air — Cfm/BF
Temp (F)
Outdoor
2250/0.12
3000/0.15
3750/0.18
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Ewb (F)
Entering Air
(Edb)
72
67
62
72
67
62
72
67
62
TC
97.6
92.5
84.3
100.8
95.6
89.9
101.6
97.8
91.7
75
SHC
47.7
61.0
72.7
51.5
67.3
83.8
55.0
74.4
89.7
75
kW
5.80
5.76
5.73
5.86
5.78
5.78
5.86
5.82
5.73
TC
97.2
89.9
79.8
100.0
94.1
86.7
102.4
96.0
89.9
85
SHC
48.1
60.2
70.5
51.7
68.1
82.4
55.8
74.1
89.3
85
kW
6.61
6.50
6.43
6.65
6.56
6.62
6.69
6.58
6.50
TC
94.4
86.9
75.0
98.2
91.3
81.8
99.6
93.7
87.3
95
SHC
47.3
59.2
68.1
51.7
67.5
79.8
55.0
74.8
87.3
95
kW
7.43
7.37
7.19
7.50
7.41
7.30
7.50
7.43
7.35
TC
91.7
82.2
70.7
94.8
87.3
76.6
97.0
90.1
83.4
105
SHC
46.3
57.4
65.9
50.9
66.3
76.4
54.8
74.1
83.4
105
kW
8.37
8.22
8.04
8.39
8.33
8.15
8.44
8.35
8.26
TC
87.7
77.4
66.9
91.7
81.6
72.5
93.9
85.3
78.8
115
SHC
44.9
55.4
64.0
50.3
64.2
72.5
55.0
72.5
78.6
115
kW
9.33
9.16
8.98
9.44
9.27
9.11
9.48
9.33
9.22
TC
83.6
73.3
66.7
87.1
76.0
69.1
89.5
79.0
74.4
125
SHC
43.6
53.9
63.8
48.7
62.0
69.1
53.7
70.1
74.4
125
kW
10.38
10.16
9.94
10.49
10.27
10.14
10.53
10.36
10.25
50HJQ009 (8
1
/
2
Tons)
Temp (F)
Indoor Entering Air — Cfm/BF
Temp (F)
Outdoor
2550/0.03
3400/0.04
4250/0.05
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Ewb (F)
Entering Air
(Edb)
72
67
62
72
67
62
72
67
62
TC
116.4
105.6
94.8
118.9
110.4
99.4
120.4
112.9
104.3
75
SHC
55.7
69.2
82.0
58.6
79.7
95.8
61.6
89.2
104.2
75
kW
6.01
5.89
5.8
6.04
5.97
5.87
6.07
6.01
5.93
TC
117.6
102.1
91.1
121.0
106.7
95.6
117.5
109.3
101.3
85
SHC
58.4
67.9
80.4
64.1
78.6
93.9
61.0
88.4
101.2
85
kW
6.47
6.72
6.61
6.52
6.80
6.69
6.91
6.85
6.77
TC
113.7
98.0
86.1
117.4
102.3
91.3
113.4
104.7
97.9
95
SHC
57.4
66.5
78.2
63.5
77.2
91.1
59.9
87.2
97.8
95
kW
7.34
7.63
7.49
7.40
7.72
7.60
7.82
7.77
7.69
TC
109.8
93.0
78.7
113.2
97.3
85.9
108.9
99.9
93.7
105
SHC
56.2
64.6
75.0
62.4
75.5
85.9
58.7
85.5
93.6
105
kW
8.28
8.59
8.42
8.36
8.71
8.57
8.81
8.74
8.68
TC
100.2
86.4
72.7
104.5
90.0
80.8
106.0
93.2
88.0
115
SHC
50.4
62.1
71.9
57.2
73.0
80.8
63.4
83.2
88.0
115
kW
9.79
9.60
9.40
9.91
9.71
9.59
9.95
9.79
9.71
TC
94.0
76.6
63.1
98.8
80.1
68.1
101.0
84.4
75.1
125
SHC
48.3
58.5
63.1
55.4
69.2
68.1
61.9
79.8
75.1
125
kW
10.91
10.65
10.45
11.03
10.78
10.61
11.1
10.86
10.73
LEGEND
BF
--- Bypass Factor
Edb
--- Entering Dry--- Bulb
Ewb
--- Entering Wet--- Bulb
kW
--- Compressor Motor Power Input
SHC
--- Sensible Heating Capacity (1000 Btuh) Gross
TC
--- Total Capacity (1000 Btuh) Gross
NOTES
:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
ldb = tedb –
1.10 x cfm
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (h
lwb
)
total capacity (Btuh)
h
lwb = hewb –
4.5x
cfm
Where:
h
ewb
= Enthalpy of air entering evaporator coil
3. The Shc is based on 80
_
F edb termperature of air entering evaporator coil.
Below 80
_
F edb, subtract (corr factor x cfm) from SHC.
Above 80
_
F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Shaded cells indicate Standard Ratings
50H
JQ
Summary of Contents for APOLLO CONTROL 50HJQ004-016
Page 5: ...5 50HEQ003 006 ...
Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...