155
FAN PERFORMANCE 50HEQ003 — HORIZONTAL DISCHARGE UNITS; STANDARD MOTOR (BELT DRIVE)**
AIRFLOW
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.1
0.2
0.4
0.6
0.8
1.0
(Cfm)
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
600
490
0.08
521
0.08
597
0.14
703
0.21
788
0.29
868
0.37
700
519
0.09
557
0.09
623
0.16
729
0.24
816
0.32
892
0.41
800
537
0.1
582
0.12
650
0.19
751
0.27
845
0.37
927
0.47
900
560
0.13
610
0.14
681
0.22
783
0.32
870
0.42
947
0.53
1000
589
0.15
640
0.16
707
0.26
808
0.36
894
0.47
971
0.58
FAN PERFORMANCE 50HEQ004 — HORIZONTAL DISCHARGE UNITS; STANDARD MOTOR (BELT DRIVE)*
AIRFLOW
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
(Cfm)
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
554
0.14
134
681
0.22
222
783
0.32
316
870
0.42
416
947
0.53
523
1000
583
0.16
163
707
0.26
257
808
0.36
358
894
0.47
465
971
0.58
578
1100
612
0.20
195
735
0.30
298
834
0.41
406
919
0.52
519
995
0.64
638
1200
643
0.23
233
762
0.35
344
860
0.46
459
944
0.58
579
1020
0.71
705
1300
674
0.28
276
791
0.40
395
887
0.52
517
970
0.65
645
1045
0.78
777
1400
706
0.33
324
820
0.45
451
914
0.59
582
997
0.72
717
1071
0.86
857
1500
738
0.38
379
849
0.52
515
942
0.66
653
1024
0.80
796
1097
0.95
942
AIRFLOW
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
1.2
1.4
1.6
1.8
2.0
(Cfm)
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1017
0.64
635
1082
0.76
753
1143
0.88
876
1200
1.01
1004
1254
1.14
1136
1000
1041
0.70
696
1105
0.82
820
1166
0.95
948
1223
1.09
1081
—
—
—
1100
1065
0.77
763
1129
0.90
892
1189
1.03
1026
1245
1.17
1165
—
—
—
1200
1089
0.84
835
1153
0.98
971
1212
1.12
1111
—
—
—
—
—
—
1300
1114
0.92
915
1177
1.06
1056
—
—
—
—
—
—
—
—
—
1400
1139
1.01
1000
1202
1.15
1149
—
—
—
—
—
—
—
—
—
1500
1164
1.10
1093
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp --- Brake Horsepower Input to Fan
Watts --- Input Watts to Motor
NOTES:
Grey box
indicates field-supplied drive is required.
See General Fan Performance Notes.
* Factory provided drive range 680 to 1044 rpm. All other rpms require field-supplied drive. Max continuous bhp is 1.20.
**Factory provided drive range 639 to 936 rpm. All other rpms require field-supplied drive. Max continuous bhp is 0.58.
50H
EQ
Summary of Contents for APOLLO CONTROL 50HJQ004-016
Page 5: ...5 50HEQ003 006 ...
Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...