Field-Installed Accessories
Space Temperature Sensor (T--55)
The T-55 space temperature sensor (part no. 33ZCT55SPT) is a
field-installed accessory. The sensor is installed on a building
interior wall to measure room air temperature. The T-55 sensor also
includes an override button on the front cover to permit occupants
to override the Unoccupied Schedule (if programmed). The jumper
wire in the installer’s packet must be connected between R and W1
when using a T-55 device.
TB--T55--1
Sensor Input
. . . . . . .
TB--T55--2
Sensor Common
. . . . . . .
Space Temperature Sensor (T--56)
The T-56 space temperature sensor (part no. 33ZCT56SPT) is a
field-installed accessory. This sensor includes a sliding scale on the
front cover that permits an occupant to adjust the space temperature
set point remotely. The T-56 sensor also includes an override
button on the front cover to allow occupants to override the
unoccupied schedule (if programmed). The jumper wire in the
installer’s packet must be connected between R and W1 when
using a T-56 device.
TB--T55--1
Sensor Input
. . . . . . .
TB--T55--2
Sensor Common
. . . . . . .
TB--T55--3
Setpoint Offset Input
. . . . . . .
Space Temperature Sensor (T--58)
The T-58 space temperature sensor (part no. 33ZCT58SPT) is a
field-installed accessory. The T-58 sensor communicates with the
Comfort
Link
™
controller, providing space temperature, heating
and cooling set points, and mode operation information. The
jumper wire in the installer’s packet must be connected between R
and W1 when using a T-58 device.
Refer to the T-58 installation instructions for information on
installing and configuring the T-58 sensor.
Each T-58 sensor must have a unique address on the CCN. Each
T-58 sensor must also be configured with the address of the unit
control it is communicating to.
Space Temperature Sensor Averaging
See Fig. 53 for space temperature averaging with T-55 sensors
only. If the use of one T-56 sensor is required, refer to Fig. 54.
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...