147
50HEQ006 (5 Tons)
Temp (F)
Indoor Entering Air — Cfm/BF
Temp (F)
Outdoor
1500/0.17
1750/0.25
2000/0.31
2500/0.42
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Ewb (F)
Entering Air
(Edb)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
TC
70.2
65.3
59.9
56.6
71.7
66.8
61.9
59.7
72.8
67.8
63.4
62.4
74.1
69.9
65.8
65.8
75
SHC
31.6
40.6
49.2
54.1
33.3
43.5
53.8
57.0
34.8
46.0
57.8
59.6
37.5
51.8
62.9
62.9
75
kW
3.51
3.47
3.45
3.43
3.52
3.48
3.46
3.44
3.45
3.49
3.47
3.46
3.55
3.51
3.48
3.48
TC
68.7
63.3
57.4
54.2
70.3
65.1
59.3
57.8
71.8
66.3
60.9
60.5
73.2
68.5
64.5
64.4
85
SHC
31.3
40.0
48.3
51.8
33.1
43.2
52.8
55.2
34.9
46.2
56.8
57.7
38.0
52.5
61.6
61.5
85
kW
3.95
3.91
3.89
3.87
3.96
3.92
3.89
3.89
3.98
3.93
3.91
3.91
4.00
3.96
3.93
3.92
TC
66.7
60.6
52.0
50.1
68.4
62.4
55.5
54.7
69.1
63.8
58.2
58.2
71.2
65.6
62.2
62.2
95
SHC
30.7
39.1
46.2
47.8
32.7
42.5
51.3
52.3
34.2
45.8
55.5
55.5
38.0
51.6
59.4
59.4
95
kW
4.43
4.39
4.34
4.32
4.45
4.41
4.37
4.37
4.46
4.43
4.39
4.40
4.48
4.43
4.42
4.42
TC
63.7
55.4
45.8
45.8
65.6
58.6
50.2
50.1
66.9
60.5
53.3
53.6
68.2
62.4
59.5
59.5
105
SHC
29.8
37.4
43.5
43.7
31.9
41.3
47.9
47.9
33.9
44.8
50.9
51.2
37.3
51.1
56.8
56.8
105
kW
4.96
4.91
4.81
4.81
4.99
4.94
4.86
4.86
5.00
4.96
4.90
4.90
5.00
4.97
4.95
4.95
TC
60.2
47.9
41.2
41.2
62.0
50.9
45.2
45.2
63.3
52.8
48.2
48.2
65.1
56.2
54.2
54.1
115
SHC
28.8
34.8
39.3
39.3
30.9
38.8
43.1
43.2
32.9
42.4
46.1
46.0
36.8
49.2
51.8
51.7
115
kW
5.55
5.43
5.33
5.33
5.57
5.46
5.40
5.40
5.58
5.49
5.44
5.44
5.59
5.53
5.50
5.50
LEGEND
BF
--- Bypass Factor
Edb
--- Entering Dry--- Bulb
Ewb
--- Entering Wet--- Bulb
kW
--- Compressor Motor Power Input
SHC
--- Sensible Heating Capacity (1000 Btuh) Gross
TC
--- Total Capacity (1000 Btuh) Gross
NOTES
:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
ldb = tedb –
1.10 x cfm
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (h
lwb
)
total capacity (Btuh)
h
lwb = hewb –
4.5x
cfm
Where:
h
ewb
= Enthalpy of air entering evaporator coil
3. The Shc is based on 80
_
F edb termperature of air entering evaporator coil.
Below 80
_
F edb, subtract (corr factor x cfm) from SHC.
Above 80
_
F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Shaded cells indicate Standard Ratings
INSTANTANEOUS AND INTEGRATED HEATING RATINGS
50HEQ004 (3 Tons)
Return
Air
Cfm
(Standard
Temperature Air Entering Outdoor Coil (F db at 70% rh)
Air
(F db)
(Standard
Air)
–20
–10
0
10
17
30
40
47
50
60
900
Cap.
10.3 9.47 13.7 12.6 16.8 15.4 20.1 18.5 23.5 21.3 27.6 24.2 31.9 31.9 35.1 35.1 36.3 36.3 40.3 40.3
900
kW
1.48
1.58
1.66
1.75
1.85
1.97
2.11
2.22
2.27
2.41
55
1200
Cap.
10.8 9.92 14.2 13.0 17.3 15.9 20.7 19.0 24.0 21.7 28.3 24.8 32.8 32.8 36.2 36.2 37.4 37.4 41.5 41.5
55
1200
kW
1.45
1.52
1.59
1.66
1.73
1.82
1.94
2.03
2.06
2.18
1500
Cap.
11.1 10.2 14.6 13.4 17.6 16.2 21.2 19.4 24.4 22.1 28.9 25.3 33.5 33.5 36.5 36.5 37.7 37.7 41.2 41.2
1500
kW
1.43
1.49
1.54
1.60
1.66
1.74
1.83
1.90
1.92
2.00
900
Cap.
8.67 7.97 11.9 10.9 15.1 13.9 18.6 17.1 22.2 20.2 26.4 23.1 30.5 30.5 33.6 33.6 34.7 34.7 39.0 39.0
900
kW
1.69
1.83
1.95
2.08
2.21
2.38
2.54
2.67
2.72
2.92
70
1200
Cap.
9.15 8.42 12.4 11.4 15.7 14.5 19.3 17.7 22.9 20.7 27.1 23.8 31.4 31.4 34.6 34.6 35.8 35.8 40.0 40.0
70
1200
kW
1.67
1.78
1.88
1.99
2.09
2.22
2.35
2.45
2.49
2.64
1500
Cap.
9.55 8.78 12.8 11.8 16.2 14.9 19.8 18.2 23.3 21.1 27.7 24.3 32.0 32.0 35.2 35.2 36.4 36.4 40.2 40.2
1500
kW
1.65
1.75
1.84
1.93
2.02
2.12
2.23
2.32
2.35
2.46
900
Cap.
7.32 6.73 10.6 9.79 14.1 12.9 17.7 16.2 21.4 19.4 25.6 22.4 29.5 29.5 32.5 32.5 33.7 33.7 38.1 38.1
900
kW
1.83
1.99
2.14
2.30
2.45
2.64
2.82
2.97
3.02
3.25
80
1200
Cap.
7.80 7.17 11.2 10.3 14.7 13.5 18.4 16.8 22.1 20.1 26.3 23.1 30.4 30.4 33.6 33.6 34.7 34.7 39.0 39.0
80
1200
kW
1.81
1.95
2.08
2.20
2.33
2.48
2.62
2.73
2.78
2.94
1500
Cap.
8.22 7.56 11.7 10.7 15.2 14.0 18.8 17.3 22.6 20.5 26.9 23.5 31.1 31.1 34.3 34.3 35.5 35.5 39.6 39.6
1500
kW
1.79
1.92
2.04
2.15
2.25
2.38
2.50
2.60
2.63
2.76
See Legend and Notes on page 97.
INSTANTANEOUS AND INTEGRATED HEATING RATINGS (CONT)
50HEQ005 (4 Tons)
Return
Air
Cfm
(Standard
Temperature Air Entering Outdoor Coil (F db at 70% rh)
Air
(F db)
(Standard
Air)
–20
–10
0
10
20
30
40
47
50
60
1200
Cap.
14.0 12.9 17.7 17.7 21.7 21.7 26.0 26.0 30.4 30.4 35.9 31.5 41.4 41.4 45.4 45.4 46.9 46.9 52.3 52.3
1200
kW
1.83
1.96
2.08
2.20
2.32
2.48
2.65
2.78
2.83
3.02
55
1600
Cap.
1.46 13.4 18.3 18.3 22.4 22.4 26.6 26.6 31.0 31.0 36.7 32.1 42.3 42.3 46.5 46.5 48.0 48.0 53.4 53.4
55
1600
kW
1.79
1.90
1.99
2.09
2.18
2.31
2.44
2.55
2.59
2.74
2000
Cap.
15.1 13.9 18.8 18.8 22.9 22.9 27.0 27.0 31.5 31.5 37.2 32.6 43.0 43.0 47.2 47.2 48.8 48.8 54.2 54.2
2000
kW
1.77
1.86
1.94
2.02
2.10
2.21
2.32
2.42
2.45
2.59
1200
Cap.
11.9 11.0 17.7 17.7 21.7 21.7 26.0 26.0 30.4 30.4 35.9 31.5 41.4 41.4 45.4 45.4 46.9 46.9 52.3 52.3
1200
kW
2.08
1.96
2.08
2.20
2.32
2.48
2.65
2.78
2.83
3.02
70
1600
Cap.
12.6 11.6 18.3 18.3 22.4 22.4 26.6 26.6 31.0 31.0 36.7 32.1 42.3 42.3 46.5 46.5 48.0 48.0 53.4 53.4
70
1600
kW
2.05
1.90
1.99
2.09
2.18
2.31
2.44
2.55
2.59
2.74
2000
Cap.
13.1 12.0 18.8 18.8 22.9 22.9 27.0 27.0 31.5 31.5 37.2 32.6 43.0 43.0 47.2 47.2 48.8 48.8 54.2 54.2
2000
kW
2.02
1.86
1.94
2.02
2.10
2.21
2.32
2.42
2.45
2.59
1200
Cap.
10.1
9.3
17.7 17.7 21.7 21.7 26.0 26.0 30.4 30.4 35.9 31.5 41.4 41.4 45.4 45.4 46.9 46.9 52.3 52.3
1200
kW
2.22
1.96
2.08
2.20
2.32
2.48
2.65
2.78
2.83
3.02
80
1600
Cap.
10.7
9.9
18.3 18.3 22.4 22.4 26.6 26.6 31.0 31.0 36.7 32.1 42.3 42.3 46.5 46.5 48.0 48.0 53.4 53.4
80
1600
kW
2.20
1.90
1.99
2.09
2.18
2.31
2.44
2.55
2.59
2.74
2000
Cap.
11.3 10.4 18.8 18.8 22.9 22.9 27.0 27.0 31.5 31.5 37.2 32.6 43.0 43.0 47.2 47.2 48.8 48.8 54.2 54.2
2000
kW
2.18
1.86
1.94
2.02
2.10
2.21
2.32
2.42
2.45
2.59
50H
EQ
50H
EQ
Summary of Contents for APOLLO CONTROL 50HJQ004-016
Page 5: ...5 50HEQ003 006 ...
Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...