Carrier 50EH Installation, Operation And Maintenance Instructions Download Page 27

Packaged rooftop units

27

Cooling MODE

Compressor

Suction pressure

bar

Suction temperature (1)

ºC

Condensation pressure

bar

Condensation temperature (2)

ºC

Air 

condenser

Gas inlet temperature

ºC

Liquid outlet temperature (3)

ºC

Air inlet temperature

ºC

Outdoor temperature

ºC

Air outlet temperature

ºC

Air 

evaporator

Air inlet temperature

ºC

Air outlet temperature

ºC

Liquid inlet temperature

ºC

Evaporation outlet temperature (4) ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

Heating MODE

Compressor

Suction pressure

bar

Suction temperature (1)

ºC

Condensation pressure

bar

Condensation temperature (2)

ºC

Air 

evaporator

Liquid inlet temperature

ºC

Gas outlet temperature (4)

ºC

Air inlet temperature

ºC

Outdoor temperature

ºC

Air outlet temperature

ºC

Air 

condenser

Air inlet temperature

ºC

Air outlet temperature

ºC

Gas inlet temperature

ºC

Liquid outlet temperature (3)

ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

13. M

AINTENANCE

The minimal maintenance operations and their periodicity will be made 
according to the national regulations. 
Any intervention on the electric cooling components must be made by 
a quali

fi

 ed and authorized technician. 

Technicians who intervene with the unit must use the necessary safety 
equipment (gloves, goggles, insulating clothing, safety shoes, etc.). 
Furthermore, if working around sources of significant noise, we 
recommend the use of noise-dampening headgear.

General recommendations

-  Do not lean on the unit. A platform must be used to work on a level.

-  Do not lean on the copper refrigerant tubes.

-  Keep the unit clean. 

-  Keep the space surrounding the unit clean and cleared in order to 

avoid accidents and ensure the proper ventilation of the coil.

-  Perform a visual (remains of water or oil below or around the unit) 

and auditory inspection of the entire installation.

-  In general, a corrosion control must be performed on the metallic 

parts of the unit (frame, bodywork, exchangers, electric panel, etc.). 

-  Check that the insulation foam is not unstuck or torn.

-  All the electric connection states must be checked as well, as well 

as the air tightness of the different circuits.

Check the unit operation by verifying the electronic control and the 
safety devices.
It is also recommendable to create a report, taking note of the date, 
which includes the following information: 
-  the nominal voltage, 
-  current absorbed by the compressors, fans and other electrical 

components, 

- signi

fi

 cant temperatures in the cooling circuit (see attached table), 

-  other aspects considered interesting such as alarms detected by the 

electronic control of the unit. 

The recording of these parameters whilst the unit is running allows 
controlling the installation performance and it is the best possible way 
to avoid breakdowns since the analysis of these data makes early 
detection of anomalies possible or the provision of the necessary means 
available to ensure that they do not take place.

Operational checks

Possible problems at commissioning

All indications given in this brochure must be respected and 
complied with to guarantee a correct operation of the units.

Next, several possible operation problems are stated which could 
happen if the conditions of the commissioning are not appropriate.
-  Air flow lack: very high differences between inlet and outlet 

temperatures, originated by a high pressure drop in the ducts, or by 
other causes that impede the correct circulation.

-  Air recirculation in the unit, originated by some obstacle in the air 

aspiration or outlet.

-  Noise problems because of excessive air 

fl

 ow in the grille.

-  Water over

fl

 owing to the pan problems, originated by an excessive 

fl

 ow, an incorrect siphon installation or because a defective unit level.

-  Refrigerant circuit humidity problem, because of an incorrect vacuum 

realization.

Summary of Contents for 50EH

Page 1: ...NANCE INSTRUCTIONS 50EN EH Nominal cooling capacity 21 2 85 2 kW Nominal heating capacity 21 7 88 7 kW 50 Hz Translation of the original document 80046 10 2016 Packaged rooftop cooling only heat pumps...

Page 2: ...Sound Level 13 9 Checking before commissioning 14 Electrical connections 14 Connection of probes by the client 15 Checks in the axial fans 17 Checks in the EC plug fans 18 Checks in the centrifugal f...

Page 3: ...onditioning of medium and large surface areas used for business or industry A vast number of options provide a solution to many operating requirements such a Free cooling Air renewal Air quality contr...

Page 4: ...Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL Artic 22CC Volume of oil l 3 1 3 1 3 1 3 1 3 1 3 1 3 1 5 3 Electrical characteristics Mains voltage 400 V III ph 50 Hz 10 Power sup...

Page 5: ...4 Type Electronic axial fan Number Diameter mm 2 800 Motor output kW 2 x 2 2 Power input in COOLING kW 2 2 2 2 2 2 2 5 2 5 2 5 2 5 Power input in HEATING kW 3 1 3 1 3 1 3 2 3 2 3 2 3 2 Speed r p m 2...

Page 6: ...highly toxic and corrosive To detect leaks an electronic leak detector an ultraviolet lamp or soapy water must be used Flame detectors do not help Important Immediately repair any refrigerant leak usi...

Page 7: ...on mixing box of 3 dampers R N E MA00 I MA01 R I N E MA02 R N E I R N E MC00 I MC02 R N E I MC01 R I N E N E MC10 R I MC11 N E R I MS assemblies Fresh air intake with damper interlocked with return da...

Page 8: ...ere may be dangerous for both the unit and the personnel who are carrying out the discharging or transport work Always check the weight of the set and verify that the discharging method used is approv...

Page 9: ...360T 1301 1034 771 1317 986 750 1297 1145 775 1314 1085 836 Electrical heaters 12 kW 18 kW 27 kW 36 kW 45 kW Weight of module kg 11 15 19 24 29 Centrifugal fans 0 75 kW 1 1 kW 1 5 kW 2 2 kW 3 kW 4 kW...

Page 10: ...way to place the unit in the ultimate location always in observation of the handling standards that have been described below is a proposed assembly sequence that may facilitate the operation keeping...

Page 11: ...172 116 273 188 122 277 179 122 276 178 141 309 191 150 318 200 141 309 191 150 318 200 360HEE 360T 115 282 184 131 298 200 137 301 190 138 302 191 163 342 205 171 351 214 163 342 205 171 351 214 50E...

Page 12: ...ed rooftop units 12 1 5m 1 5m Minimum free space for commissioning and maintenance operations 50EN EH 90HEE 90T 120HEE 120T 160HEE 160T 180HEE and 180T 50EN EH 200HEE 240HEE 240T 320HEE 320T 360HEE an...

Page 13: ...ard unit Unit with return plug fan in top box MC1 optional Unit with return plug fan in top box and MRC1 cooling recovery circuit optional Note The sound pressure level depends on the installation con...

Page 14: ...atic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V 220004 V 220005 The installer must fix line protection elements accord...

Page 15: ...J3 with 2 x 1 5 mm2 section cable within a maximum distance of 30 metres RS485 connector J10 withAWG20 section cable single braided pair preferably shielded with drain wire Power supply 24 Vac 2 wires...

Page 16: ...ng the IAQ Recommended cable section 1 5 mm2 Factory settings 6 5 4 0 10 V 3 2 1 0 Off DIP Switches left position right position 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 IAQ 40 45 50 55 60 65 70 75 80 IAQ IAQ CO...

Page 17: ...he outlet probe B3 and the mixing probe B4 can be replaced by RS485 enthalpic probes for calculation of the cooling and heating capacities optional The outdoor humidity probe optional necessary for th...

Page 18: ...d consumptions The coupling of characteristic curves of the fan and the room is very important so that the flows and pressures provided to the duct network are as required The variable speed plug fans...

Page 19: ...nt drain junction gas threaded Cooling recovery circuit 3 4 M in bronze Gas burner consult in the specific instruction brochure of burners supplied with the burner The air supply and return ducts must...

Page 20: ...int in the electronic control For those units with centrifugal supply fans optional a differential pressostat can be incorporated in order to measure the variation in air flow This pressostat allows t...

Page 21: ...outdoor temperature if the outdoor temperature drops below 4 C the control activates the pump and the 3 way valve opens to maintain in the water coil a water outlet temperature of 10 C in ON operatin...

Page 22: ...of long unit stops and forcibly if they happen in the winter season the coil must be emptied To prevent the water from freezing with this option the unit always has an anti freezing thermostat Add gly...

Page 23: ...inked inside the unit To that extent drills have been made in the unit to which the supports must be screwed Supports attached to the unit Access panel Step 3 Take the hoses with the electric power su...

Page 24: ...eties in the burner The burner module includes a name plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary in...

Page 25: ...The stop drop can be installed in the indoor air coil and at the fresh air intake Indoor air coil recommended in cases where a high moisture content in the air is foreseen or when the air flow is hig...

Page 26: ...anomaly When commissioning the compressors check the subcooling and overheating and thus verify if the refrigerant load is appropriate to the operating conditions If the refrigerant load is lower tha...

Page 27: ...lation In general a corrosion control must be performed on the metallic parts of the unit frame bodywork exchangers electric panel etc Check that the insulation foam is not unstuck or torn All the ele...

Page 28: ...grease Cleaning the accumulated dust on the coil can be performed with a vacuum cleaner perpendicular to the fins or with a low pressure water cleaner Grease can be removed with water with degreaser...

Page 29: ...ated in the characteristics table in chapter 4 Check the oil level and aspect In case of a colour change check the oil quality using a contamination test In the case of the presence of acid water or m...

Page 30: ...he lower rail when sliding Tab for displacement of gravimetric lters of the upper rail Air lters Clean regularly Depending on the installation conditions the filter aspect must be examined to define t...

Page 31: ...to place the frames back on First the frames from the upper rail will be placed on Then the two rail attachment screws will be placed on and finally the frames of the lower rail will be placed on Filt...

Page 32: ...d tilting the rail slightly Attachment screw Tabs in displacement Filters G or G F the frames with each type of filters gravimetrics and opacimetric if the unit has includes the latter are assembled o...

Page 33: ...nt are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electronic c...

Page 34: ...Packaged rooftop units 34 Notes...

Page 35: ......

Page 36: ...Order No 10046 10 2016 Supersedes order No 03 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: