148
PERFORMANCE DATA----50HEQ (CONT)
50HEQ006 (5 Tons)
Return
Air
Cfm
(Standard
Temperature Air Entering Outdoor Coil (F db at 70% rh)
Air
(F db)
(Standard
Air)
–20
–10
0
10
17
30
40
47
50
60
1500
Cap.
15.6 14.3 20.5 18.8 25.6 21.8 35.4 32.3 35.4 32.3 43.6 38.2 50.7 50.7 56.2 56.2 63.3 63.3 63.0 63.0
1500
kW
3.16
3.26
3.36
3.54
3.54
3.72
3.88
4.01
4.20
4.18
1750
Cap.
16.0 14.7 20.9 19.2 26.0 22.1 35.8 32.7 35.8 32.7 44.6 39.1 51.3 51.3 56.4 56.4 62.9 62.9 63.0 63.0
55
1750
kW
3.19
3.28
3.36
3.52
3.52
3.67
3.80
3.90
4.04
4.04
55
2000
Cap.
16.9 15.6 21.9 20.2 27.0 23.0 36.9 33.7 36.9 33.7 45.6 40.1 52.3 52.3 56.7 56.7 62.8 62.8 62.6 62.6
2000
kW
3.41
3.49
3.56
3.69
3.69
3.83
3.93
4.01
4.12
4.11
2500
Cap.
18.9 17.6 23.9 22.1 29.1 25.0 38.9 35.7 38.9 35.7 47.8 42.1 53.5 53.5 56.9 56.9 62.2 62.2 62.5 62.5
2500
kW
3.92
3.99
4.04
4.15
4.15
4.25
4.32
4.37
4.45
4.45
1500
Cap.
12.5 11.5 17.9 16.5 23.4 19.9 33.2 30.2 33.2 30.2 41.7 36.5 48.8 48.8 54.2 54.2 62.7 62.7 62.7 62.7
1500
kW
3.46
3.63
3.78
4.01
4.01
4.23
4.44
4.60
4.86
4.85
1750
Cap.
13.0 11.9 18.4 16.9 23.9 20.3 33.8 30.8 33.8 30.8 42.3 37.1 49.5 49.5 55.0 55.0 62.1 62.1 63.1 63.1
70
1750
kW
3.5
3.65
3.78
3.98
3.98
4.17
4.34
4.48
4.66
4.68
70
2000
Cap.
13.9 12.9 19.4 17.9 24.9 21.3 34.9 31.8 34.9 31.8 43.5 38.2 50.6 50.6 56.2 56.2 63.0 63.0 63.2 63.2
2000
kW
3.73
3.87
3.98
4.15
4.15
4.32
4.47
4.58
4.73
4.73
2500
Cap.
16.0 14.9 21.5 19.9 27.0 23.3 37.1 34.0 37.1 34.0 45.8 40.4 52.9 52.9 57.7 57.7 63.3 63.3 63.1 63.1
2500
kW
4.24
4.37
4.46
4.60
4.60
4.74
4.85
4.92
5.03
5.01
1500
Cap.
9.93 9.14 15.7 14.5 21.5 18.2 31.6 28.8 31.6 28.8 39.9 35.0 46.9 46.9 52.8 52.8 61.9 61.9 62.1 62.1
1500
kW
3.65
3.87
4.06
4.36
4.36
4.59
4.82
5.02
5.35
5.35
1750
Cap.
10.3 9.51 16.2 14.9 22.0 18.7 32.2 29.4 32.2 29.4 40.7 35.7 47.7 47.7 53.6 53.6 62.1 62.1 62.5 62.5
80
1750
kW
3.70
3.90
4.07
4.33
4.33
4.53
4.73
4.89
5.14
5.14
80
2000
Cap.
11.3 10.5 17.2 15.9 23.1 19.7 33.3 30.4 33.3 30.4 42.1 37.0 49.0 49.0 54.9 54.9 63.0 63.0 62.7 62.7
2000
kW
3.92
4.11
4.27
4.50
4.50
4.67
4.85
4.99
5.19
5.18
2500
Cap.
13.4 12.5 19.4 18.0 25.3 21.8 35.6 32.6 35.6 32.6 44.4 39.2 51.7 51.7 57.0 57.0 63.8 63.8 63.8 63.8
2500
kW
4.45
4.62
4.75
4.94
4.94
5.09
5.23
5.32
5.46
5.45
LEGEND
Cap. ---
Heating Capacity (1000 Btuh) (includes indoor-fan motor heat
kW
--- Total Power Input (includes compressor motor power input,outdoor-fan motor input, and indoor-fan motor input)
rh ---
Relative Humidity
NOTES:
1. Shaded cells indicate integrated ratings.
2. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
50H
EQ
Summary of Contents for APOLLO CONTROL 50HJQ004-016
Page 5: ...5 50HEQ003 006 ...
Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...