3. T
ECHNICAL CHARACTERISTICS
(EN-14511-2013)
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 27ºC, 19ºC WB and 35ºC outdoor temperature.
Heating capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature.
Total power input by compressors and motorised fans under nominal conditions, calculated in accordance with the EN-14511-2013 standard.
Climatic warming potential of a kilogram of
fl
uorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
50EN/EH
200HEE
240HEE
240T
320HEE
320T
360HEE
360T
Cooling
capacities
Cooling capacity
(kW)
52,7
58,5
61,3
71,3
74,6
79,9
85,2
Power input
(kW)
17,5
19,4
21,8
23,7
26,5
26,5
30,3
EER performance
3,01
3,01
2,81
3,01
2,81
3,01
2,81
Heating
capacities
Heating capacity
(kW)
55,6
62,5
66,1
74,4
78,7
86,0
88,7
Power input
(kW)
16,3
18,3
20,6
21,8
24,5
25,2
27,6
COP performance
3,41
3,41
3,21
3,41
3,21
3,41
3,21
Outdoor
circuit
fan
Nominal air fl ow (m
3
/h)
30000
Available static pressure (mm.w.c)
4
Type
Electronic axial fan
Number / Diameter (mm)
2 / 800
Motor output (kW)
2 x 2,2
Power input in COOLING (kW)
2,2
2,2
2,2
2,5
2,5
2,5
2,5
Power input in HEATING (kW)
3,1
3,1
3,1
3,2
3,2
3,2
3,2
Speed (r.p.m.)
2 / 980
Indoor
circuit
supply
fan
Nominal air fl ow (m
3
/h)
10000
12000
14300
15900
Available static pressure (mm.w.c)
20
20
20
20
25
25
25
Type
Electronic plug-fan
Number / Diameter (mm)
2 / 500
Motor output (kW)
2 x 2,68
Power input (kW)
1,7
2,2
2,2
3,0
3,3
3,7
3,7
Speed (r.p.m.)
2 / 1700
Compressor
Type
Scroll
Number of compressors
4
Number of stages
4
Number of circuits
2
Oil type
Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate RL 32CF, Mobil EAL Artic 22CC
Volume of oil (l)
6,3
6,3
6,3
6,3
6,3
6,3
8,5
Electrical
characteristics
Mains voltage
400 V / III ph / 50 Hz (±10%)
Power supply
3 wires + ground
Maximum
absorbed
current
Compressors (A)
36,1
41,6
48,3
55,0
59,2
63,4
62,3
Outdoor fans (A)
6,8
6,8
6,8
6,8
6,8
6,8
6,8
Indoor fans (A)
8,4
8,4
8,4
8,4
8,4
8,4
8,4
Control (A)
1,8
1,8
1,8
1,8
1,8
1,8
1,8
Total (A)
53,1
58,6
65,3
72,0
76,2
80,4
79,3
Refrigerant
Type
R-410A
Global warming potential (GWP)
2.088
Charge (kg)
11,5
11,5
11,5
15,0
15,0
17,0
17,0
Environment impact (tCO2eq)
24,0
24,0
24,0
31,3
31,3
35,5
35,5
Dimensions
Length (mm)
2750
2750
Width (mm)
2115
2115
Height (mm)
1705
2005
Weight
(kg)
1071
1071
1071
1104
1104
1210
1210
Condensate outlet Ø
1 1/4” adaptor