42
Configuring the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensor’s Alarm LED
turns on and its Dirty LED flashes twice (approxim-
ately 60 seconds).
2. Reset the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensor’s Alarm LED turns off (approximately 2
seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
NOTICE
: This test places the duct detector into the alarm
state. Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the test.
If the duct detector is connected to a fire alarm system,
notify the proper authorities before performing the test.
SD--TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position
for seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
3. Reset the sensor by turning the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns
off.
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset
station’s ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 52 and configured to operate the controller’s
supervision relay. For more information, see “Changing
sensor dirty test operation.”
1
12
14
13
19
15
2
20
3
Reset/Test
Trouble
Power
Alarm
Supervision relay
contacts [3]
5
4
1
3
2
SD-TRK4
2
1
TB3
18 Vdc ( )
+
18 Vdc ( )
−
Auxiliary
equipment
+
−
Wire must be
added by installer
Smoke Detector Controller
C08247
Fig. 52 -- Remote Test/Reset Station Connections
NOTICE
: If the test/reset station’s key switch is left in
the RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state and
activate all automatic alarm responses.
Dirty Sensor Test Using an SD--TRK4
1. Turn the key switch to the RESET/TEST position
for two seconds.
2. Verify that the test/reset station’s Trouble LED
flashes.
Detector Cleaning
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is
flashing continuously or sooner if conditions warrant.
NOTICE
: If the smoke detector is connected to a fire
alarm system, first notify the proper authorities that the
detector is undergoing maintenance then disable the
relevant circuit to avoid generating a false alarm.
1. Disconnect power from the duct detector then re-
move the sensor’s cover. See Fig. 53.
AIRFLOW
HVAC DUCT
SAMPLING
TUBE
RETAINER
CLIP
OPTIC
PLATE
OPTIC
HOUSING
SENSOR
HOUSING
C07305
Fig. 53 -- Sensor Cleaning Diagram
2. Using a vacuum cleaner, clean compressed air, or a
soft bristle brush, remove loose dirt and debris from
inside the sensor housing and cover.
Use isopropyl alcohol and a lint--free cloth to remove
dirt and other contaminants from the gasket on the
sensor’s cover.
3. Squeeze the retainer clips on both sides of the optic
housing then lift the housing away from the printed
circuit board.
4. Gently remove dirt and debris from around the optic
plate and inside the optic housing.
5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a
sensor alarm test.
48TC
Summary of Contents for 48TC 04 Series
Page 27: ...27 COOLING CHARGING CHARTS cont C14064 Fig 33 Cooling Charging Charts 12 5 Ton 48TC...
Page 29: ...29 COOLING CHARGING CHARTS cont C13218 Fig 35 Charging Chart 48TC Size D16 48TC...
Page 40: ...40 C14052 Fig 51 Typical Smoke Detector System Wiring 48TC...
Page 122: ...122 APPENDIX III WIRING DIAGRAMS C12413 Fig 103 48TC A04 A07 Power Diagram 208 230 1 60 48TC...
Page 124: ...124 APPENDIX III WIRING DIAGRAM LIST C12415 Fig 105 48TC A04 A07 Power Diagram 575 3 60 48TC...
Page 126: ...126 APPENDIX III WIRING DIAGRAM LIST C13246 Fig 107 48TC A08 A12 Power Diagram 575 3 60 48TC...
Page 128: ...128 APPENDIX III WIRING DIAGRAM LIST C13247 Fig 109 48TC D08 D12 Power Diagram 575 3 60 48TC...
Page 130: ...130 APPENDIX III WIRING DIAGRAM LIST C13249 Fig 111 48TC D14 Power Diagram 575 3 60 48TC...
Page 139: ...139 APPENDIX III WIRING DIAGRAMS C12423 Fig 120 48TC D16 Power Diagram 575 3 60 48TC...
Page 143: ...143 APPENDIX III WIRING DIAGRAM LIST C13485 Fig 124 48TC 16 PremierLink Control Diagram 48TC...
Page 145: ...145 APPENDIX III WIRING DIAGRAM LIST C13487 Fig 126 48TC 16 RTU Open Control Diagram 48TC...
Page 146: ...146 APPENDIX III WIRING DIAGRAM LIST C14124 Fig 127 48TC D08 14 E08 14 W7220 2 Speed IFM 48TC...