background image

17

4. Divide number of seconds in Step 3 into 3600 (number of

seconds in one hr).

5. Multiply result of Step 4 by the number of cubic feet (cu ft)

shown for one revolution of test dial to obtain cubic feet (cu
ft) of gas flow per hour.

6. Multiply result of Step 5 by Btu heating value of gas to

obtain total measured input in Btuh. Compare this value

with heating input shown in Table 3 (Consult the local gas
supplier if the heating value of gas is not known).

EXAMPLE: Assume that the size of test dial is 1 cu ft, one

revolution takes 32 sec, and the heating value of the gas is 1050

Btu/ft

3

. Proceed as follows:

1. 32 sec. to complete one revolution.
2. 3600

÷

32 = 112.5.

3. 112.5 x 1 =112.5 ft

3

of gas flow/hr.

4. 112.5 x 1050 = 118,125 Btuh input.

If the desired gas input is 115,000 Btuh, only a minor change in the
manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas

input:

1. Remove regulator cover screw over plastic adjustment

screw on gas valve (See Fig. 13).

2. Turn plastic adjustment screw clockwise to increase gas

input, or turn plastic adjustment screw counterclockwise to

decrease input (See Fig. 13). Manifold pressure must be
between 3.2 and 3.8 IN. W.C.

REGULATOR 
COVER SCREW

ADJUSTMENT
SCREW

REGULATOR SPRING
(PROPANE - WHITE)

NATURAL - SILVER)

GAS PRESSURE 
REGULATOR 
ADJUSTMENT

MANIFOLD 
PRESSURE TAP

INLET 
PRESSURE TAP

ON/OFF SWITCH

PLASTIC

(

A07751

Fig. 13 -- Single--Stage Gas Valve

FIRE AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure

is outside this range.

!

WARNING

3. Replace regulator cover screw on gas valve (See Fig. 13).
4. Turn off gas supply to unit. Remove manometer from

pressure tap and replace pipe plug on gas valve. (See Fig.
11.) Turn on gas to unit and check for leaks.

Measure Manifold Pressure (Propane Units)

Refer to propane kit installation instructions for properly checking

gas input.

NOTE

: For installations below 2,000 ft (610 m), refer to the unit

rating plate for proper propane conversion kit. For installations
above 2,000 ft (610 m), contact your distributor for proper propane
conversion kit.

Check Burner Flame

With control access panel (see Fig. 19) removed, observe the unit
heating operation. Watch the burner flames to see if they are light

blue and soft in appearance, and that the flames are approximately

the same for each burner. Propane will have blue flame (See Fig.
12). Refer to the Maintenance section for information on burner

removal.

Normal Operation

An LED (light--emitting diode) indicator is provided on the
integrated gas unit controller (IGC) to monitor operation. The IGC

is located by removing the control access panel (see Fig. 19).
During normal operation, the LED is continuously on (See Table 5

for error codes).

Airflow and Temperature Rise

The heating section for each size unit is designed and approved for
heating operation within the temperature--rise range stamped on the

unit rating plate.
Table 10 shows the approved temperature rise range for each
heating input, and the air delivery cfm at various temperature rises

for a given external static pressure. The heating operation airflow
must produce a temperature rise that falls within the approved

range.
Refer to Indoor Airflow and Airflow Adjustments section to adjust
heating airflow when required.

Limit Switches

Normally closed limit switch (LS) completes the control circuit.
Should the leaving--air temperature rise above the maximum

allowable temperature, the limit switch opens and the control

circuit “breaks.” Any interruption in the control circuit instantly
closes the gas valve and stops gas flow to the burners. The blower

motor continues to run until LS resets.
When the air temperature at the limit switch drops to the

low--temperature setting of the limit switch, the switch closes and

completes the control circuit. The direct--spark ignition system
cycles and the unit returns to normal heating operation.

Table 5 – LED Indications

STATUS CODE

LED INDICATION

Normal Operation

2

On

No Power or Hardware Failure

Off

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Four Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Pressure Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Temporary 1 hr auto reset

1

9 Flashes

NOTES:

1.This code indicates an internal processor fault that will reset itself in one

hr. Fault can be caused by stray RF signals in the structure or nearby. This

is a UL requirement.

2. LED indicates acceptable operation. Do not change ignition control

board.

3. When W is energized the burners will remain on for a minimum of 60 sec.

4. If more than one error mode exists they will be displayed on the LED in

sequence.

Rollout Switch

The function of the rollout switch is to close the main gas valve in
the event of flame rollout. The switch is located above the main

burners. When the temperature at the rollout switch reaches the

maximum allowable temperature, the control circuit trips, closing
the gas valve and stopping gas flow to the burners. The indoor

(evaporator) fan motor (IFM) and induced draft motor continue to
run until switch is reset. The IGC LED will display FAULT CODE

7.

48E

Z

--

A

Summary of Contents for 48EZ(N) - A

Page 1: ...Limit Switch 29 Burner Ignition 29 Main Burners 29 Outdoor Coil Indoor Coil Condensate Drain Pan 29 A09034 Fig 1 Unit 48EZ A Outdoor Fan 30 Electrical Controls and Wiring 30 Refrigerant Circuit 30 Ga...

Page 2: ...ms against shipping list Immediately notify the nearest equipment distribution office if any item is missing To prevent loss or damage leave all parts in original packages until installation If the un...

Page 3: ...3 A09450 Fig 2 48EZ A24 36 Unit Dimensions 48EZ A...

Page 4: ...4 A09451 Fig 3 48EZ A42 60 Unit Dimensions 48EZ A...

Page 5: ...S 1 Roof curb must be set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 gauge steel 4 Attach ductwork to curb flanges of duct r...

Page 6: ...t recirculate to the condenser coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a normal house overhang is 48 in 1...

Page 7: ...verflowing Prime the trap with water Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap Do not undersize the tube Pitc...

Page 8: ...supply pipe within 6 ft 1 8 m of heating section 6 Install ground joint union close to heating section between unit manual shutoff and external manual main shut off valve 7 Pressure test all gas pipi...

Page 9: ...3 7 3 17 3 7 3 17 4 7 3 17 4 7 INDOOR BLOWER Nominal Cooling Airflow CFM Size in mm Motor hp 800 10x10 254x254 1 2 800 10x10 254x254 1 2 1000 10x10 254x254 1 2 1000 10x10 254x254 1 2 1200 11x10 279x2...

Page 10: ...ceed 0 08 IN W C If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity Table 2 Maximum Gas Flow Capacity NOMINAL IRON PIPE SIZE IN INTERNAL...

Page 11: ...amage to the unit being installed When cutting duct panels do not contact or damage any internal components heat exchanger electric heat Do not use a saw blade that protrudes more than 1 in 25 mm into...

Page 12: ...y Knockout Basepan Downflow Vertical Return Knockout A09060 Fig 8 Supply and Return Duct Opening Return Duct Panels Return Supply Duct Panels from Underside of Base Alternate Method Supply Duct Panels...

Page 13: ...nd Fig 10 for reference when making high voltage connections Proceed as follows to complete the high voltage connections to the unit Single phase units 1 Run the high voltage L1 L2 and ground lead int...

Page 14: ...thstand a 30 sec overload or shorted secondary condition If an overload or short is present correct overload condition and check for blown fuse on gas control board or Interface Fan Board Replace fuse...

Page 15: ...before the time delay has expired 2 T2 energizes the compressor contactor via the High Pressure Switch HPS and Low Pressure Switch LPS The compressor and outdoor fan start Thermostat G energizes the...

Page 16: ...DERATE MULTIPLIER FACTOR 0 2000 0 610 0 1 00 2001 3000 610 914 8 12 0 90 3001 4000 315 1219 12 16 0 86 4001 5000 1220 1524 16 20 0 82 5001 6000 1524 1829 20 24 0 78 6001 7000 1829 2134 24 28 0 74 7001...

Page 17: ...ormal Operation An LED light emitting diode indicator is provided on the integrated gas unit controller IGC to monitor operation The IGC is located by removing the control access panel see Fig 19 Duri...

Page 18: ...abnormal condition exists somewhere in the cooling system such as insufficient airflow across either coil or both coils CAUTION Proceed as follows 1 Remove caps from low and high pressure service fit...

Page 19: ...wire from the LOW terminal on the interface fan board IFB See Fig 14 2 Determine correct normal cooling fan speed for unit and application Add the wet coil pressure drop in Table 8 to the system stati...

Page 20: ...WIRE COLOR EXTERNAL STATIC PRESSURE in W C 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 48EZ N A24040 30 60oF 17 33oC Low Blue CFM 754 650 538 429 Heating Rise oF 40 46 56 NA NA NA NA NA NA Heating Rise oC 22...

Page 21: ...665 538 451 Heating Rise oF 46 50 54 NA NA NA NA NA NA Heating Rise oC 25 28 30 NA NA NA NA NA NA Medium Red CFM 1088 1023 954 881 800 723 658 563 461 Heating Rise oF 41 43 47 50 NA NA NA NA NA Heatin...

Page 22: ...CFM 1345 1282 1235 1194 1140 1095 1027 974 921 Heating Rise oF 33 35 36 37 39 41 43 46 48 Heating Rise oC 18 19 20 21 22 23 24 25 27 Medium Red CFM 1505 1452 1413 1358 1323 1282 1234 1169 1130 Heating...

Page 23: ...nk CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104 Heating Rise oF 60 NA NA NA NA NA NA NA NA Heating Rise oC 33 NA NA NA NA NA NA NA NA Medium2 Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381 H...

Page 24: ...8 49 49 51 51 53 Heating Rise oC 25 26 26 26 27 27 28 29 29 Med High1 Orange CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785 Heating Rise oF 41 42 42 43 44 45 46 47 49 Heating Rise oC 23 23 23 24 24...

Page 25: ...25 A09068 Fig 15 208 230 1 60 Wiring Diagram Unit 48EZ A 48EZ A...

Page 26: ...26 A09209 Fig 16 208 230 3 60 Wiring Diagram Unit 48EZ A 48EZ A...

Page 27: ...27 A08019 Fig 17 Cooling Charging Table Subcooling 48EZ A...

Page 28: ...pect blower wheel bi monthly to determine proper cleaning frequency 4 Check electrical connections for tightness and controls for proper operation each heating and cooling season Service when necessar...

Page 29: ...Table 5 in these instructions for LED interpretation If lockout occurs unit may be reset by either momentarily interrupting power supply to unit or by turning selector switch to OFF position at the t...

Page 30: ...l controls and wiring annually Be sure to turn off the gas supply and then the electrical power to the unit Remove access panels see Fig 19 to locate all the electrical controls and wiring Check all e...

Page 31: ...supply and return air grilles are open and free from obstructions and that the air filter is clean When necessary refer to the Indoor Airflow and Airflow Adjustments section to check the system airfl...

Page 32: ...rigerant The compressor used in this product is specifically designed to operate with Puron R 410A refrigerant and cannot be interchanged The compressor is an electrical as well as mechanical device E...

Page 33: ...s Puron R 410A refrigerant which has higher operating pressures than R 22 and other refrigerants No other refrigerant may be used in this system Gauge set hoses andrecoverysystemmustbe designedto hand...

Page 34: ...dip tube charge Puron units with cylinder in upright position and a commercial metering device in manifold hose Charge refrigerant into suction line TROUBLESHOOTING Use the Troubleshooting Guides See...

Page 35: ...restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrig...

Page 36: ...n of the indoor evaporator fan motor Ensure that the supply air temperature rise is in accordance with the range on the unit nameplate Clean or replace filters Flame sense fault LED 3 flashes The IGC...

Page 37: ...N IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR C...

Page 38: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 08 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48EZ 0...

Reviews: