95
APPENDIX I. PHYSICAL DATA (cont.)
Table 43 – PHYSICAL DATA
(HEATING)
7.5 -- 10 TONS
48TC**08
48TC**09
48TC**12
Gas Connection
# of Gas Valves
1
1
1
Nat. gas supply line press (in. w.g.)/ (PSIG)
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
LP supply line press (in. w.g.) / (PSIG)
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
Heat Anticipator setting (Amps)
1st stage
0.14
0.14
0.14
2nd stage
0.14
0.14
0.14
Natural Gas Heat
LO
W
# of stages / # of burners (total)
1 / 3
1 / 3
2 / 4
Connection Size
1/2---in NPT
1/2---in NPT
3/4---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
Temperature Rise
20 --- 50
20 --- 50
25 --- 65
ME
D
# of stages / # of burners (total)
2 / 4
2 / 4
2 / 5
Connection Size
3/4---in NPT
3/4---in NPT
3/4---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
Temperature Rise
35 --- 65
30 --- 65
30 --- 65
HI
G
H
# of stages / # of burners (total)
2 / 5
2 / 5
2 / 5
Connection Size
3/4---in NPT
3/4---in NPT
3/4---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
Temperature Rise
45 --- 75
40 --- 75
35 --- 70
Liquid Propane Heat
LO
W
# of stages / # of burners (total)
1 / 3
1 / 3
2 / 4
Connection Size
1/2---in NPT
1/2---in NPT
3/4---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
Temperature Rise
20 --- 50
20 --- 50
25 --- 65
ME
D
# of stages / # of burners (total)
2 / 4
2 / 4
2 / 5
Connection Size
3/4---in NPT
3/4---in NPT
3/4---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
Temperature Rise
35 --- 65
30 --- 65
30 --- 65
HI
G
H
# of stages / # of burners (total)
2 / 5
2 / 5
2 / 5
Connection Size
3/4---in NPT
3/4---in NPT
3/4---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
Temperature Rise
45 --- 75
40 --- 75
35 --- 70
Low NOx Gas Heat
LO
W
# of stages / # of burners (total)
---
---
---
Connection Size
---
---
---
Rollout switch opens / closes
---
---
---
Temperature Rise
---
---
---
ME
D
# of stages / # of burners (total)
---
---
---
Connection Size
---
---
---
Rollout switch opens / closes
---
---
---
Temperature Rise
---
---
---
HI
G
H
# of stages / # of burners (total)
---
---
---
Connection Size
---
---
---
Rollout switch opens / closes
---
---
---
Temperature Rise
---
---
---
--- Not applicable
48TC
Summary of Contents for 48TC 04 Series
Page 27: ...27 COOLING CHARGING CHARTS cont C14064 Fig 33 Cooling Charging Charts 12 5 Ton 48TC...
Page 29: ...29 COOLING CHARGING CHARTS cont C13218 Fig 35 Charging Chart 48TC Size D16 48TC...
Page 40: ...40 C14052 Fig 51 Typical Smoke Detector System Wiring 48TC...
Page 122: ...122 APPENDIX III WIRING DIAGRAMS C12413 Fig 103 48TC A04 A07 Power Diagram 208 230 1 60 48TC...
Page 124: ...124 APPENDIX III WIRING DIAGRAM LIST C12415 Fig 105 48TC A04 A07 Power Diagram 575 3 60 48TC...
Page 126: ...126 APPENDIX III WIRING DIAGRAM LIST C13246 Fig 107 48TC A08 A12 Power Diagram 575 3 60 48TC...
Page 128: ...128 APPENDIX III WIRING DIAGRAM LIST C13247 Fig 109 48TC D08 D12 Power Diagram 575 3 60 48TC...
Page 130: ...130 APPENDIX III WIRING DIAGRAM LIST C13249 Fig 111 48TC D14 Power Diagram 575 3 60 48TC...
Page 139: ...139 APPENDIX III WIRING DIAGRAMS C12423 Fig 120 48TC D16 Power Diagram 575 3 60 48TC...
Page 143: ...143 APPENDIX III WIRING DIAGRAM LIST C13485 Fig 124 48TC 16 PremierLink Control Diagram 48TC...
Page 145: ...145 APPENDIX III WIRING DIAGRAM LIST C13487 Fig 126 48TC 16 RTU Open Control Diagram 48TC...
Page 146: ...146 APPENDIX III WIRING DIAGRAM LIST C14124 Fig 127 48TC D08 14 E08 14 W7220 2 Speed IFM 48TC...