56
INDOOR-FAN MOTOR PERFORMANCE — 50TFQ UNITS
UNIT
50TFQ
INDOOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY
(%)
208/230
2.8
Standard
460
0.34
440
1.3
Standard
575
0.34
440
1.3
208/230
4.9
004
Alternate
460
1.00
1000
2.1
75
004
Alternate
575
1.00
1000
2.1
75
208/230
6.0
High Static
460
2.40
2120
3.0
High Static
575
2.40
2120
3.0
208/230
3.5
Standard
460
0.75
850
1.8
Standard
575
0.75
850
1.8
208/230
4.9
005
Alternate
460
1.00
1000
2.1
75
005
Alternate
575
1.00
1000
2.1
75
208/230
6.0
High Static
460
2.40
2120
3.0
High Static
575
2.40
2120
3.0
208/230
5.9
Standard
460
1.20
1340
3.2
Standard
575
1.20
1340
3.2
208/230
7.6/6.0†
006
Alternate
460
1.30/2.40†
2120
3.0
74
006
Alternate
575
1.30/2.40†
2120
3.0
74
208/230
8.6
High Static
460
2.90
2562
3.9
High Static
575
2.90
2562
3.9
208/230
6.0
Standard
460
2.40
2120
3.0
007
Standard
575
2.40
2120
3.0
84
007
208/230
8.6
84
High Static
460
2.90
2562
3.9
High Static
575
2.90
2562
3.9
208/230
6.0
Standard,
Alternate
460
2.40
2120
3.0
008
Standard,
Alternate
575
2.40
2120
3.0
80
008
208/230
11.7
80
High Static
460
3.70
3313
5.5
High Static
575
3.70
3313
5.5
208/230
6.0
Standard
460
2.40
2120
3.0
Standard
575
2.40
2120
3.0
208/230
8.6
012
Alternate
460
2.90
2615
3.9
80
012
Alternate
575
2.90
2615
3.9
80
208/230
17.3
High Static
460
5.25
4400
8.5
High Static
575
5.25
4400
8.5
LEGEND
BHP —
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence. Using your fan
motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
†Single-phase/three-phase.
NOTES
:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2.
High-static motor not available on single-phase units.
50TFQ
Summary of Contents for APOLLO CONTROL 50HJQ004-016
Page 5: ...5 50HEQ003 006 ...
Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...