Packaged rooftop units

14

In this case, it´s posible to install the TCO terminal on the electric panel.

It’s necessary that the terminal uses the same power supply that the control 

board.

  Up to four RS485 ambient probes can be connected in series on the 

fi

 eld-bus 

of the control board.

1

2

3

4
5
6

8

9

7

TCO user terminal  (optional):

This terminal can be installed on the electric 
panel, instead of pGD1 terminal. In this 
case, the remote connection of the pGD1 
terminal is posible.

9. C

HECKING BEFORE COMMISSIONING

Electrical connections

Note: Under no circumstance should the unit be started without having read the brochure completely.

Installation norms

To perform the electric installation of the unit (cable glands , conductor 
section and their calculations, protections, etc.), refer to the information 
provided in this document (see the technical characteristic table), the 
electrical scheme included with the unit and norms in effect that regulate 
the installation of air conditioning units and electrical receivers.
The electric power supply of the unit must be sized in accordance with 
the maximum power input by the unit taking into account all the options 
it features (if necessary, refer to the technical brochure).
Verify that electrical power corresponds to the one on the data plate 
and that the voltage remains constant.

Check that the electrical connections are correct and tight 
(an electrical diagram is included with each unit, along with 
its legend).

Note:

 All connections in the site are the responsibility of 

the installer. These connections are always made as per 
the current regulation.

To prevent electrical shocks, make all electrical connections 
before energizing the unit. Check that the automatic switch is 
closed. Omitting this can cause personal damage. Make the 
ground connection before any other electrical connection.

V-220004

V-220005

The installer must 

fi

 x line protection elements according to 

the effective legislation.

CARRIERrtc electronic control

The 

CARRIERrtc

 control is basically composed of a 

μ

PC MEDIUM 

control plate, a pGD1 graphical terminal, a TCO user terminal (optional), 
and sensors. 
Please refer to this control brochure to obtain more detailed information 
about its operation. 

pGD1 terminal:

This terminal, installed in the 
electric panel of the machine, 
allows for:
-  The initial programming of the 

unit.

-   The modi

fi

 cation of the operating parameters.

-  Stopping/starting the unit.
-  The selection of the operating mode.
-  Setting the setpoints.
-  The on-screen view of the controlled variables and the values 

measured by the sensors.

-  The on-screen view of the description of the active alarms and the 

alarms log.

Optionally, these units can change the electronic control to 

CARRIERrtc 

basic

 (models 90 to 180) or 

CARRIERrtc medium 

(all models). This 

control is 

fi

 tted with the TCO terminal as standard, and the pGD1 terminal 

as an option. Consult the technical brochure.

Note:

 for more detailed information on these controls, please refer to 

their brochures.

CARRIERrtc connection chart

Nb.

50EN/EH

90 to 360

1 Main power supply 400 III (±10%)

3 wires + ground

2

Remote connection of pGD1  

terminal (by default it’s installed 

on the electric panel) 

telephone cable 6 wires 

standard (RJ12 connector) 

3 Connection of TCO user terminal 

on the electric panel (optional) 

2 wires for power supply 230V + 1 

shielded cable for communication 

type AGW20 / 22 (1 braided pair + 

dra shielding)

4 Remote off/on (optional)

2 wires

5 Main failure signal (optional)

2 wires

6 Circulation pump signal for HWC 

(antifreeze sec.) (opt.)

1 wire 

7 NTC ambient probe (std)

2 wires

8 RS485 ambient probe (opt.)

5 wires 

9 Air quality probe (opt.)

3 wires

Summary of Contents for 50EH

Page 1: ...NANCE INSTRUCTIONS 50EN EH Nominal cooling capacity 21 2 85 2 kW Nominal heating capacity 21 7 88 7 kW 50 Hz Translation of the original document 80046 10 2016 Packaged rooftop cooling only heat pumps...

Page 2: ...Sound Level 13 9 Checking before commissioning 14 Electrical connections 14 Connection of probes by the client 15 Checks in the axial fans 17 Checks in the EC plug fans 18 Checks in the centrifugal f...

Page 3: ...onditioning of medium and large surface areas used for business or industry A vast number of options provide a solution to many operating requirements such a Free cooling Air renewal Air quality contr...

Page 4: ...Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL Artic 22CC Volume of oil l 3 1 3 1 3 1 3 1 3 1 3 1 3 1 5 3 Electrical characteristics Mains voltage 400 V III ph 50 Hz 10 Power sup...

Page 5: ...4 Type Electronic axial fan Number Diameter mm 2 800 Motor output kW 2 x 2 2 Power input in COOLING kW 2 2 2 2 2 2 2 5 2 5 2 5 2 5 Power input in HEATING kW 3 1 3 1 3 1 3 2 3 2 3 2 3 2 Speed r p m 2...

Page 6: ...highly toxic and corrosive To detect leaks an electronic leak detector an ultraviolet lamp or soapy water must be used Flame detectors do not help Important Immediately repair any refrigerant leak usi...

Page 7: ...on mixing box of 3 dampers R N E MA00 I MA01 R I N E MA02 R N E I R N E MC00 I MC02 R N E I MC01 R I N E N E MC10 R I MC11 N E R I MS assemblies Fresh air intake with damper interlocked with return da...

Page 8: ...ere may be dangerous for both the unit and the personnel who are carrying out the discharging or transport work Always check the weight of the set and verify that the discharging method used is approv...

Page 9: ...360T 1301 1034 771 1317 986 750 1297 1145 775 1314 1085 836 Electrical heaters 12 kW 18 kW 27 kW 36 kW 45 kW Weight of module kg 11 15 19 24 29 Centrifugal fans 0 75 kW 1 1 kW 1 5 kW 2 2 kW 3 kW 4 kW...

Page 10: ...way to place the unit in the ultimate location always in observation of the handling standards that have been described below is a proposed assembly sequence that may facilitate the operation keeping...

Page 11: ...172 116 273 188 122 277 179 122 276 178 141 309 191 150 318 200 141 309 191 150 318 200 360HEE 360T 115 282 184 131 298 200 137 301 190 138 302 191 163 342 205 171 351 214 163 342 205 171 351 214 50E...

Page 12: ...ed rooftop units 12 1 5m 1 5m Minimum free space for commissioning and maintenance operations 50EN EH 90HEE 90T 120HEE 120T 160HEE 160T 180HEE and 180T 50EN EH 200HEE 240HEE 240T 320HEE 320T 360HEE an...

Page 13: ...ard unit Unit with return plug fan in top box MC1 optional Unit with return plug fan in top box and MRC1 cooling recovery circuit optional Note The sound pressure level depends on the installation con...

Page 14: ...atic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V 220004 V 220005 The installer must fix line protection elements accord...

Page 15: ...J3 with 2 x 1 5 mm2 section cable within a maximum distance of 30 metres RS485 connector J10 withAWG20 section cable single braided pair preferably shielded with drain wire Power supply 24 Vac 2 wires...

Page 16: ...ng the IAQ Recommended cable section 1 5 mm2 Factory settings 6 5 4 0 10 V 3 2 1 0 Off DIP Switches left position right position 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 IAQ 40 45 50 55 60 65 70 75 80 IAQ IAQ CO...

Page 17: ...he outlet probe B3 and the mixing probe B4 can be replaced by RS485 enthalpic probes for calculation of the cooling and heating capacities optional The outdoor humidity probe optional necessary for th...

Page 18: ...d consumptions The coupling of characteristic curves of the fan and the room is very important so that the flows and pressures provided to the duct network are as required The variable speed plug fans...

Page 19: ...nt drain junction gas threaded Cooling recovery circuit 3 4 M in bronze Gas burner consult in the specific instruction brochure of burners supplied with the burner The air supply and return ducts must...

Page 20: ...int in the electronic control For those units with centrifugal supply fans optional a differential pressostat can be incorporated in order to measure the variation in air flow This pressostat allows t...

Page 21: ...outdoor temperature if the outdoor temperature drops below 4 C the control activates the pump and the 3 way valve opens to maintain in the water coil a water outlet temperature of 10 C in ON operatin...

Page 22: ...of long unit stops and forcibly if they happen in the winter season the coil must be emptied To prevent the water from freezing with this option the unit always has an anti freezing thermostat Add gly...

Page 23: ...inked inside the unit To that extent drills have been made in the unit to which the supports must be screwed Supports attached to the unit Access panel Step 3 Take the hoses with the electric power su...

Page 24: ...eties in the burner The burner module includes a name plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary in...

Page 25: ...The stop drop can be installed in the indoor air coil and at the fresh air intake Indoor air coil recommended in cases where a high moisture content in the air is foreseen or when the air flow is hig...

Page 26: ...anomaly When commissioning the compressors check the subcooling and overheating and thus verify if the refrigerant load is appropriate to the operating conditions If the refrigerant load is lower tha...

Page 27: ...lation In general a corrosion control must be performed on the metallic parts of the unit frame bodywork exchangers electric panel etc Check that the insulation foam is not unstuck or torn All the ele...

Page 28: ...grease Cleaning the accumulated dust on the coil can be performed with a vacuum cleaner perpendicular to the fins or with a low pressure water cleaner Grease can be removed with water with degreaser...

Page 29: ...ated in the characteristics table in chapter 4 Check the oil level and aspect In case of a colour change check the oil quality using a contamination test In the case of the presence of acid water or m...

Page 30: ...he lower rail when sliding Tab for displacement of gravimetric lters of the upper rail Air lters Clean regularly Depending on the installation conditions the filter aspect must be examined to define t...

Page 31: ...to place the frames back on First the frames from the upper rail will be placed on Then the two rail attachment screws will be placed on and finally the frames of the lower rail will be placed on Filt...

Page 32: ...d tilting the rail slightly Attachment screw Tabs in displacement Filters G or G F the frames with each type of filters gravimetrics and opacimetric if the unit has includes the latter are assembled o...

Page 33: ...nt are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electronic c...

Page 34: ...Packaged rooftop units 34 Notes...

Page 35: ......

Page 36: ...Order No 10046 10 2016 Supersedes order No 03 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: