background image

29

f. Connect 5 pin plug and 4 pin plug to indoor blower

motor.

g. Reinstall blower access panel (see Fig. 19).

3. Restore electrical power to unit. Start unit and check for

proper blower rotation and motor speeds during heating and

cooling cycles.

Integrated 
Gas Unit
Controller
(IGC)

Induced Draft
Motor

Rollout
Switch

Mounting 
Screw

Burner
Rack

Inducer
Blower
Housing

Flue
Collector 
Box

Interface Fan
Board (IFB)

Auto Transformer
fuses used on 460
volt units only.
(Hidden)

Fan Partition
Mounting
Bracket

A09193

Fig. 18 -- Blower Housing and Flue Collector Box

COMPRESSOR
ACCESS PANEL

BLOWER
ACCESS 
PANEL

CONTROL
ACCESS
PANEL

A09207

Fig. 19 -- Unit Access Panels

Induced Draft (combustion air) Blower Assembly

The induced--draft blower assembly consists of the inducer motor,
the blower housing, and the induced--draft blower wheel.
Clean periodically to assure proper airflow and heating efficiency.
Inspect blower wheel every fall and periodically during the heating

season. For the first heating season, inspect blower wheel

bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood assembly. Shine a

flashlight into opening to inspect wheel. If cleaning is required,
remove induced--draft blower assembly as follows:

1. Remove control access panel (See Fig. 19).
2. Remove the 5 screws that attach induced--draft blower as-

sembly to the flue collector box cover.

3. Slide the assembly out of the unit. (See 20). Clean the

blower wheel. If additional cleaning is required, continue
with Steps 4 and 5.

4. To remove blower wheel, remove 2 setscrews.
5. To remove inducer motor, remove screws that hold the

inducer motor to the blower housing.

6. To reinstall, reverse the procedure outlined above.

Flue Gas Passageways

To inspect the flue collector box and upper areas of the heat

exchanger:

1. Remove the induced draft blower assembly according to

directions in the Induced Draft Blower Assembly section.

2. Remove the 11 screws holding the flue collector box cover

(See Fig. 18) to the heat exchanger assembly. Inspect the
heat exchangers.

3. Clean all surfaces, as required, using a wire brush.

Limit Switch

Remove blower access panel (see Fig. 19). Limit switch is located

on the fan partition.

Burner Ignition

Unit is equipped with a direct spark ignition 100 percent lockout
system. Ignition module (IGC) is located in the control box (See

Fig. 18). Module contains a self--diagnostic LED. During

servicing, refer to label diagram or Table 5 in these instructions for
LED interpretation.
If lockout occurs, unit may be reset by either momentarily
interrupting power supply to unit or by turning selector switch to

OFF position at the thermostat.

Main Burners

At the beginning of each heating season, inspect for deterioration
or blockage due to corrosion or other causes. Observe the main

burner flames and adjust, if necessary.
Removal of Gas Train
To remove the gas train for servicing:

1. Shut off main gas valve.
2. Shut off power to unit and install lockout tag.
3. Remove control access panel (See Fig. 19).
4. Disconnect gas piping at unit gas valve.
5. Remove fan partition mounting bracket (2 screws located

on the left side of the control compartment on the fan parti-
tion panel). Slide bracket forward, bottom first, to remove
(See Fig. 18).

6. Remove wires connected to gas valve. Mark each wire.
7. Remove the mounting screw that attaches the burner rack to

the unit base (See Fig. 18).

8. Partially slide the burner rack out of the unit (see Fig. 18

and 21). Remove ignitor and sensor wires at the burner as-
sembly. Remove rollout switch wires.

9. Slide the burner rack out of the unit (See Fig. 18 and 21).

10. To reinstall, reverse the procedure outlined above.

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the outdoor coil, indoor coil, and condensate drain pan at

least once each year. The coils are easily cleaned when dry;

therefore, inspect and clean the coils either before or after each
cooling season. Remove all obstructions, including weeds and

shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,

clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or

grease, clean the coils with a mild detergent--and--water solution.

Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best

results, spray outdoor coil fins from inside to outside the unit. On
units with an outer and inner condenser coil, be sure to clean

between the coils. Be sure to flush all dirt and debris from the unit

base.
Inspect the drain pan and condensate drain line when inspecting

the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with

clear water. Do not splash water on the insulation, motor, wiring, or

air filter(s). If the drain tube is restricted, clear it with a “plumbers
snake” or similar probe device. Ensure that the auxiliary drain port

above the drain tube is also clear.

48E

Z

--

A

Summary of Contents for 48EZ(N) - A

Page 1: ...Limit Switch 29 Burner Ignition 29 Main Burners 29 Outdoor Coil Indoor Coil Condensate Drain Pan 29 A09034 Fig 1 Unit 48EZ A Outdoor Fan 30 Electrical Controls and Wiring 30 Refrigerant Circuit 30 Ga...

Page 2: ...ms against shipping list Immediately notify the nearest equipment distribution office if any item is missing To prevent loss or damage leave all parts in original packages until installation If the un...

Page 3: ...3 A09450 Fig 2 48EZ A24 36 Unit Dimensions 48EZ A...

Page 4: ...4 A09451 Fig 3 48EZ A42 60 Unit Dimensions 48EZ A...

Page 5: ...S 1 Roof curb must be set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 gauge steel 4 Attach ductwork to curb flanges of duct r...

Page 6: ...t recirculate to the condenser coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a normal house overhang is 48 in 1...

Page 7: ...verflowing Prime the trap with water Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap Do not undersize the tube Pitc...

Page 8: ...supply pipe within 6 ft 1 8 m of heating section 6 Install ground joint union close to heating section between unit manual shutoff and external manual main shut off valve 7 Pressure test all gas pipi...

Page 9: ...3 7 3 17 3 7 3 17 4 7 3 17 4 7 INDOOR BLOWER Nominal Cooling Airflow CFM Size in mm Motor hp 800 10x10 254x254 1 2 800 10x10 254x254 1 2 1000 10x10 254x254 1 2 1000 10x10 254x254 1 2 1200 11x10 279x2...

Page 10: ...ceed 0 08 IN W C If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity Table 2 Maximum Gas Flow Capacity NOMINAL IRON PIPE SIZE IN INTERNAL...

Page 11: ...amage to the unit being installed When cutting duct panels do not contact or damage any internal components heat exchanger electric heat Do not use a saw blade that protrudes more than 1 in 25 mm into...

Page 12: ...y Knockout Basepan Downflow Vertical Return Knockout A09060 Fig 8 Supply and Return Duct Opening Return Duct Panels Return Supply Duct Panels from Underside of Base Alternate Method Supply Duct Panels...

Page 13: ...nd Fig 10 for reference when making high voltage connections Proceed as follows to complete the high voltage connections to the unit Single phase units 1 Run the high voltage L1 L2 and ground lead int...

Page 14: ...thstand a 30 sec overload or shorted secondary condition If an overload or short is present correct overload condition and check for blown fuse on gas control board or Interface Fan Board Replace fuse...

Page 15: ...before the time delay has expired 2 T2 energizes the compressor contactor via the High Pressure Switch HPS and Low Pressure Switch LPS The compressor and outdoor fan start Thermostat G energizes the...

Page 16: ...DERATE MULTIPLIER FACTOR 0 2000 0 610 0 1 00 2001 3000 610 914 8 12 0 90 3001 4000 315 1219 12 16 0 86 4001 5000 1220 1524 16 20 0 82 5001 6000 1524 1829 20 24 0 78 6001 7000 1829 2134 24 28 0 74 7001...

Page 17: ...ormal Operation An LED light emitting diode indicator is provided on the integrated gas unit controller IGC to monitor operation The IGC is located by removing the control access panel see Fig 19 Duri...

Page 18: ...abnormal condition exists somewhere in the cooling system such as insufficient airflow across either coil or both coils CAUTION Proceed as follows 1 Remove caps from low and high pressure service fit...

Page 19: ...wire from the LOW terminal on the interface fan board IFB See Fig 14 2 Determine correct normal cooling fan speed for unit and application Add the wet coil pressure drop in Table 8 to the system stati...

Page 20: ...WIRE COLOR EXTERNAL STATIC PRESSURE in W C 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 48EZ N A24040 30 60oF 17 33oC Low Blue CFM 754 650 538 429 Heating Rise oF 40 46 56 NA NA NA NA NA NA Heating Rise oC 22...

Page 21: ...665 538 451 Heating Rise oF 46 50 54 NA NA NA NA NA NA Heating Rise oC 25 28 30 NA NA NA NA NA NA Medium Red CFM 1088 1023 954 881 800 723 658 563 461 Heating Rise oF 41 43 47 50 NA NA NA NA NA Heatin...

Page 22: ...CFM 1345 1282 1235 1194 1140 1095 1027 974 921 Heating Rise oF 33 35 36 37 39 41 43 46 48 Heating Rise oC 18 19 20 21 22 23 24 25 27 Medium Red CFM 1505 1452 1413 1358 1323 1282 1234 1169 1130 Heating...

Page 23: ...nk CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104 Heating Rise oF 60 NA NA NA NA NA NA NA NA Heating Rise oC 33 NA NA NA NA NA NA NA NA Medium2 Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381 H...

Page 24: ...8 49 49 51 51 53 Heating Rise oC 25 26 26 26 27 27 28 29 29 Med High1 Orange CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785 Heating Rise oF 41 42 42 43 44 45 46 47 49 Heating Rise oC 23 23 23 24 24...

Page 25: ...25 A09068 Fig 15 208 230 1 60 Wiring Diagram Unit 48EZ A 48EZ A...

Page 26: ...26 A09209 Fig 16 208 230 3 60 Wiring Diagram Unit 48EZ A 48EZ A...

Page 27: ...27 A08019 Fig 17 Cooling Charging Table Subcooling 48EZ A...

Page 28: ...pect blower wheel bi monthly to determine proper cleaning frequency 4 Check electrical connections for tightness and controls for proper operation each heating and cooling season Service when necessar...

Page 29: ...Table 5 in these instructions for LED interpretation If lockout occurs unit may be reset by either momentarily interrupting power supply to unit or by turning selector switch to OFF position at the t...

Page 30: ...l controls and wiring annually Be sure to turn off the gas supply and then the electrical power to the unit Remove access panels see Fig 19 to locate all the electrical controls and wiring Check all e...

Page 31: ...supply and return air grilles are open and free from obstructions and that the air filter is clean When necessary refer to the Indoor Airflow and Airflow Adjustments section to check the system airfl...

Page 32: ...rigerant The compressor used in this product is specifically designed to operate with Puron R 410A refrigerant and cannot be interchanged The compressor is an electrical as well as mechanical device E...

Page 33: ...s Puron R 410A refrigerant which has higher operating pressures than R 22 and other refrigerants No other refrigerant may be used in this system Gauge set hoses andrecoverysystemmustbe designedto hand...

Page 34: ...dip tube charge Puron units with cylinder in upright position and a commercial metering device in manifold hose Charge refrigerant into suction line TROUBLESHOOTING Use the Troubleshooting Guides See...

Page 35: ...restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrig...

Page 36: ...n of the indoor evaporator fan motor Ensure that the supply air temperature rise is in accordance with the range on the unit nameplate Clean or replace filters Flame sense fault LED 3 flashes The IGC...

Page 37: ...N IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR C...

Page 38: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 08 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48EZ 0...

Reviews: