WICHTIG: WIEDERBEHEIZUNG DER

OLWANNE

IMPORTANT: CRANKCASE HEATING

IMPORTANT: SURCHAUFFE CARTER D’HUILE

IMPORTANTE: RISCALDARE IL CARTER

DELL’OLIO

IMPORTANTE: RECALENTAMIENTO DE

ACEITE DEL CÁRTER

KOENNEN.

TO ALLOW THE COMPRESSOR(S) STARTING

AU PREMIER DÉMARRAGE OU APRÈS UNE ABSCENCE

TENSION 24 HEURES AVANT D’AUTORISER LE

DÉMARRAGE DU(DES) COMPRESSEUR(S).

AL PRIMO AVVIAMENTO U DOPO UNA INTERRUZIONE

PROLUNGATA DELLA ALIMENTAZIONE ELETTRICA,

LASCIARE LA MACCINA SOTTO TENSIONE PER 24 ORE

PRIMA DI AUTORIZZARE L’AVVIAMENTO DEL(DEI)

COMPRESSORE(I).

ANTES DEL PRIMER ARRANQUE O DESPUÉS DE UNA

AUSENCIA DE CORRIENTE POR UN LARGO PERIODO DE

TIEMPO, CONVIENE QUE LA UNIDAD ESTÉ CONECTADA

UN MÍNIMO DE 24 HORAS.

BEIDER ERSTEN INBETRIEBSETRUNZ ORDER NACH EINER

LANGEN STROMUNTER-BRECHUNG BRINGEN SIE DIE

MASCHINE UNTER SPANNUNG 24 STRUNDERLANG

BEVOR SIE DEN(DIE) KOMPRESSOR(EN) EINSCHALTEN

FOR THE FIRSTSTART OR AFTER ALONG TIME OUT OF

VOLTAGE PUT THE MACHINE ON LIVE 24 HOURS BEFORE

DE COURANT PROLONGÉE, METTRE LA MACHINE SOUS

COMPRESOR SCROLL.

COMPROBAR SENTIDO DE GIRO

COMPRESSEUR SCROLL.

VÉRIFIER LE SENS DE ROTATION

SCROLL COMPRESSOR.

CHECK SENSE OF ROTATION

-  Check the unit operation and verify the safety devices.

-  Verify the absence of any leaks of the refrigerant. In case of a leak:

•  Completely empty the unit using a speci

fi

 c recovery unit for R-410A 

and repair the leak. 

•  Next, reload the gas into the unit according to load data provided 

in the technical characteristics table and in the unit’s data plate.

•  Add the refrigerant via the schrader valve of the liquid line using the 

appropriate equipment and tools, with the compressor(s) stopped, 
monitoring the pressures to control any anomaly.

-  When commissioning the compressors, check the subcooling and 

overheating and thus verify if the refrigerant load is appropriate to 
the operating conditions.

-  If the refrigerant load is lower than required, the suction pressure 

will be rather lower than normal, and overheating when suctioning 
from the compressors will be high. This can cause an interruption 
in operation due to activation of the refrigerant load safety device.

  To adjust the refrigerant load, a schrader valve is built into the unit 

on the liquid line for each circuit.  

  Note: the schrader valves are located inside the compressors 

enclosure.

R 410A

Control of the refrigerant load

Access to the compressors 

enclosure of circuit 1 and 

recovery circuit (optional)

Access to the 

compressors

enclosure of circuit 2

Models 200 to 360

-  All the 50EN/EH models are equipped with scroll type compressors 

and have a phase control relay. Verify that they turn in the correct 
direction and, if not, reverse the power wires.

12. C

OMMISSIONING

Checks prior to commissioning

-  It is advisable to make a complete sketch of the installation including 

the location of the unit and all the components used. This will be very 
helpful for maintenance and repairs to the installation.

-  The following must be veri

fi

 ed:

•  That  the  electrical  power  supply  remains  constant  and  that  it 

corresponds to that featured on the unit data plate.

•  That the electric installation has been carried out according to the 

electric wiring diagram provided with the unit (consult the chapter 
on “Checking before commissioning”). 

•  The correct connection of the sensors supplied with the unit.
•  That they are no cables close to heat sources.

-  Once the above veri

fi

 cations have been carried out, the control circuit 

is supplied with voltage by the automatic control switch. It is necessary 
to leave the compressor crankcase heater with voltage for 24 hours 
before starting the compressor.

Summary of Contents for 50EH

Page 1: ...NANCE INSTRUCTIONS 50EN EH Nominal cooling capacity 21 2 85 2 kW Nominal heating capacity 21 7 88 7 kW 50 Hz Translation of the original document 80046 10 2016 Packaged rooftop cooling only heat pumps...

Page 2: ...Sound Level 13 9 Checking before commissioning 14 Electrical connections 14 Connection of probes by the client 15 Checks in the axial fans 17 Checks in the EC plug fans 18 Checks in the centrifugal f...

Page 3: ...onditioning of medium and large surface areas used for business or industry A vast number of options provide a solution to many operating requirements such a Free cooling Air renewal Air quality contr...

Page 4: ...Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL Artic 22CC Volume of oil l 3 1 3 1 3 1 3 1 3 1 3 1 3 1 5 3 Electrical characteristics Mains voltage 400 V III ph 50 Hz 10 Power sup...

Page 5: ...4 Type Electronic axial fan Number Diameter mm 2 800 Motor output kW 2 x 2 2 Power input in COOLING kW 2 2 2 2 2 2 2 5 2 5 2 5 2 5 Power input in HEATING kW 3 1 3 1 3 1 3 2 3 2 3 2 3 2 Speed r p m 2...

Page 6: ...highly toxic and corrosive To detect leaks an electronic leak detector an ultraviolet lamp or soapy water must be used Flame detectors do not help Important Immediately repair any refrigerant leak usi...

Page 7: ...on mixing box of 3 dampers R N E MA00 I MA01 R I N E MA02 R N E I R N E MC00 I MC02 R N E I MC01 R I N E N E MC10 R I MC11 N E R I MS assemblies Fresh air intake with damper interlocked with return da...

Page 8: ...ere may be dangerous for both the unit and the personnel who are carrying out the discharging or transport work Always check the weight of the set and verify that the discharging method used is approv...

Page 9: ...360T 1301 1034 771 1317 986 750 1297 1145 775 1314 1085 836 Electrical heaters 12 kW 18 kW 27 kW 36 kW 45 kW Weight of module kg 11 15 19 24 29 Centrifugal fans 0 75 kW 1 1 kW 1 5 kW 2 2 kW 3 kW 4 kW...

Page 10: ...way to place the unit in the ultimate location always in observation of the handling standards that have been described below is a proposed assembly sequence that may facilitate the operation keeping...

Page 11: ...172 116 273 188 122 277 179 122 276 178 141 309 191 150 318 200 141 309 191 150 318 200 360HEE 360T 115 282 184 131 298 200 137 301 190 138 302 191 163 342 205 171 351 214 163 342 205 171 351 214 50E...

Page 12: ...ed rooftop units 12 1 5m 1 5m Minimum free space for commissioning and maintenance operations 50EN EH 90HEE 90T 120HEE 120T 160HEE 160T 180HEE and 180T 50EN EH 200HEE 240HEE 240T 320HEE 320T 360HEE an...

Page 13: ...ard unit Unit with return plug fan in top box MC1 optional Unit with return plug fan in top box and MRC1 cooling recovery circuit optional Note The sound pressure level depends on the installation con...

Page 14: ...atic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V 220004 V 220005 The installer must fix line protection elements accord...

Page 15: ...J3 with 2 x 1 5 mm2 section cable within a maximum distance of 30 metres RS485 connector J10 withAWG20 section cable single braided pair preferably shielded with drain wire Power supply 24 Vac 2 wires...

Page 16: ...ng the IAQ Recommended cable section 1 5 mm2 Factory settings 6 5 4 0 10 V 3 2 1 0 Off DIP Switches left position right position 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 IAQ 40 45 50 55 60 65 70 75 80 IAQ IAQ CO...

Page 17: ...he outlet probe B3 and the mixing probe B4 can be replaced by RS485 enthalpic probes for calculation of the cooling and heating capacities optional The outdoor humidity probe optional necessary for th...

Page 18: ...d consumptions The coupling of characteristic curves of the fan and the room is very important so that the flows and pressures provided to the duct network are as required The variable speed plug fans...

Page 19: ...nt drain junction gas threaded Cooling recovery circuit 3 4 M in bronze Gas burner consult in the specific instruction brochure of burners supplied with the burner The air supply and return ducts must...

Page 20: ...int in the electronic control For those units with centrifugal supply fans optional a differential pressostat can be incorporated in order to measure the variation in air flow This pressostat allows t...

Page 21: ...outdoor temperature if the outdoor temperature drops below 4 C the control activates the pump and the 3 way valve opens to maintain in the water coil a water outlet temperature of 10 C in ON operatin...

Page 22: ...of long unit stops and forcibly if they happen in the winter season the coil must be emptied To prevent the water from freezing with this option the unit always has an anti freezing thermostat Add gly...

Page 23: ...inked inside the unit To that extent drills have been made in the unit to which the supports must be screwed Supports attached to the unit Access panel Step 3 Take the hoses with the electric power su...

Page 24: ...eties in the burner The burner module includes a name plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary in...

Page 25: ...The stop drop can be installed in the indoor air coil and at the fresh air intake Indoor air coil recommended in cases where a high moisture content in the air is foreseen or when the air flow is hig...

Page 26: ...anomaly When commissioning the compressors check the subcooling and overheating and thus verify if the refrigerant load is appropriate to the operating conditions If the refrigerant load is lower tha...

Page 27: ...lation In general a corrosion control must be performed on the metallic parts of the unit frame bodywork exchangers electric panel etc Check that the insulation foam is not unstuck or torn All the ele...

Page 28: ...grease Cleaning the accumulated dust on the coil can be performed with a vacuum cleaner perpendicular to the fins or with a low pressure water cleaner Grease can be removed with water with degreaser...

Page 29: ...ated in the characteristics table in chapter 4 Check the oil level and aspect In case of a colour change check the oil quality using a contamination test In the case of the presence of acid water or m...

Page 30: ...he lower rail when sliding Tab for displacement of gravimetric lters of the upper rail Air lters Clean regularly Depending on the installation conditions the filter aspect must be examined to define t...

Page 31: ...to place the frames back on First the frames from the upper rail will be placed on Then the two rail attachment screws will be placed on and finally the frames of the lower rail will be placed on Filt...

Page 32: ...d tilting the rail slightly Attachment screw Tabs in displacement Filters G or G F the frames with each type of filters gravimetrics and opacimetric if the unit has includes the latter are assembled o...

Page 33: ...nt are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electronic c...

Page 34: ...Packaged rooftop units 34 Notes...