PERFORMANCE DATA—50TFQ (CONT)
ELECTRIC HEATING CAPACITIES — 50TFQ008-012
UNIT
50TFQ
UNIT VOLTAGE
(60 Hz)
ACCESSORY
kW
ELECTRIC HEATER
PART NUMBER
CRHEATER---A00
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE---A00
208/230/240
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
017
010
011
012
012 and 017
007
007
009
009
013
008, 009
460/480
(3 phase)
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
016
013
014
015
014 and 016
006
006
008
008
010
575
(3 phase)
17.0
34.0
018
019
006
006†
208/230/240
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
017
010
012
012 and 017
010 and 012
012
012
015
017
017
012
460/480
(3 phase)
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
45.9/50.0*
013
014
015
014 and 016
013 and 015
011
014
014
016
016
575
(3 phase)
17.0
34.0
51.0*
018
019
018 and 019
011
014
016
*Two heater packages required to provide kW indicated.
†Use CRSINGLE004A00 for units with convenience outlet.
NOTES
:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW new = 16 kW (215/240)
2
kW new = 12.8 kW (rating at 215 v)
50TFQ
Summary of Contents for APOLLO CONTROL 50HJQ004-016
Page 5: ...5 50HEQ003 006 ...
Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...