Carrier 50EH Installation, Operation And Maintenance Instructions Download Page 22

Packaged rooftop units

22

11. O

PCIONAL EQUIPMENT

Hot water coil

-  Hot water coil with a three-way valve managed by the electronic 

control of the unit. The water coil could be activated in the following 
cases:

•  As a support in HEATING mode, as the 

fi

 rst stage or subsequently 

with the input of all the available compressors. 

•  As  support  in  HEATING  mode  in  accordance  with  the  outlet 

temperature.  

•  During the defrosting operation if selected as support.
•  With  the  unit  running  or  shut  down  if  an  anti-freeze  alarm  is 

triggered.

•  With the unit stopped when the outdoor temperature drops below 

4ºC. In this case the circulation pump of the water circuit will be 
connected. 

•  As support in COOLING mode in accordance with the return and 

the oultlet temperatures.

The pump of the water circuit has to be activated whenever the 3-way 
valve is switched on. It is the installer’s responsibility to connect 
the pump to the electronic control, except with the factory-installed 
GREAT COLD option. Consult the electrical scheme supplied with 
the unit.

- Coil 

fi

 lling:

•  The coil 

fi

 lling must be made with the bleeder valve open until 

water runs through it, which is when it is time to close it.

•  Cut off the water supply and let the bubbles generated go up to 

the highest coil point, which is the same as the bleeder valve, and 
eliminate by opening the purger.

•  Pour more water into the circuit and repeat the previous steps.
•  Activate  the  water  pump  (to  be  foreseen  by  the  installer)  and 

repeat the previous steps until no air noises are heard in the piping, 
which is when the 

fi

 lling of the installation will have been 

fi

 nished 

successfully.

-  In case of long unit stops, and forcibly if they happen in the winter 

season, the coil must be emptied. 

-  To prevent the water from freezing, with this option the unit always 

has an anti-freezing thermostat. Add glycol to the water if necessary. 
With the GREAT COLD option, it is necessary to consult for glycol 
percentages higher than 20%. 

-  The direction of the water 

fl

 ow must be correct and so the following 

indications must be observed:

HOT WATER COIL

BATTERIE D’APPOINT

BATERÍA DE APOYO

HOT WATER COIL

BATTERIE D’APPOINT

BATERÍA DE APOYO

A

B

C

2

1

LEGEND

1

Water outlet 

2

Water inlet 

50EN/EH

A

(mm)

B

(mm)

C

(mm)

Ø hydraulic 

connections: I/O

90HEE / 90T / 120HEE / 120T

203

190

177

1 1/4”

160HEE / 160T / 180HEE / 180T

203

190

177

1 1/2”

200HEE / 240HEE / 240T / 

320HEE / 320T / 360HEE / 360T

295

250

177

2”

Note:

 With stop-drop in the indoor air coil it is not possible to assemble 

the hot water coil.

Note:

the access panel to the 

fi

 lters is 

fi

 tted with quarter-turn latches 

(models 90 to 180) or  quarter-turn latches (models 200 to 
360). These latches of stainless steel have triangular insert 8 mm. The 
closing mode is described in the chapter of “Maintenance”.

  Note: Refer to the operation mode of the pump with the GREAT 

COLD option in the chapter “Safety elements”.

-  Assembly inside the unit. The inlet/outlet connections of the hot water 

coil are located inside the unit. The connection can be established 
via the unit base using 

fl

 exible piping or via the side panel. 

  In the diagram below the position of the sheet metal precuts is shown 

on the side panel.

Creased opacimetric fi lters

Gravimetric fi lters

Filters

All model types can substitute the 

fi

 ltering mesh that the units include 

regularly with G4 rating, mounted on the same frames. Creased 
opacimetric 

fi

 lters  classi

fi

 ed F6 to F9, as well as double stage F+F 

creased opacimetric 

fi

 lters, can also be added.

Summary of Contents for 50EH

Page 1: ...NANCE INSTRUCTIONS 50EN EH Nominal cooling capacity 21 2 85 2 kW Nominal heating capacity 21 7 88 7 kW 50 Hz Translation of the original document 80046 10 2016 Packaged rooftop cooling only heat pumps...

Page 2: ...Sound Level 13 9 Checking before commissioning 14 Electrical connections 14 Connection of probes by the client 15 Checks in the axial fans 17 Checks in the EC plug fans 18 Checks in the centrifugal f...

Page 3: ...onditioning of medium and large surface areas used for business or industry A vast number of options provide a solution to many operating requirements such a Free cooling Air renewal Air quality contr...

Page 4: ...Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL Artic 22CC Volume of oil l 3 1 3 1 3 1 3 1 3 1 3 1 3 1 5 3 Electrical characteristics Mains voltage 400 V III ph 50 Hz 10 Power sup...

Page 5: ...4 Type Electronic axial fan Number Diameter mm 2 800 Motor output kW 2 x 2 2 Power input in COOLING kW 2 2 2 2 2 2 2 5 2 5 2 5 2 5 Power input in HEATING kW 3 1 3 1 3 1 3 2 3 2 3 2 3 2 Speed r p m 2...

Page 6: ...highly toxic and corrosive To detect leaks an electronic leak detector an ultraviolet lamp or soapy water must be used Flame detectors do not help Important Immediately repair any refrigerant leak usi...

Page 7: ...on mixing box of 3 dampers R N E MA00 I MA01 R I N E MA02 R N E I R N E MC00 I MC02 R N E I MC01 R I N E N E MC10 R I MC11 N E R I MS assemblies Fresh air intake with damper interlocked with return da...

Page 8: ...ere may be dangerous for both the unit and the personnel who are carrying out the discharging or transport work Always check the weight of the set and verify that the discharging method used is approv...

Page 9: ...360T 1301 1034 771 1317 986 750 1297 1145 775 1314 1085 836 Electrical heaters 12 kW 18 kW 27 kW 36 kW 45 kW Weight of module kg 11 15 19 24 29 Centrifugal fans 0 75 kW 1 1 kW 1 5 kW 2 2 kW 3 kW 4 kW...

Page 10: ...way to place the unit in the ultimate location always in observation of the handling standards that have been described below is a proposed assembly sequence that may facilitate the operation keeping...

Page 11: ...172 116 273 188 122 277 179 122 276 178 141 309 191 150 318 200 141 309 191 150 318 200 360HEE 360T 115 282 184 131 298 200 137 301 190 138 302 191 163 342 205 171 351 214 163 342 205 171 351 214 50E...

Page 12: ...ed rooftop units 12 1 5m 1 5m Minimum free space for commissioning and maintenance operations 50EN EH 90HEE 90T 120HEE 120T 160HEE 160T 180HEE and 180T 50EN EH 200HEE 240HEE 240T 320HEE 320T 360HEE an...

Page 13: ...ard unit Unit with return plug fan in top box MC1 optional Unit with return plug fan in top box and MRC1 cooling recovery circuit optional Note The sound pressure level depends on the installation con...

Page 14: ...atic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V 220004 V 220005 The installer must fix line protection elements accord...

Page 15: ...J3 with 2 x 1 5 mm2 section cable within a maximum distance of 30 metres RS485 connector J10 withAWG20 section cable single braided pair preferably shielded with drain wire Power supply 24 Vac 2 wires...

Page 16: ...ng the IAQ Recommended cable section 1 5 mm2 Factory settings 6 5 4 0 10 V 3 2 1 0 Off DIP Switches left position right position 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 IAQ 40 45 50 55 60 65 70 75 80 IAQ IAQ CO...

Page 17: ...he outlet probe B3 and the mixing probe B4 can be replaced by RS485 enthalpic probes for calculation of the cooling and heating capacities optional The outdoor humidity probe optional necessary for th...

Page 18: ...d consumptions The coupling of characteristic curves of the fan and the room is very important so that the flows and pressures provided to the duct network are as required The variable speed plug fans...

Page 19: ...nt drain junction gas threaded Cooling recovery circuit 3 4 M in bronze Gas burner consult in the specific instruction brochure of burners supplied with the burner The air supply and return ducts must...

Page 20: ...int in the electronic control For those units with centrifugal supply fans optional a differential pressostat can be incorporated in order to measure the variation in air flow This pressostat allows t...

Page 21: ...outdoor temperature if the outdoor temperature drops below 4 C the control activates the pump and the 3 way valve opens to maintain in the water coil a water outlet temperature of 10 C in ON operatin...

Page 22: ...of long unit stops and forcibly if they happen in the winter season the coil must be emptied To prevent the water from freezing with this option the unit always has an anti freezing thermostat Add gly...

Page 23: ...inked inside the unit To that extent drills have been made in the unit to which the supports must be screwed Supports attached to the unit Access panel Step 3 Take the hoses with the electric power su...

Page 24: ...eties in the burner The burner module includes a name plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary in...

Page 25: ...The stop drop can be installed in the indoor air coil and at the fresh air intake Indoor air coil recommended in cases where a high moisture content in the air is foreseen or when the air flow is hig...

Page 26: ...anomaly When commissioning the compressors check the subcooling and overheating and thus verify if the refrigerant load is appropriate to the operating conditions If the refrigerant load is lower tha...

Page 27: ...lation In general a corrosion control must be performed on the metallic parts of the unit frame bodywork exchangers electric panel etc Check that the insulation foam is not unstuck or torn All the ele...

Page 28: ...grease Cleaning the accumulated dust on the coil can be performed with a vacuum cleaner perpendicular to the fins or with a low pressure water cleaner Grease can be removed with water with degreaser...

Page 29: ...ated in the characteristics table in chapter 4 Check the oil level and aspect In case of a colour change check the oil quality using a contamination test In the case of the presence of acid water or m...

Page 30: ...he lower rail when sliding Tab for displacement of gravimetric lters of the upper rail Air lters Clean regularly Depending on the installation conditions the filter aspect must be examined to define t...

Page 31: ...to place the frames back on First the frames from the upper rail will be placed on Then the two rail attachment screws will be placed on and finally the frames of the lower rail will be placed on Filt...

Page 32: ...d tilting the rail slightly Attachment screw Tabs in displacement Filters G or G F the frames with each type of filters gravimetrics and opacimetric if the unit has includes the latter are assembled o...

Page 33: ...nt are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electronic c...

Page 34: ...Packaged rooftop units 34 Notes...

Page 35: ......

Page 36: ...Order No 10046 10 2016 Supersedes order No 03 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: